Controls
Additional controls are located
behind the room cabinet.
Access to the controls is obtained
by removing the room cabinet.
To remove the room cabinet,
grasp it at both sides, pull it out to
release it from the tabs. Then lift it
up and pull forward.
To replace the room cabinet,
position tabs at top of room cabinet
over the rail at top of chassis. Push
the room cabinet inward until it
snaps into place.
Ventilation Control
The ventilation
-
control lever is
located at the lower
left side of the unit,
behind the room
cabinet.
This knob is set
at CLOSE at the
factory. When in
this position, the
vent door is closed
and only indoor air is circulated
by the air conditioner.
Switching the knob to OPEN
opens the vent door to allow
outdoor air to enter the room.
However, leaving the vent door
OPEN reduces heating or cooling
effectiveness and increase
operating costs.
CLASS 2 REMOTE
CDC
BY
The CLASS 2 REMOTE and CDC terminals
are located behind a cover
above the
controls. To remove the plate,
remove and save the screws that hold the
plate to the unit.
IMPORTANT:
the wire connections are
completed, replace the plate to prevent
damage to the unit or personal
Fan Cycle Switch
This switch is set at
at
the factory to provide continuous
fan operation in cool or heat
modes. Leaving the switch in the
setting allows continuous
circulation of room air and
will result in a more balanced
temperature throughout the room.
If you want the fan to cycle on
and off with the compressor or
resistance heater, set the switch
at CYCLE.
Unit Power Switch
This switch controls power to the
cool, heat or fan modes. When set
at ON it allows the unit to operate
in the cool, heat or fan modes.
If this switch is set at OFF, the
unit will not operate in any modes
but the Freeze Sentinel will
still function.
Caution: The Unit Power Switch
Freeze Sentinel
The Freeze Sentinel sensor helps
prevent plumbing damage due to
sub-freezing temperatures—even
you have turned the operation
switch to STOP. The sensor
automatically turns on the heater
and fan if the room temperature
falls to about
You do not have to do anything to
activate the Freeze Sentinel. It will
work as long as power to the unit
has not been interrupted.
Remote Control
The unit may be controlled either
by the controls on the unit or by
changing the CONTROL switch to
REMOTE and connecting the unit
to a remote thermostat.
See Installation Instructions.
Central Desk
Control (CDC)
The unit may be connected to a
Central Desk Control system by
connecting the wires from the
central control system to the CDC
terminals located on the panel
behind the room cabinet. These
terminals may also be used an
interface for other systems used to
control the unit such as infrared
detectors, key-activated systems,
etc. The Freeze Sentinel remains in
an active mode to
protect
against low temperature damage
even though the unit may be OFF
at the central control location.
is
not a power disconnect. If
See Installation Instructions.
power must be disconnected from
the unit, remove the line cord plug
from the wall outlet, or remove the
fuses, or turn off the circuit
breakers at the power panel.
4