– 13 –
2800 Series
Running Current
Cooling
- With unit in case and room front installed, operated for 10 minutes on HI-COOL.
Temperature Differential Cooling
- Unit must operate for one hour with thermostat at coldest setting prior
to measuring air temperatures.
7000 BTUH Units
9000 BTUH Units
12000 BTUH Units
15000 BTUH Units
Current/Temperature Check Data - Cooling Current in Amps
Air Temp
Condenser In
230V
Min Max
208V
Min Max
230V
Min Max
208V
Min Max
230V
Min Max
208V
Min Max
230V
Min Max
208V
Min Max
80°F
2.3
2.8
2.4
2.9
3.1
3.6
3.2
3.7
3.8
4.3
4.0
4.5
4.8
5.3
5.2
5.7
95°F
2.7
3.2
2.8
3.3
3.5
4.0
3.8
4.3
4.4
4.9
4.7
5.2
6.2
6.7
6.8
7.3
110°F
3.2
3.7
3.4
3.9
4.5
5.0
4.8
5.3
5.4
5.9
5.8
6.3
7.7
8.2
8.5
9.0
Temperature Differential Check Data - Evaporator Air Temp Out in °F
Evaporator
Air Temp In
230V
Min Max
208V
Min Max
230V
Min Max
208V
Min Max
230V
Min Max
208V
Min Max
230V
Min Max
208V
Min Max
70°F
45
50
44
49
40
44
39
43
42
46
41
45
39
43
37
41
80°F
55
60
53
58
57
61
56
60
53
57
53
57
48
52
46
50
90°F
61
66
62
67
64
68
63
67
59
63
61
65
56
61
54
59
230/208 VAC, 2800 Series Models
265 VAC, 2800 Series Models
7000 BTUH Units
9000 BTUH Units
12000 BTUH Units
15000 BTUH Units
Current/Temperature Check Data - Cooling Current in Amps
Air Temp
Condenser In
265V
Min Max
265V Min
Max
265V
Min Max
265V
Min Max
80°F
2.0
2.5
2.7
3.2
3.3
3.8
4.2
4.6
95°F
2.3
2.8
3.1
3.6
3.8
4.3
5.4
5.9
110°F
2.8
3.3
3.9
4.4
4.7
5.2
6.6
7.1
Temperature Differential Check Data - Evaporator Air Temp Out °F
Evaporator
Air Temp In
265V
Min Max
265V
Min Max
265V
Min Max
265V
Min Max
70°F
45
50
40
45
42
46
39
43
80°F
55
60
57
62
53
57
48
52
90°F
61
66
64
69
59
63
56
61