background image

4

 

 

PROFIBUS Master Module 

GFK-2739  

 

Important Product Information for this Release 

Release History 

Version 

Firmware Release 

Date 

Comments 

IC200BEM003-AA 

1.00 

March 2012 

Initial release 

Compatibility 

The PROFIBUS Master module requires the following programming software and CPU versions: 

Programmer software 

Proficy Machine Edition, version 7.0 with SIM7 or later 

VersaMax CPU version 

Requires IC200CPU005 or IC200CPUE05 firmware version 2.36 or later 

VersaMax PNS version 

Requires IC200PNS001/PNS002 firmware version 1.10 or later 

Rx3i PNC version 

Requires IC695PNC001 firmware version 1.10 or later 

Rx3i CPU version 

Requires IC695CPU320, CPU315, CPE305 or CPE310 firmware version 
7.13 or later 

 

Restrictions and Open Issues 

Subject 

Description 

RX3i PBS301 returns an error 
response to a VersaMax PBM 
configured at high baud rate 

If an RX3i PBS301 is configured with DPV1 enabled as PROFIBUS slave 
attached to a VersaMax PBM, and the baud rate is configured to 1.5M or 
greater, the RX3i PBS cannot respond to the DPV1 alarm acknowledge request 
quickly enough when it receives these request messages at a high rate. 

 

Reviews: