background image

2-64

UR SERIES – COMMUNICATIONS GUIDE

MEMORY MAP

CHAPTER 2: MODBUS COMMUNICATION

2

"

5A13

...Repeated for Phase Instantaneous 

Overcurrent 2

B30, C60, C70, 

D30, D60, F35, 

F60, L30, L60, 

L90, M60, N60, 

T60

5A26

...Repeated for Phase Instantaneous 

Overcurrent 3

"

5A39

...Repeated for Phase Instantaneous 

Overcurrent 4

B30, C60, C70, 

D60, F35, F60, 

L90, M60, N60, 

T60

5A4C

...Repeated for Phase Instantaneous 

Overcurrent 5

"

5A5F

...Repeated for Phase Instantaneous 

Overcurrent 6

C60, C70, D60, 

F35, F60, L90, 

M60, N60, T60

5A72

...Repeated for Phase Instantaneous 

Overcurrent 7

"

5A85

...Repeated for Phase Instantaneous 

Overcurrent 8

C70, F35, N60, 

T60

5A98

...Repeated for Phase Instantaneous 

Overcurrent 9

"

5AAB

...Repeated for Phase Instantaneous 

Overcurrent 10

"

5ABE

...Repeated for Phase Instantaneous 

Overcurrent 11

"

5AD1

...Repeated for Phase Instantaneous 

Overcurrent 12

Neutral Time Overcurrent (Read/Write Grouped Setting)

 

(1, 2, 4, or 6 Modules) 

B30, C60, C70, 

D30, D60, F35, 

F60, G30, G60, 

L30, L60, L90, 

T60

5B00

Neutral Time Overcurrent 1 Function

0 to 1

---

1

F102

0 (Disabled)

"

5B01

Neutral Time Overcurrent 1 Signal Source

0 to 5

---

1

F167

0 (SRC 1)

"

5B02

Neutral Time Overcurrent 1 Input

0 to 1

---

1

F122

0 (Phasor)

"

5B03

Neutral Time Overcurrent 1 Pickup

0 to 30

pu

0.001 F001

1000

"

5B04

Neutral Time Overcurrent 1 Curve

0 to 16

---

1

F103

0 (IEEE Mod 

Inv)

"

5B05

Neutral Time Overcurrent 1 Multiplier

0 to 600

---

0.01

F001

100

"

5B06

Neutral Time Overcurrent 1 Reset

0 to 1

---

1

F104

(Instantaneo

us)

"

5B07

Neutral Time Overcurrent 1 Block

0 to 4294967295

---

1

F300

0

"

5B09

Neutral Time Overcurrent 1 Target

0 to 2

---

1

F109

0 (Self-reset)

"

5B0A

Neutral Time Overcurrent 1 Events

0 to 1

---

1

F102

0 (Disabled)

"

5B0B

Reserved (6 items)

0 to 1

---

1

F001

0

B30, C60, C70, 

D30, D60, F35, 

F60, L30, L60, 

L90, T60

5B11

...Repeated for Neutral Time Overcurrent 2

B30, C60, C70, 

D60, F35, F60, 

L60, L90, T60

5B22

...Repeated for Neutral Time Overcurrent 3

"

5B33

...Repeated for Neutral Time Overcurrent 4

B30, C60, C70, 

F35, L90, T60

5B44

...Repeated for Neutral Time Overcurrent 5

Products

Address Register name

Range

Units

Step

Format

Default

Summary of Contents for UR series

Page 1: ...Digital Energy Product version 7 3x GE publication code 1601 0401 AB2 GEK 119629A UR Series Communications Guide 1601 0401 AB2 IISO9001 G N E I M L I U T L TE S I R G E D E R LISTED IND CONT EQ E8384...

Page 2: ...or registered trademarks of GE Multilin Inc The contents of this manual are the property of GE Multilin Inc This documentation is furnished on license and may not be reproduced in whole or in part wi...

Page 3: ...nction codes 2 4 2 2 2 Read actual values or settings function code 03 04h 2 4 2 2 3 Execute operation function code 05h 2 5 2 2 4 Store single setting function code 06h 2 5 2 2 5 Store multiple setti...

Page 4: ...ia SCL 3 162 3 10 1 Introduction 3 162 3 10 2 Configuration process 3 163 3 10 3 Configuration process with IED setup tool 3 164 3 10 4 IED Capability Description ICD file 3 165 3 10 5 Instantiated IE...

Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...

Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...

Page 7: ...r roles for example are explained in the Instruction Manual This chapter outlines general safety and technical support information 1 1 Products This document applies to the following UR products B30 B...

Page 8: ...ltage banks 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Auxiliary Undervoltage of voltage banks 3 3 3 3 3 3 3 3 3 3 3 3 3 B90 Breaker Failure of feeders from software option 24 24 B90 Bus Differential of zones from...

Page 9: ...Temperat ure monitor 1 Breaker Arcing Current I2t of current banks 2 if current banks 2 6 6 6 6 6 6 6 6 6 6 6 Breaker Control of elements 6 6 2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Breaker Switch of element...

Page 10: ...6 96 96 96 96 96 96 96 96 96 96 96 96 96 96 Contact Outputs Latching can be only 14 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 CT Fail of current banks 6 6 6 6 6 6 6 6 6 CT Trouble of zo...

Page 11: ...CT terminal 24 24 Energy Metering of elements 1 per source 6 6 6 6 6 6 6 6 6 6 6 6 Event Recorder 1024 events 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 FaultLocation of elements 1 per current bank 5 1 1 1...

Page 12: ...1 1 1 Flexlogic timers 32 FlexMath 1 Direct Analogs 32 32 Direct integers 16 16 Summato r 6 6 Frequency Rate of Change 4 4 4 4 4 4 4 4 Generator Unbalance 1 1 1 Generic Comparator 8 bit comparat or 6...

Page 13: ...ion 6 XSWI configura tion 24 IPv4 Routes 6 IEC 61850 Remote I O Fixed GOOSE GSSE GOOSE 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Remote devices 32 16 16 32 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 Remote DP...

Page 14: ...ons 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Modbus User Map 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Motor Acceleration Time 1 1 Motor Mechanical Jam 1 1 Motor Start Supervision 1 1 Negative Sequence Dire...

Page 15: ...Open Pole Detect 1 1 1 Oscillography 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Over Under Frequency Accumulation 1 1 1 Overfrequenc y 4 4 4 4 4 4 4 4 4 Phase Comparison 1 1 PhaseCurrent Unbalance of curre...

Page 16: ...ocol 1588 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Reduced Voltage Starting 1 1 Restricted Ground Fault of CT banks 0 if L90 has no inzone transfor mer 6 6 6 6 6 6 RRTD Protection 12 12 12 12 RTD Protect...

Page 17: ...r Ground 1 1 Switch 6 6 6 6 Synchrocheck 4 4 4 4 4 4 4 4 4 4 4 4 Synchrophas ors of PMUs software option 6 2 1 1 1 1 1 6 1 of Aggregat ors 4 2 1 1 1 1 1 4 1 Teleprotectio n I O 1 1 1 1 1 1 1 1 1 1 1 1...

Page 18: ...48 48 48 48 User Programmabl e Pushbuttons of pushbutt ons 16 for J L N T V Y software options 6 for vertical front panel 12 for others 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 control Push buttons 3 User...

Page 19: ...nt See the Instruction Manual for safety information 1 5 For further assistance For product support contact the information and call center as follows GE Digital Energy 650 Markland Street Markham Ont...

Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...

Page 21: ...that it never initiates communications It listens and responds to requests issued by a master computer A subset of Modbus RTU and Modbus TCP IP protocol format is supported that allows extensive monit...

Page 22: ...ion based on the packet but none respond to the master FUNCTION CODE This is one of the supported functions codes of the unit which tells the slave what action to perform See the Supported function co...

Page 23: ...p and parity ignored as one continuous binary number This number is first shifted left 16 bits and then divided by a characteristic polynomial 11000000000000101b The 16 bit remainder of the division i...

Page 24: ...codes 03h and 04h are therefore identical The following table shows the format of the master and slave packets in Modbus RTU Modbus TCP IP ADUs have a MBAP instead of slave address and CRC is in anot...

Page 25: ...of the master and slave packets in Modbus RTU Modbus TCP IP ADUs have a MBAP instead of slave address and CRC is in another stack layer The example shows a master device storing the value 200 at memo...

Page 26: ...rs sends a response packet to the master with the high order bit of the function code set to 1 The following table shows the format of the master and slave packets in Modbus RTU Modbus TCP IP ADUs hav...

Page 27: ...end of file Discard any bytes you have read beyond the indicated block size 4 If you need to re try a block read only the size of and block of data without reading the position The file pointer is on...

Page 28: ...files datalog cfg and datalog dat To read the entire data logger in ASCII COMTRADE format read the following files dataloga cfg and dataloga dat To limit the range of records to be returned in the COM...

Page 29: ...uct Information Read Only Written by Factory All 0010 Serial Number F203 0 0020 Manufacturing Date 0 to 4294967295 1 F050 0 0022 Modification Number 0 to 65535 1 F001 0 0040 Order Code F204 Order Code...

Page 30: ...08 0 Off 0411 Virtual Input 18 State 0 to 1 1 F108 0 Off 0412 Virtual Input 19 State 0 to 1 1 F108 0 Off 0413 Virtual Input 20 State 0 to 1 1 F108 0 Off 0414 Virtual Input 21 State 0 to 1 1 F108 0 Off...

Page 31: ...F108 0 Off 043D Virtual Input 62 State 0 to 1 1 F108 0 Off 043E Virtual Input 63 State 0 to 1 1 F108 0 Off 043F Virtual Input 64 State 0 to 1 1 F108 0 Off IEC103 Protocol Settings Read Write Setting A...

Page 32: ...ted for Binary Input 40 0624 Repeated for Binary Input 41 0628 Repeated for Binary Input 42 062C Repeated for Binary Input 43 0630 Repeated for Binary Input 44 0634 Repeated for Binary Input 45 0638 R...

Page 33: ...Input 92 06F4 Repeated for Binary Input 93 06F8 Repeated for Binary Input 94 06FC Repeated for Binary Input 95 0700 Repeated for Binary Input 96 IEC103 ASDU Settings Read Write Setting 4 Modules All 0...

Page 34: ...peated for IEC103 ASDU 3 0761 Repeated for IEC103 ASDU 4 IEC103 Commands Read Write Setting 32 Modules All 0780 IEC103 Command 1 FUN 0 to 255 1 F001 0 0781 IEC103 Command 1 INF 0 to 255 1 F001 0 0782...

Page 35: ...Repeated for Digital Counter 8 FlexStates Read Only All 0900 FlexState Bits 16 items 0 to 65535 1 F001 0 RxGOOSE Boolean Read Write Setting 128 Modules All 0912 RxGOOSE Boolean 1 Default State 0 to 3...

Page 36: ...OOSE Boolean 43 0968 Repeated for RxGOOSE Boolean 44 096A Repeated for RxGOOSE Boolean 45 096C Repeated for RxGOOSE Boolean 46 096E Repeated for RxGOOSE Boolean 47 0970 Repeated for RxGOOSE Boolean 48...

Page 37: ...lean 90 09C6 Repeated for RxGOOSE Boolean 91 09C8 Repeated for RxGOOSE Boolean 92 09CA Repeated for RxGOOSE Boolean 93 09CC Repeated for RxGOOSE Boolean 94 09CE Repeated for RxGOOSE Boolean 95 09D0 Re...

Page 38: ...alog Output 1 Value 0 to 65535 1 F600 0 1321 Direct Analog Output 1 Deadband 0 to 1000000000 0 001 F060 1000000 1323 Direct Analog Output 1 Trigger 0 to 4294967295 1 F300 0 1325 Direct Analog Input 1...

Page 39: ...or Direct Analog Input and Output 25 147E Repeated for Direct Analog Input and Output 26 148C Repeated for Direct Analog Input and Output 27 149A Repeated for Direct Analog Input and Output 28 14A8 Re...

Page 40: ...s 0 to 65535 1 F500 0 15C8 Direct Outputs Average Message Return Time 1 0 to 65535 ms 1 F001 0 15C9 Direct Outputs Average Message Return Time 2 0 to 65535 ms 1 F001 0 15CA Direct Inputs Outputs Unret...

Page 41: ...to 2 1 F134 2 n a 1626 Channel 1 Loop Delay 0 to 200 ms 0 1 F001 0 1627 Channel 2 Status 0 to 2 1 F134 2 n a 1628 Channel 2 Number of Lost Packets 0 to 65535 1 F001 0 1629 Channel 2 Local Loopback Sta...

Page 42: ...999 A 0 001 F060 0 16A2 Restricted Ground Current Magnitude 0 to 999999 999 A 0 001 F060 0 16A4 Repeated for Restricted Ground Fault 2 16A8 Repeated for Restricted Ground Fault 3 16AC Repeated for Re...

Page 43: ...Source 1 Ground Current Magnitude 0 to 999999 999 A 0 001 F060 0 1818 Source 1 Ground Current Angle 359 9 to 0 degrees 0 1 F002 0 1819 Source 1 Zero Sequence Current Magnitude 0 to 999999 999 A 0 001...

Page 44: ...ary Voltage Magnitude 0 to 999999 999 V 0 001 F060 0 1A22 Source 1 Auxiliary Voltage Angle 359 9 to 0 degrees 0 1 F002 0 1A23 Source 1 Zero Sequence Voltage Magnitude 0 to 999999 999 V 0 001 F060 0 1A...

Page 45: ...013 0 1C1B Source 1 Phase C Power Factor 0 999 to 1 0 001 F013 0 1C1C Reserved 4 items F001 0 1C20 Repeated for Source 2 B30 C60 C70 D60 F35 F60 G30 G60 L60 L90 M60 N60 T35 T60 1C40 Repeated for Sourc...

Page 46: ...E20 Repeated for Source 3 1E30 Repeated for Source 4 F35 N60 T60 1E40 Repeated for Source 5 1E50 Repeated for Source 6 Source Demand Peaks Read Only Non Volatile 4 or 6 Modules C60 F35 F60 L90 N60 T60...

Page 47: ...lashover 1 Status Closed C 0 to 4294967295 1 F300 0 219F Breaker Flashover 1 Voltage Pickup Level 0 to 1 5 pu 0 001 F001 850 21A0 Breaker Flashover 1 Voltage Difference Pickup Level 0 to 100000 V 1 F0...

Page 48: ...ctuals Read Only 6 Modules B90 21E8 Repeated for Bus Zone 2 continued Breaker Arcing Current Actual Values Read Only Non Volatile 2 4 or 6 Modules C60 D30 D60 F35 F60 L30 L60 L90 T35 T60 21E8 Breaker...

Page 49: ...Command F60 2240 Hi Z Clear Oscillography 0 to 1 1 F126 0 No 2241 Hi Z Oscillography Force Trigger 0 to 1 1 F126 0 No 2242 Hi Z Oscillography Force Algorithm Capture 0 to 1 1 F126 0 No 2243 Hi Z Rese...

Page 50: ...er Differential Phasor Ibd Angle 359 9 to 0 degrees 0 1 F002 0 230B Transformer Restraint Phasor Ibr Magnitude 0 to 30 pu 0 001 F001 0 230C Transformer Restraint Phasor Ibr Angle 359 9 to 0 degrees 0...

Page 51: ...e Angle 359 9 to 0 degrees 0 1 F002 0 2352 Fault 1 Phase A Current Magnitude 0 to 999999 999 A 0 001 F060 0 2354 Fault 1 Phase A Current Angle 359 9 to 0 degrees 0 1 F002 0 2355 Fault 1 Phase B Curren...

Page 52: ...ential Current IB Magnitude 0 to 999999 999 A 0 001 F060 0 2496 Differential Current IC Magnitude 0 to 999999 999 A 0 001 F060 0 2498 Local IA Angle 359 9 to 0 degrees 0 1 F002 0 2499 Local IB Angle 3...

Page 53: ...Differential 87L Second Harmonic Iad Magnitude 0 to 999999 999 A 0 001 F060 0 24CF Line Current Differential 87L Second Harmonic Ibd magnitude 0 to 999999 999 A 0 001 F060 0 24D1 Line Current Differen...

Page 54: ...60 0 2584 PMU 1 Phase A Current Angle 180 to 180 0 01 F002 0 2585 PMU 1 Phase B Current Magnitude 0 to 999999 999 A 0 001 F060 0 2587 PMU 1 Phase B Current Angle 180 to 180 0 01 F002 0 2588 PMU 1 Phas...

Page 55: ...ctual Value 0 to 4294967295 1 F003 0 2740 Direct Integer Input 9 Actual Value 0 to 4294967295 1 F003 0 2742 Direct Integer Input 10 Actual Value 0 to 4294967295 1 F003 0 2744 Direct Integer Input 11 A...

Page 56: ...illography Analog Values Read Only All 3012 Oscillography Number of Triggers 0 to 32767 1 F001 0 Fault Report Indexing Read Only Non Volatile C60 D30 D60 F35 F60 L30 L60 L90 3020 Number of Fault Repor...

Page 57: ...F001 0 3203 Block of Data from Requested File 122 items 0 to 65535 1 F001 0 Security Read Write Setting All 3280 Administrator Alphanumeric Password Setting F202 none Security Read Only All 328A Admin...

Page 58: ...arm 0 to 1 1 F102 1 Enabled 3337 Settings Lock Alarm 0 to 1 1 F102 1 Enabled 3338 Bypass Access 0 to 3 1 F628 0 Disabled 333A Serial Inactivity Timeout 1 to 9999 min 1 F001 1 Security Command Read Wri...

Page 59: ...matic Setting Function 0 to 2 1 F092 0 Disabled 3451 Phase Current Unbalance Ka Actual Value Read Only 0 1000 to 0 1000 0 000 1 F004 0 3453 Phase Current Unbalance Auto set Ka 0 to 1 1 F126 0 No 3454...

Page 60: ...3 Value 9999 999 to 9999 999 0 001 F004 0 34DA DCMA Inputs 14 Value 9999 999 to 9999 999 0 001 F004 0 34DC DCMA Inputs 15 Value 9999 999 to 9999 999 0 001 F004 0 34DE DCMA Inputs 16 Value 9999 999 to...

Page 61: ...F002 0 350A RTD Input 27 Value 32768 to 32767 C 1 F002 0 350B RTD Input 28 Value 32768 to 32767 C 1 F002 0 350C RTD Input 29 Value 32768 to 32767 C 1 F002 0 350D RTD Input 30 Value 32768 to 32767 C 1...

Page 62: ...ge 0 to 99 9999 pu 0 000 1 F003 0 3644 Voltage Differential 1 Bus Phase B Voltage 0 to 99 9999 pu 0 000 1 F003 0 3646 Voltage Differential 1 Differential Phase B Voltage 0 to 99 9999 pu 0 000 1 F003 0...

Page 63: ...o 65535 1 F001 1812 373D Secondary Accounting Port 0 to 65535 1 F001 1813 373F RADIUS Authentication Method 1 F619 0 EAP TTLS 3740 RADIUS Vendor ID 1 to 65535 1 F001 2910 3741 Authentication Timeout 0...

Page 64: ...9 0 1 F001 0 37A5 Frequency OOB Accumulator Band 6 Accumulation OvUnFrecAccActualBand_6 0 0 to 999 9 0 1 F001 0 37A6 Frequency OOB Accumulator Band 7 Accumulation OvUnFrecAccActualBand_7 0 0 to 999 9...

Page 65: ...T 1 Primary 1 to 65000 1 F001 1 3898 Remote Ground CT 1 Secondary 0 to 1 1 F123 0 1 A 3899 Remote Phase VT 1 Connection 0 to 1 1 F100 0 Wye 389A Remote Phase VT 1 Secondary 25 to 240 0 1 F001 664 389B...

Page 66: ...r Field Contact Input 29 3A3F Repeated for Field Contact Input 30 3A4A Repeated for Field Contact Input 31 3A55 Repeated for Field Contact Input 32 3A60 Repeated for Field Contact Input 33 3A6B Repeat...

Page 67: ...LO 3DCD Field Latching Output 1 Open 0 to 4294967295 1 F300 0 3DCF Field Latching Output 1 Close 0 to 4294967295 1 F300 0 3DD1 Field Latching Output 1 Events 0 to 1 1 F102 1 Enabled 3DD2 Field Latchi...

Page 68: ...ield Unit Transducers Read Write Setting 8 Modules All except B90 L60 3F40 Field Unit Transducer 1 Name 0 to 1 1 F205 TRD 1 3F46 Field Unit Transducer 1 Origin 0 to 24 1 F253 0 None 3F47 Field Unit Tr...

Page 69: ...Setting Auth 1 to 4294967295 1 F300 1 4031 Remote Setting Auth 0 to 4294967295 1 F300 1 4033 Access Auth Timeout 5 to 480 min 1 F001 30 User Display Invoke Read Write Setting All 4040 Invoke and Scrol...

Page 70: ...ms 0 001 F001 100 Remote RTD Communications Read Write Setting G60 M60 T60 407A RRTD Slave Address 1 to 254 1 F001 254 407B RRTD Baud Rate 0 to 4 1 F602 4 19200 Communications Read Write Setting All 4...

Page 71: ...r Factor Default Deadband 0 to 100000000 1 F003 30000 40BE DNP Other Default Deadband 0 to 100000000 1 F003 30000 40C0 DNP IIN Time Synchronization Bit Period 1 to 10080 min 1 F001 1440 40C1 DNP Messa...

Page 72: ...fault Variation 0 to 3 1 F523 0 1 4145 DNP Object 23 Default Variation 0 to 3 1 F523 0 1 4146 DNP Object 30 Default Variation 1 to 5 1 F001 1 4147 DNP Object 32 Default Variation 0 to 5 1 F525 0 1 414...

Page 73: ...B1 Daylight Savings Time DST Stop Hour 0 to 23 1 F001 2 Fault Report Commands Read Write Command C60 D30 D60 F35 F60 L30 L60 L90 41B2 Fault Reports Clear Data Command 0 to 1 1 F126 0 No Oscillography...

Page 74: ...24 4308 Repeated for User Programmable LED 25 430B Repeated for User Programmable LED 26 430E Repeated for User Programmable LED 27 4311 Repeated for User Programmable LED 28 4314 Repeated for User Pr...

Page 75: ...able RxGOOSE Off Function 0 to 1 1 F102 1 Enabled 4444 User Programmable First Ethernet Fail Function 0 to 1 1 F102 0 Disabled 4445 User Programmable Secondary Ethernet Fail Function 0 to 1 1 F102 0 D...

Page 76: ...Source 6 Power System Read Write Setting All except B90 C30 4600 Nominal Frequency 25 to 60 Hz 1 F001 60 4601 Phase Rotation 0 to 1 1 F106 0 ABC 4602 Frequency and Phase Reference 0 to 5 1 F167 0 SRC...

Page 77: ...rite Settings 6 Modules G30 T35 T60 4640 Transformer Winding 1 Source 0 to 5 1 F167 0 SRC 1 4641 Transformer Winding 1 Rated MVA 0 001 to 2000 MVA 0 001 F003 100000 4643 Transformer Winding 1 Nominal...

Page 78: ...1 F300 0 47DF Breaker 1 External Alarm 0 to 4294967295 1 F300 0 47E1 Breaker 1 Alarm Delay 0 to 65 535 s 0 001 F003 0 47E3 Breaker 1 Pushbutton Control 0 to 1 1 F102 0 Disabled 47E4 Breaker 1 Manual...

Page 79: ...No FlexCurves A and B Read Write Settings All except C30 N60 4910 FlexCurve A 120 items 0 to 655535 ms 1 F011 0 4988 FlexCurve B 120 items 0 to 655535 ms 1 F011 0 Modbus User Map Read Write Setting Al...

Page 80: ...Raw Field Data DC3 0 to 0 001 V 0 001 F002 0 4E1B Raw Field Data FCI States 2 items 0 to 1 1 F500 0 4E1D Raw Field Data SI States 0 to 1 1 F500 0 4E1E Raw Field Data SI Test States 0 to 1 1 F500 0 4E1...

Page 81: ...F102 0 Disabled 5414 Repeated for RTD Input 2 5428 Repeated for RTD Input 3 543C Repeated for RTD Input 4 5450 Repeated for RTD Input 5 5464 Repeated for RTD Input 6 5478 Repeated for RTD Input 7 548...

Page 82: ...5 items 0 to 65535 1 F001 0 5808 Repeated for FlexLogic Timer 2 5810 Repeated for FlexLogic Timer 3 5818 Repeated for FlexLogic Timer 4 5820 Repeated for FlexLogic Timer 5 5828 Repeated for FlexLogic...

Page 83: ...1 Target 0 to 2 1 F109 0 Self reset 5910 Phase Time Overcurrent 1 Events 0 to 1 1 F102 0 Disabled 5911 Reserved 3 items 0 to 1 1 F001 0 B30 C60 C70 D30 D60 F35 F60 L30 L60 L90 T35 T60 5914 Repeated fo...

Page 84: ...D30 D60 F35 F60 G30 G60 L30 L60 L90 T60 5B00 Neutral Time Overcurrent 1 Function 0 to 1 1 F102 0 Disabled 5B01 Neutral Time Overcurrent 1 Signal Source 0 to 5 1 F167 0 SRC 1 5B02 Neutral Time Overcurr...

Page 85: ...Neutral Instantaneous Overcurrent 3 5C33 Repeated for Neutral Instantaneous Overcurrent 4 B30 C60 C70 D60 F35 F60 L90 M60 T60 5C44 Repeated for Neutral Instantaneous Overcurrent 5 5C55 Repeated for Ne...

Page 86: ...0 G60 L30 L60 L90 M60 T60 5DA0 Ground Instantaneous Overcurrent 1 Function 0 to 1 1 F102 0 Disabled 5DA1 Ground Instantaneous Overcurrent 1 Signal Source 0 to 5 1 F167 0 SRC 1 5DA2 Ground Instantaneou...

Page 87: ...ltage Pickup 0 to 2 pu 0 01 F001 20 5E75 CT Fail 1 Pickup Delay 0 to 65 535 s 0 001 F001 1000 5E76 CT Fail 1 Target 0 to 2 1 F109 0 Self reset 5E77 CT Fail 1 Events 0 to 1 1 F102 0 Disabled 5E78 Repea...

Page 88: ...bled Frequency Out Of Band Accumulation Read Write Setting G30 G60 5F40 Frequency Out Of Band Accumulation Block 0 to 4294967295 1 F300 0 5F42 Frequency Out Of Band Accumulation Events Enable 0 to 1 1...

Page 89: ...5 seconds 0 01 F001 10 600D 87L Current Differential Key DTT 0 to 1 1 F102 1 Enabled 600E 87L Current Differential External Key DTT 0 to 4294967295 1 F300 0 6010 87L Current Differential Target 0 to 2...

Page 90: ...Target 0 to 2 1 F109 0 Self reset 608A Negative Sequence di dt FD Events 0 to 1 1 F102 0 Disabled Phase Comparison Rate of Change of Positive Sequence Current Settings Read Write Grouped Setting L60 6...

Page 91: ...0 to 4294967295 1 F300 0 60CB Supervision Element 0 to 4294967295 1 F300 0 60CD Infeed Pickup Delay 0 to 50 s 0 001 F001 0 60CE Infeed Reset Delay 0 to 50 s 0 001 F001 35 60CF Open Breaker Keying Pic...

Page 92: ...ts 0 to 1 1 F102 0 Disabled Transformer Hottest Spot Read Write Grouped Setting T60 6140 Transformer Hottest Spot Function 0 to 1 1 F102 0 Disabled 6141 Transformer Hottest Spot Pickup 50 to 300 C 1 F...

Page 93: ...Differential Break 1 1 to 2 pu 0 001 F001 2000 61C4 Percent Differential Break 2 2 to 30 pu 0 001 F001 8000 61C5 Percent Differential Slope 2 50 to 100 1 F001 100 61C6 Inrush Inhibit Function 0 to 2 1...

Page 94: ...0 to 655 35 s 0 01 F001 0 6222 Autoreclose 1 Add Delay 2 0 to 4294967295 1 F300 0 6224 Autoreclose 1 Delay 2 0 to 655 35 s 0 01 F001 0 6225 Reserved 4 items 0 to 0 001 0 001 F001 0 F35 F60 L30 6229 Re...

Page 95: ...6340 Bank Phase Overvoltage 1 Stage 3C Pickup 0 8 to 2 pu 0 001 F001 1200 6341 Bank Phase Overvoltage 1 Stage 4C Pickup 0 8 to 2 pu 0 001 F001 1050 6342 Bank Phase Overvoltage 1 Stage 1 Pickup Delay...

Page 96: ...Differential Function 0 to 1 1 F102 0 Disabled 6421 Stator Differential Pickup 0 05 to 1 pu 0 001 F001 100 6422 Stator Differential Slope 1 1 to 100 1 F001 10 6423 Stator Differential Slope 2 1 to 100...

Page 97: ...to 1 1 F102 0 Disabled 64E1 Bus Zone 1 Pickup 0 05 to 6 pu 0 001 F001 100 64E2 Bus Zone 1 Low Slope 15 to 100 1 F001 25 64E3 Bus Zone 1 Low Breakpoint 1 to 30 pu 0 01 F001 200 64E4 Bus Zone 1 High Slo...

Page 98: ...rse Reach 0 1 to 500 ohms 0 01 F001 5000 65C7 Power Swing Detect Reverse RCA 40 to 90 degrees 1 F001 75 65C8 Power Swing Detect Outer Limit Angle 40 to 140 degrees 1 F001 120 65C9 Power Swing Detect M...

Page 99: ...7 Thermal Model RTD 3 0 to 48 1 F151 0 NONE 6608 Thermal Model RTD 4 0 to 48 1 F151 0 NONE 6609 Thermal Model RTD 5 0 to 48 1 F151 0 NONE 660A Thermal Model RTD 6 0 to 48 1 F151 0 NONE 660B Motor Emer...

Page 100: ...Radius 1 0 1 to 300 ohm 0 01 F001 800 666E Loss Of Excitation UV Supervision Enable 1 0 to 1 1 F102 1 Enabled 666F Loss Of Excitation Pickup Delay 1 0 to 65 535 s 0 001 F001 50 6670 Loss Of Excitation...

Page 101: ...Disabled 66C1 Load Encroachment Source 0 to 5 1 F167 0 SRC 1 66C2 Load Encroachment Minimum Voltage 0 to 3 pu 0 001 F001 250 66C3 Load Encroachment Reach 0 02 to 250 ohms 0 01 F001 100 66C4 Load Encro...

Page 102: ...F167 0 SRC 1 Subharmonic Stator Ground Read Write Grouped Setting G60 6710 Subharmonic Stator Ground Function 0 to 1 1 F102 0 Disabled 6711 Subharmonic Stator Ground Stage 1 Pickup 1 to 20 kOhm 1 F001...

Page 103: ...673E Split Phase Protection Delay 0 to 65 535 s 0 001 F001 0 Bus Configuration Read Write Setting 6 Modules B90 673E Repeated for Bus Zone 5 Split Phase Protection Read Write Grouped Setting G30 G60...

Page 104: ...set 0 to 2 1 F609 0 Pole Curr OR Custom 6794 Start Timer Zone 2 Phase Input 1 0 to 4294967295 1 F300 0 6796 Start Timer Zone 2 Phase Input 2 0 to 4294967295 1 F300 0 6798 Start Timer Zone 2 Ground Inp...

Page 105: ...Write Setting D60 L90 6820 Hybrid POTT 1P Scheme Function 0 to 1 1 F102 0 Disabled 6821 Hybrid POTT 1P Permissive Echo 0 to 2 1 F199 0 Disabled 6822 Hybrid POTT 1P Rx Pickup Delay 0 to 65 535 s 0 001...

Page 106: ...ximum Number of Shots 1 to 4 1 F001 2 6862 Autoreclose Block Breaker 1 0 to 4294967295 1 F300 0 6864 Autoreclose Close Time Breaker 1 0 to 655 35 s 0 01 F001 10 6865 Autoreclose Breaker Manual Close 0...

Page 107: ...ocking Block 0 to 4294967295 1 F300 0 68A3 Directional Comparison Unblocking Permissive Echo 0 to 2 1 F199 0 Disabled 68A4 Directional Comparison Unblocking Echo Condition 0 to 4294967295 1 F300 0 68A...

Page 108: ...r Time Interval 1 to 300 min 1 F001 60 6922 Starts Per Hour Maximum Number of Starts 1 to 16 1 F001 3 6923 Starts Per Hour Block 0 to 4294967295 1 F300 0 6925 Starts Per Hour Target 0 to 2 1 F109 0 Se...

Page 109: ...6AF4 Undervoltage 1 Pickup Delay 0 to 65 535 s 0 001 F001 0 6AF5 Undervoltage 1 Reset Delay 0 to 65 535 s 0 001 F001 0 6AF6 Undervoltage 1 Block 0 to 4294967295 1 F300 0 6AF8 Undervoltage 1 Target 0 t...

Page 110: ...tion 18 6C6A Repeated for End of Fault Protection 19 6C77 Repeated for End of Fault Protection 20 6C84 Repeated for End of Fault Protection 21 6C91 Repeated for End of Fault Protection 22 6C9E Repeate...

Page 111: ...ed for Isolator 37 6E78 Repeated for Isolator 38 6E84 Repeated for Isolator 39 6E90 Repeated for Isolator 40 6E9C Repeated for Isolator 41 6EA8 Repeated for Isolator 42 6EB4 Repeated for Isolator 43 6...

Page 112: ...Terminal Voltage 6 6F5A Repeated for Terminal Voltage 7 6F5D Repeated for Terminal Voltage 8 6F60 Repeated for Terminal Voltage 9 6F63 Repeated for Terminal Voltage 10 6F66 Repeated for Terminal Volta...

Page 113: ...rminal Frequency Read Only B90 6FD0 Terminal Frequency 2 to 90 Hz 0 01 F001 0 6FD1 Terminal Tracking Frequency 2 to 90 Hz 0 01 F001 0 Breaker Failure Current Supervision Read Write Grouped Setting 24...

Page 114: ...1 Events 0 to 1 1 F102 0 Disabled 700A Phase Undervoltage 1 Measurement Mode 0 to 1 1 F186 0 Phase to Ground 700B Reserved 6 items 0 to 1 1 F001 0 7013 Repeated for Phase Undervoltage 2 7022 Repeated...

Page 115: ...7087 Reserved 10 items F001 0 7091 Repeated for Phase Distance Zone 2 70B2 Repeated for Phase Distance Zone 3 D30 D60 L90 T60 70D3 Repeated for Phase Distance Zone 4 70F4 Repeated for Phase Distance...

Page 116: ...340 Repeated for Breaker Failure 13 7370 Repeated for Breaker Failure 14 73A0 Repeated for Breaker Failure 15 73D0 Repeated for Breaker Failure 16 7400 Repeated for Breaker Failure 17 7430 Repeated fo...

Page 117: ...d Distance Zone 3 D30 D60 L90 T60 7196 Repeated for Ground Distance Zone 4 71B8 Repeated for Ground Distance Zone 5 Line Pickup Read Write Grouped Setting D30 D60 L60 L90 71E0 Line Pickup Function 0 t...

Page 118: ...1 50 7236 Neutral Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 90 7237 Neutral Directional Overcurrent 1 Reverse Pickup 0 006 to 30 pu 0 001 F001 50 7238 Neutral Directional O...

Page 119: ...Source 0 to 5 1 F167 0 SRC 1 7292 Breaker 1 Arcing Amp Init 0 to 4294967295 1 F300 0 7294 Breaker 1 Arcing Amp Init B 0 to 4294967295 1 F300 0 7296 Breaker 1 Arcing Amp Init C 0 to 4294967295 1 F300 0...

Page 120: ...nnect Switch 11 75F5 Repeated for Disconnect Switch 12 7614 Repeated for Disconnect Switch 13 7633 Repeated for Disconnect Switch 14 7652 Repeated for Disconnect Switch 15 7671 Repeated for Disconnect...

Page 121: ...768C Repeated for Instantaneous Overcurrent 15 7696 Repeated for Instantaneous Overcurrent 16 76A0 Repeated for Instantaneous Overcurrent 17 76AA Repeated for Instantaneous Overcurrent 18 76B4 Repeat...

Page 122: ...9 77E4 Repeated for Time Overcurrent 20 77F0 Repeated for Time Overcurrent 21 77FC Repeated for Time Overcurrent 22 7808 Repeated for Time Overcurrent 23 7814 Repeated for Time Overcurrent 24 Thermal...

Page 123: ...peated for Ohm Inputs 2 Phasor Measurement Unit Recorder Config Counter Command Read Write Command 1 2 4 or 6 Modules C60 D60 F60 G60 L30 L90 N60 T60 781A PMU 1 Recorder Clear Config Counter 0 to 1 1...

Page 124: ...003 60000 78C9 PMU 1 Test df dt 10 to 10 Hz s 0 01 F002 0 C60 N60 78CA Repeated for PMU 2 N60 78E6 Repeated for PMU 3 7902 Repeated for PMU 4 791E Repeated for PMU 5 793A Repeated for PMU 6 Validation...

Page 125: ...102 0 Disabled 7B21 Voltage Dependent Overload Minimum Motor Volts 60 to 99 1 F001 80 7B22 Voltage Dependent Overload Voltage Loss 0 to 4294967295 1 F300 0 7B24 VD Overload Stall Current at Minimum Vo...

Page 126: ...mable Pushbutton 1 Top Line F202 none 7B6B User Programmable Pushbutton 1 On Text F202 none 7B75 User Programmable Pushbutton 1 Off Text F202 none 7B7F User Programmable Pushbutton 1 Drop Out Time 0 t...

Page 127: ...kup 0 01 to 10 pu 0 01 F001 150 7E68 Hi Z Neutral OC Min Pickup 0 01 to 10 pu 0 01 F001 100 7E69 Hi Z Phase Rate of Change 1 to 999 A 2cycle 1 F001 150 7E6A Hi Z Neutral Rate of Change 1 to 999 A 2cyc...

Page 128: ...ion 0 to 4294967295 1 F300 0 Distance Actual Values Read Only D30 D60 G60 L60 L90 T60 7E94 AB Loop Resistance 2147483647 to 2147483647 ohm 1 F060 0 7E96 AB Loop Reactance 2147483647 to 2147483647 ohm...

Page 129: ...ouped Setting 3 Modules All except B90 C30 L30 N60 T35 7F00 Neutral Overvoltage 1 Function 0 to 1 1 F102 0 Disabled 7F01 Neutral Overvoltage 1 Signal Source 0 to 5 1 F167 0 SRC 1 7F02 Neutral Overvolt...

Page 130: ...90 Hz 0 01 F001 0 Generic Comparator Settings Read Write Setting 6 Modules N60 8010 Comparator 1 Function 0 to 1 1 F102 0 Disabled 8011 Comparator 1 Addition Subtraction Mode Operand 0 to 4294967295 1...

Page 131: ...0 0 81A0 Direct Analog Input 17 Value 0 to 2147483647 1 F060 0 81A2 Direct Analog Input 18 Value 0 to 2147483647 1 F060 0 81A4 Direct Analog Input 19 Value 0 to 2147483647 1 F060 0 81A6 Direct Analog...

Page 132: ...ted for Digitizer 5 Digitizer Actual Values Read Only 5 Modules N60 82A0 Digitizer 1 Output 127 to 127 1 F004 0 82A2 Digitizer 2 Output 127 to 127 1 F004 0 82A4 Digitizer 3 Output 127 to 127 1 F004 0...

Page 133: ...ion 0 to 4294967295 1 F003 0 846B EGD Slow Producer Exchange 1 Data Rate 500 to 1000 ms 50 F001 1000 846C EGD Slow Producer Exchange 1 Data Item 1 50 items 0 to 65535 1 F001 0 849E Reserved 50 items F...

Page 134: ...Breaker Failure 1 Breaker Status 1 Phase A 3P 0 to 4294967295 1 F300 0 8613 Breaker Failure 1 Breaker Status 2 Phase A 3P 0 to 4294967295 1 F300 0 8615 Breaker Failure 1 Breaker Test On 0 to 429496729...

Page 135: ...lement 1 Name F203 DigElement 1 8A09 Digital Element 1 Input 0 to 4294967295 1 F300 0 8A0B Digital Element 1 Pickup Delay 0 to 999999 999 s 0 001 F003 0 8A0D Digital Element 1 Reset Delay 0 to 999999...

Page 136: ...ated for Digital Element 42 8D9C Repeated for Digital Element 43 8DB2 Repeated for Digital Element 44 8DC8 Repeated for Digital Element 45 8DDE Repeated for Digital Element 46 8DF4 Repeated for Digita...

Page 137: ...ed for FlexElement 7 9093 Repeated for FlexElement 8 C70 F35 G30 G60 M60 N60 T35 T60 90A8 Repeated for FlexElement 9 90BD Repeated for FlexElement 10 90D2 Repeated for FlexElement 11 90E7 Repeated for...

Page 138: ...5 to 600 s 5 F001 5 926D RRTD RTD 1 Trip Reset Delay 5 to 600 s 5 F001 5 926E RRTD RTD 1 Trip Voting 0 to 13 1 F603 0 None 926F RRTD RTD 1 Block 0 to 4294967295 1 F300 0 9271 RRTD RTD 1 Open 0 to 2 1...

Page 139: ...d for Direct Input Output 2 9418 Repeated for Direct Input Output 3 9424 Repeated for Direct Input Output 4 9430 Repeated for Direct Input Output 5 943C Repeated for Direct Input Output 6 9448 Repeate...

Page 140: ...utput 47 9634 Repeated for Direct Input Output 48 9640 Repeated for Direct Input Output 49 964C Repeated for Direct Input Output 50 9658 Repeated for Direct Input Output 51 9664 Repeated for Direct In...

Page 141: ...t Input Output 94 9868 Repeated for Direct Input Output 95 9874 Repeated for Direct Input Output 96 FlexElement Actual Values Read Only 8 or 16 Modules All except B90 9900 FlexElement 1 Actual 2147483...

Page 142: ...70 F35 T60 9952 Repeated for Breaker Restrike 3 Teleprotection Inputs Outputs Commands Read Write Command All except B90 C70 L30 L90 9980 Teleprotection Clear Lost Packets 0 to 1 1 F126 0 No Teleprote...

Page 143: ...9B1B Capacitor Control 1 Trip 4 0 to 4294967295 1 F300 0 9B1D Capacitor Control 1 Trip 5 0 to 4294967295 1 F300 0 9B1F Capacitor Control 1 Trip 6 0 to 4294967295 1 F300 0 9B21 Capacitor Control Switc...

Page 144: ...Before Close 0 to 65 535 s 0 001 F001 1000 9C9E Automatic Voltage Regulator 1 Delay Before Open 0 to 65 535 s 0 001 F001 1000 9C9F Automatic Voltage Regulator 1 Block 0 to 4294967295 1 F300 0 9CA1 Aut...

Page 145: ...1 Function 0 to 1 1 F102 0 Disabled 9D51 Neutral Voltage Unbalance 1 Neutral Point Source 0 to 5 1 F167 0 SRC 1 9D52 Neutral Voltage Unbalance 1 Bus Source 0 to 5 1 F167 0 SRC 1 9D53 Neutral Voltage U...

Page 146: ...rent Unbalance 1 Inherent Factor B 0 1000 to 0 1000 0 000 1 F002 0 9DC5 Phase Current Unbalance 1 Inherent Factor C 0 1000 to 0 1000 0 000 1 F002 0 9DC6 Phase Current Unbalance 1 Stage 1A Pickup 0 001...

Page 147: ...tage 2A Pickup 0 001 to 1 000 pu 0 001 F001 20 9E4C Voltage Differential 1 Stage 3A Pickup 0 001 to 1 000 pu 0 001 F001 30 9E4D Voltage Differential 1 Stage 4A Pickup 0 001 to 1 000 pu 0 001 F001 40 9...

Page 148: ...peed 2 Alarm Pickup Delay 0 00 to 600 00 s 0 01 F001 200 9F0E Undercurrent Speed 2 Trip Pickup 0 10 to 0 95 FLA 0 01 F001 70 9F0F Undercurrent Speed 2 Trip Pickup Delay 0 00 to 600 00 s 0 01 F001 100...

Page 149: ...60 A070 POTT Scheme Function 0 to 1 1 F102 0 Disabled A071 POTT Permissive Echo 0 to 1 1 F102 0 Disabled A072 POTT Rx Pickup Delay 0 to 65 535 s 0 001 F001 0 A073 POTT Transient Block Pickup Delay 0 t...

Page 150: ...F207 none A0E7 Summator 1 Events 0 to 1 1 F102 0 Disabled A0E8 Summator 1 Per Unit Base 1 to 2000000 1 F004 1 A0EA Repeated for Summator 2 A114 Repeated for Summator 3 A13E Repeated for Summator 4 A1...

Page 151: ...s F001 0 A328 Repeated for Digital Counter 2 A350 Repeated for Digital Counter 3 A378 Repeated for Digital Counter 4 A3A0 Repeated for Digital Counter 5 A3C8 Repeated for Digital Counter 6 A3F0 Repeat...

Page 152: ...1 T Reset 0 to 1000 s 0 1 F001 10 A58A Volts Per Hertz 1 Voltage Mode 0 to 1 1 F186 0 Phase to Ground A58B Repeated for Volts Per Hertz 2 Volts Per Hertz Actuals Read Only 2 Modules G30 G60 T60 A5A0...

Page 153: ...to 2 1 F198 0 1 A80C POTT 1P Rx1 0 to 4294967295 1 F300 0 A80E POTT 1P Rx2 0 to 4294967295 1 F300 0 A810 POTT 1P Rx3 0 to 4294967295 1 F300 0 A812 POTT 1P Rx4 0 to 4294967295 1 F300 0 A814 POTT 1P Ta...

Page 154: ...F300 0 A877 Blocking 1 Scheme 1P Force Tx Stop 1 0 to 4294967295 1 F300 0 A879 Blocking 1 Scheme 1P Force Tx Stop 2 0 to 4294967295 1 F300 0 A87B Blocking 1 Scheme 1P Comm Bits 0 to 2 1 F198 0 1 A87C...

Page 155: ...1 Events 0 to 1 1 F102 0 Disabled A96A Repeated for Restricted Ground Fault 2 A974 Repeated for Restricted Ground Fault 3 A97E Repeated for Restricted Ground Fault 4 F60 G60 L90 T60 A988 Repeated for...

Page 156: ...log Input 25 AAAF Repeated for IEC 61850 GOOSE Analog Input 26 AAB6 Repeated for IEC 61850 GOOSE Analog Input 27 AABD Repeated for IEC 61850 GOOSE Analog Input 28 AAC4 Repeated for IEC 61850 GOOSE Ana...

Page 157: ...5 AF33 Repeated for IEC 61850 GGIO4 Analog Input 6 AF3A Repeated for IEC 61850 GGIO4 Analog Input 7 AF41 Repeated for IEC 61850 GGIO4 Analog Input 8 AF48 Repeated for IEC 61850 GGIO4 Analog Input 9 AF...

Page 158: ...000000000 to 1000000000000 0 001 F060 0 B212 Repeated for Received Analog 2 B214 Repeated for Received Analog 3 B216 Repeated for Received Analog 4 B218 Repeated for Received Analog 5 B21A Repeated fo...

Page 159: ...B30A Wattmetric Ground Fault 1 Curve 0 to 5 1 F236 0 Definite Time B30B Wattmetric Ground Fault 1 Multiplier 0 01 to 2 s 0 01 F001 100 B30C Wattmetric Ground Fault 1 Block 0 to 4294967295 1 F300 0 B30...

Page 160: ...ndications in GGIO1 8 to 128 8 F001 8 B402 IEC 61850 GGIO1 Indication FlexLogic operands 128 items 0 to 4294967295 1 F300 0 Contact Inputs Read Write Setting 96 Modules All BB00 Contact Input 1 Name F...

Page 161: ...for Contact Input 39 BC38 Repeated for Contact Input 40 BC40 Repeated for Contact Input 41 BC48 Repeated for Contact Input 42 BC50 Repeated for Contact Input 43 BC58 Repeated for Contact Input 44 BC6...

Page 162: ...BDB8 Repeated for Contact Input 88 BDC0 Repeated for Contact Input 89 BDC8 Repeated for Contact Input 90 BDD0 Repeated for Contact Input 91 BDD8 Repeated for Contact Input 92 BDE0 Repeated for Contac...

Page 163: ...for Virtual Input 30 BF98 Repeated for Virtual Input 31 BFA4 Repeated for Virtual Input 32 BFB0 Repeated for Virtual Input 33 BFBC Repeated for Virtual Input 34 BFC8 Repeated for Virtual Input 35 BFD...

Page 164: ...for Virtual Output 10 C180 Repeated for Virtual Output 11 C188 Repeated for Virtual Output 12 C190 Repeated for Virtual Output 13 C198 Repeated for Virtual Output 14 C1A0 Repeated for Virtual Output...

Page 165: ...Virtual Output 57 C2F8 Repeated for Virtual Output 58 C300 Repeated for Virtual Output 59 C308 Repeated for Virtual Output 60 C310 Repeated for Virtual Output 61 C318 Repeated for Virtual Output 62 C...

Page 166: ...anced Diagnostics Active 0 to 1 1 F126 0 No C436 Synchrophasor Feature Active 0 to 1 1 F126 0 No Mandatory Read Write Command All C437 Relay Reboot Command 0 to 1 1 F126 0 No C438 Save Volatile Data 0...

Page 167: ...01 0 Direct Input Output Settings Read Write Setting L30 L90 C500 Direct Input Default States 8 items 0 to 1 1 F108 0 Off C508 Direct Input Default States 8 items 0 to 1 1 F108 0 Off C510 Direct Outpu...

Page 168: ...ed for Direct Output 42 C67E Repeated for Direct Output 43 C681 Repeated for Direct Output 44 C684 Repeated for Direct Output 45 C687 Repeated for Direct Output 46 C68A Repeated for Direct Output 47 C...

Page 169: ...C714 Repeated for Direct Output 93 C717 Repeated for Direct Output 94 C71A Repeated for Direct Output 95 C71D Repeated for Direct Output 96 Reset Read Write Setting All C750 FlexLogic operand which i...

Page 170: ...Input 1 Events 0 to 1 1 F102 0 Disabled C894 Repeated for Direct Input 2 C898 Repeated for Direct Input 3 C89C Repeated for Direct Input 4 C8A0 Repeated for Direct Input 5 C8A4 Repeated for Direct Inp...

Page 171: ...eated for Direct Input 51 C95C Repeated for Direct Input 52 C960 Repeated for Direct Input 53 C964 Repeated for Direct Input 54 C968 Repeated for Direct Input 55 C96C Repeated for Direct Input 56 C970...

Page 172: ...1 CRC Alarm Threshold 1 to 1000 1 F001 10 CAD3 Direct Input Output Channel 1 CRC Alarm Events 0 to 1 1 F102 0 Disabled CAD4 Reserved 4 items 1 to 1000 1 F001 10 CAD8 Direct Input Output Channel 2 CRC...

Page 173: ...9 ctlModel Value 0 to 2 1 F001 1 D329 IEC 61850 GGIO2 CF SPCSO10 ctlModel Value 0 to 2 1 F001 1 D32A IEC 61850 GGIO2 CF SPCSO11 ctlModel Value 0 to 2 1 F001 1 D32B IEC 61850 GGIO2 CF SPCSO12 ctlModel...

Page 174: ...IO2 CF SPCSO38 ctlModel Value 0 to 2 1 F001 1 D346 IEC 61850 GGIO2 CF SPCSO39 ctlModel Value 0 to 2 1 F001 1 D347 IEC 61850 GGIO2 CF SPCSO40 ctlModel Value 0 to 2 1 F001 1 D348 IEC 61850 GGIO2 CF SPCS...

Page 175: ...te Device 1 StNum 0 to 4294967295 1 F003 0 D362 Remote Device 1 SqNum 0 to 4294967295 1 F003 0 D364 Repeated for Remote Device 2 D368 Repeated for Remote Device 3 D36C Repeated for Remote Device 4 D37...

Page 176: ...tact Output 6 D43A Repeated for Contact Output 7 D449 Repeated for Contact Output 8 D458 Repeated for Contact Output 9 D467 Repeated for Contact Output 10 D476 Repeated for Contact Output 11 D485 Repe...

Page 177: ...54 D70A Repeated for Contact Output 55 D719 Repeated for Contact Output 56 D728 Repeated for Contact Output 57 D737 Repeated for Contact Output 58 D746 Repeated for Contact Output 59 D755 Repeated for...

Page 178: ...0 T60 DC70 Synchrocheck 1 Function 0 to 1 1 F102 0 Disabled DC71 Synchrocheck 1 V1 Source 0 to 5 1 F167 0 SRC 1 DC72 Synchrocheck 1 V2 Source 0 to 5 1 F167 1 SRC 2 DC73 Synchrocheck 1 Maximum Voltage...

Page 179: ...3 PMU 1 Reserved 15 items 0 to 1 1 F001 0 C60 N60 DEB2 Repeated for PMU 2 N60 E0B0 Repeated for PMU 3 E2AE Repeated for PMU 4 E4AC Repeated for PMU 5 E6AA Repeated for PMU 6 Phasor Measurement Unit Ag...

Page 180: ...or PMU Aggregator 2 N60 E9E6 Repeated for PMU Aggregator 3 E9F5 Repeated for PMU Aggregator 4 Phasor Measurement Unit Recording Command Read Write Command 1 2 4 or 6 Modules C60 D60 F60 G60 L30 L90 N6...

Page 181: ...MU 5 EA97 Repeated for PMU 6 Phasor Measurement Unit Current Trigger Read Write Setting 1 2 4 or 6 Modules C60 D60 F60 G60 L30 L90 N60 T60 EAA4 PMU 1 Current Trigger Function 0 to 1 1 F102 0 Disabled...

Page 182: ...urement Unit Power Trigger Read Write Setting 1 2 4 or 6 Modules C60 D60 F60 G60 L30 L90 N60 T60 EB88 PMU 1 Power Trigger Function 0 to 1 1 F102 0 Disabled EB89 PMU 1 Power Trigger Active 0 25 to 3 pu...

Page 183: ...C00 Repeated for PMU 3 EC12 Repeated for PMU 4 EC24 Repeated for PMU 5 EC36 Repeated for PMU 6 Phasor Measurement Unit Network Reporting Configuration Read Write Setting C60 D60 F60 G60 L30 L90 N60 T6...

Page 184: ...kup ratio indicates the offset into the FlexCurve base address where the correspond ing time value is stored F013 POWER_FACTOR SIGNED 16 BIT INTEGER Positive values indicate lagging power factor negat...

Page 185: ...ded without Vn F094 ENUMERATION BANK OVERVOLTAGE CURVE TYPE 0 FlexCurve A 1 FlexCurve B 2 FlexCurve C 3 FlexCurve D F095 ENUMERATION REDUCED VOLTAGE START TRANSITION MODE 0 Current Only 1 Current or T...

Page 186: ...hasor 1 RMS F123 ENUMERATION CT SECONDARY 0 1 A 1 5 A F124 ENUMERATION LIST OF ELEMENTS Bitmask Curve shape Bitmask Curve shape 0 IEEE Mod Inv 9 IAC Inverse 1 IEEE Very Inv 10 IAC Short Inv 2 IEEE Ext...

Page 187: ...l Time Overcurrent 3 51 Neutral Time Overcurrent 4 B30 C60 C70 F35 L90 T60 52 Neutral Time Overcurrent 5 53 Neutral Time Overcurrent 6 Products Bit mas k Element C70 D30 D60 F60 G30 G60 L30 L60 L90 M6...

Page 188: ...Neutral Overvoltage 1 157 Neutral Overvoltage 2 158 Neutral Overvoltage 3 D30 D60 G60 L60 L90 T60 160 Phase Distance Zone 1 161 Phase Distance Zone 2 Products Bit mas k Element 162 Phase Distance Zone...

Page 189: ...aker Arcing Current 1 289 Breaker Arcing Current 2 C60 D60 F35 L90 T35 T60 290 Breaker Arcing Current 3 Products Bit mas k Element 291 Breaker Arcing Current 4 F35 T35 292 Breaker Arcing Current 5 293...

Page 190: ...ment 5 405 FlexElement 6 406 FlexElement 7 407 FlexElement 8 C70 F35 G30 G60 M60 N60 T35 T60 408 FlexElement 9 409 FlexElement 10 410 FlexElement 11 Products Bit mas k Element 411 FlexElement 12 412 F...

Page 191: ...Undervoltage 8 508 Undervoltage 9 509 Undervoltage 10 510 Undervoltage 11 511 Undervoltage 12 518 Bus 1 519 Bus 2 520 Bus 3 521 Bus 4 522 Bus 5 523 Bus 6 524 CT Trouble1 525 CT Trouble2 526 CT Troubl...

Page 192: ...616 Breaker Fail 9 617 Breaker Fail 10 618 Breaker Fail 11 619 Breaker Fail 12 620 Breaker Fail 13 621 Breaker Fail 14 622 Breaker Fail 15 623 Breaker Fail 16 624 Breaker Fail 17 625 Breaker Fail 18 6...

Page 193: ...46 738 Digital Element 47 739 Digital Element 48 C60 D60 F60 G60 L30 L90 N60 T60 740 Phasor Measurement Unit 1 Frequency C60 N60 741 Phasor Measurement Unit 2 Frequency N60 742 Phasor Measurement Unit...

Page 194: ...Measurement Unit 1 C60 N60 824 Phasor Measurement Unit 2 N60 825 Phasor Measurement Unit 3 826 Phasor Measurement Unit 4 827 Phasor Measurement Unit 5 828 Phasor Measurement Unit 6 C70 830 Bank phase...

Page 195: ...witch 8 B30 C60 C70 D60 F35 F60 G30 G60 L60 L90 M60 N60 T35 T60 928 Disconnect switch 9 929 Disconnect switch 10 930 Disconnect switch 11 931 Disconnect switch 12 Products Bit mas k Element 932 Discon...

Page 196: ...ed 1 Self Reset 2 Latched F139 ENUMERATION DEMAND CALCULATIONS 0 Thermal Exponential 1 Block Interval 2 Rolling Demand 998 Remote RTD Input 8 999 Remote RTD Input 9 100 0 Remote RTD Input 10 100 1 Rem...

Page 197: ...ll except B90 L60 24 Brick Trouble All 25 Field RTD Trouble 26 Field TDR Trouble 27 RxGOOSE Offline 28 Direct Device Offline 29 Maintenance Alert 30 Any Minor Error 31 Any Major Error 33 Maintenance A...

Page 198: ...line 23 Ethernet Port 4 Offline 24 Ethernet Port 5 Offline 25 Ethernet Port 6 Offline 26 Test Mode Isolated 27 Test Mode Forcible 28 Test Mode Disabled 29 Temperature Warning On 30 Temperature Warning...

Page 199: ...NG CONNECTION 0 Wye 1 Delta 2 Zig zag F164 ENUMERATION TRANSFORMER WINDING GROUNDING 0 Not within zone 1 Within zone F166 ENUMERATION AUXILIARY VT CONNECTION TYPE 0 Vn 1 Vag 2 Vbg 3 Vcg 4 Vab 5 Vbc 6...

Page 200: ...PUT WAVEFORMS F186 ENUMERATION MEASUREMENT MODE 0 Phase to Ground 1 Phase to Phase F187 ENUMERATION HI Z STATES F188 ENUMERATION HI Z CAPTURE TRIGGER TYPES F189 ENUMERATION INRUSH INHIBIT MODE 0 Per P...

Page 201: ...ters 16 Bits 1st Char MSB 2nd Char LSB F203 TEXT16 16 CHARACTER ASCII TEXT F204 TEXT80 80 CHARACTER ASCII TEXT F205 TEXT12 12 CHARACTER ASCII TEXT F206 TEXT6 6 CHARACTER ASCII TEXT F207 TEXT4 4 CHARAC...

Page 202: ...IO1 ST Ind2 stVal 255 GGIO1 ST Ind128 q 256 GGIO1 ST Ind128 stVal 257 MMXU1 MX TotW mag f 258 MMXU1 MX TotVAr mag f 259 MMXU1 MX TotVA mag f 260 MMXU1 MX TotPF mag f 261 MMXU1 MX Hz mag f 262 MMXU1 MX...

Page 203: ...X Hz mag f 336 MMXU3 MX PPV phsAB cVal mag f 337 MMXU3 MX PPV phsAB cVal ang f Value IEC 61850 GOOSE Tx dataset item 338 MMXU3 MX PPV phsBC cVal mag f 339 MMXU3 MX PPV phsBC cVal ang f 340 MMXU3 MX PP...

Page 204: ...mag f 427 MMXU5 MX A phsC cVal ang f 428 MMXU5 MX A neut cVal mag f 429 MMXU5 MX A neut cVal ang f Value IEC 61850 GOOSE Tx dataset item 430 MMXU5 MX W phsA cVal mag f 431 MMXU5 MX W phsB cVal mag f 4...

Page 205: ...GIO5 ST UIntIn2 q 514 GGIO5 ST UIntIn2 stVal 515 GGIO5 ST UIntIn3 q 516 GGIO5 ST UIntIn3 stVal 517 GGIO5 ST UIntIn4 q 518 GGIO5 ST UIntIn4 stVal 519 GGIO5 ST UIntIn5 q 520 GGIO5 ST UIntIn5 stVal 521 G...

Page 206: ...stVal 166 GGIO3 ST UIntIn1 q 167 GGIO3 ST UIntIn1 stVal 168 GGIO3 ST UIntIn2 q 169 GGIO3 ST UIntIn2 stVal 170 GGIO3 ST UIntIn3 q 171 GGIO3 ST UIntIn3 stVal 172 GGIO3 ST UIntIn4 q 173 GGIO3 ST UIntIn4...

Page 207: ...F246 ENUMERATION BRICK TRANSDUCER RANGE F247 ENUMERATION BRICK AC BANK ORIGIN 6 July 7 August 8 September 9 October 10 November 11 December Value Day 0 Sunday 1 Monday 2 Tuesday 3 Wednesday 4 Thursday...

Page 208: ...ENUMERATION BANK REDUNDANCY TYPE 0 None 1 Dependability Biased 2 Security Biased F262 ENUMERATION BRICK STATUS 0 Disabled 1 OK 2 Communications Trouble 3 Equipment Mismatch 4 Brick Trouble 12 U6 AC5 7...

Page 209: ...to 96 3 CONTACT INPUTS OFF 1 to 96 4 VIRTUAL INPUTS 1 to 32 6 VIRTUAL OUTPUTS 1 to 64 8 CONTACT OUTPUTS 10 CONTACT OUTPUTS VOLTAGE DETECTED 1 to 64 11 CONTACT OUTPUTS VOLTAGE OFF DETECTED 1 to 64 12 C...

Page 210: ...o 15 corresponding to input output state 49 to 64 if required The number of registers required is determined by the specific data item A bit value of 0 Off and 1 On 0 Off 1 On F501 UR_UINT16 LED STATU...

Page 211: ...5 Vaux 6 Vag 7 Vbg 8 Vcg F536 ENUMERATION AUTOMATIC VOLTAGE REGULATOR CONTROL MODE 0 Voltage 1 VAR F537 ENUMERATION AUTOMATIC VOLTAGE REGULATOR VAR OPEN MODE 0 Minimize uptime 1 Minimize number of op...

Page 212: ...OTING F552 ENUMERATION RTD INPUT OPEN Enumeration Filter 0 None 1 10Hz s 10Hz 2 10Hz s 20Hz 3 20Hz s 10Hz 4 20Hz s 20Hz 5 None Value Phasor Value Phasor 0 Off 8 Ig 1 Va 9 V1 2 Vb 10 V2 3 Vc 11 V0 4 Vx...

Page 213: ...zone transformer connection 0 None 1 0 lag 2 30 lag 3 60 lag 4 90 lag 5 120 lag 6 150 lag 7 180 lag 8 210 lag 9 240 lag 10 270 lag 11 300 lag 12 330 lag Enumeration Inrush inhibit mode 0 Disabled 1 Pe...

Page 214: ...ether the password has been set 1 Bit 0 Administrator password was set The list is continued for all other roles Engineer bit 2 Operator bit 3 Observer bit 3 F619 ENUMERATION RADIUS AUTHENTICATION MET...

Page 215: ...TION IEC 61850 CONTROL MODEL F634 ENUMERATION IEC 61850 CONTROL MODEL NORMAL SECURITY ONLY 0 Status only 1 Direct with normal security 2 SBO with normal security F635 ENUMERATION RS232 BAUD RATE 0 192...

Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...

Page 217: ...for configuration tools to understand each other s configuration files The standards can be obtained from the IEC http www iec ch The UR supports a large subset of the IEC 61850 features These are de...

Page 218: ...lay Functions block to the Abstract Communications Service Interface These signals are typically Boolean and numeric signals including FlexLogic operands FlexAnalog operands actual values and UR setti...

Page 219: ...defined set of signal values to one or more subscriber IEDs periodically and or whenever one of the signals undergoes a change of state or value This service is intended for trip and blocking signals...

Page 220: ...ch as ST status information or SP setting For instance the Single point status CDC which is named SPS requires data attributes stVal q and t and it allows certain data attributes concerned with the su...

Page 221: ...h addresses common issues for the containing logical device Logical devices can also contain as many logical nodes as desired UR devices have six logical devices with logical node instance names and c...

Page 222: ...ed to define which data attributes to include in a GOOSE message or a sampled value message or a report A dataset member can be either a functional constrained data attribute FCDA or a functional cons...

Page 223: ...he system gocbRef A reference to the control block object that controls message publishing datSet A reference to the dataset whose members are published goID A string that allows a user to assign an i...

Page 224: ...e is controlled by the TIME TO LIVE setting When any published member value changes state the GOOSE message is immediately sent with the new values Such a message is called an event message A short ti...

Page 225: ...ia RxGOOSE configuration pages The figure shows an example of an RxGOOSE configuration page which subscribes to the message generated by the TxGOOSE and dataset examples of the preceding sections of t...

Page 226: ...ent is lost unbuffered reports flush events not yet reported to the client while buffered reports retain buffer any events not yet reported and any subsequent events so that the interruption does not...

Page 227: ...ct Control with Normal Security an IEC 61850 Client can write to the Pos Oper structure The entire Pos Oper structure must be written in one MMS write transaction Pos Oper ctlVal determines whether th...

Page 228: ...at allows the UR and UR Setup to determine if a non GE tool has modified the first one Thus between the Public and Private elements a UR SCL file contains all of the device s settings in that single f...

Page 229: ...l Energy UR 7 31 on Thu Oct 1 8 56 15 2014 3 SCL xmlns http www iec ch 61850 2003 SCL xmlns xsi http www w3 org 2001 XMLSchema instance xsi schemaLocation http www iec ch 61850 2003 SCL SCL xsd versio...

Page 230: ...12 maxAttributes 64 13112 ReadWrite 13113 ConfReportControl max 34 13114 GetCBValues 13115 ReportSettings datSet Conf rptID Conf optFields Conf bufTime Conf trgOps Conf intgPd Conf 13116 GSESettings...

Page 231: ...e of the information model by specifying for each logical node its lnType for example see line 13127 earlier After the IED element there is a DataTypeTemplates element that contains LNodeType elements...

Page 232: ...SSD or SED files so they are not discussed further here see instead the documentation of the SCT ICD files for UR devices can be obtained a number of ways as follows An ICD file can be obtained direct...

Page 233: ...ver starting the configuration from the factory default values for each of several similar UR devices applications unnecessarily duplicates setting efforts In these cases it is more efficient to begin...

Page 234: ...e other additions changes can be tolerated on import but are not preserved on export If the configuration generated by the SCT in the SCD is complete the next step is to use it to program each of the...

Page 235: ...ine IEC 61850 screen sends a CID file to the UR EnerVista UR Setup can also generate a CID from a URS using the Create CID File option in the Offline Window area These CID files are the only ones sens...

Page 236: ...sic conformance statement Table 3 2 PICS for A profile support Table 3 3 PICS for T profile support 3 4 ACSI conformance statement 3 4 1 ACSI basic conformance statement The table contains the Abstrac...

Page 237: ...e comments M1 Logical device Yes M2 Logical node Yes M3 Data Yes M4 Data set Yes M5 Substitution M6 Setting group control Yes Reporting M7 Buffered report control Yes M7 1 sequence number Yes M7 2 rep...

Page 238: ...ociation IEC 61850 7 2 clause 8 S2 Associate Yes S3 Abort Yes S4 Release Yes Logical device IEC 61850 7 2 clause 9 S5 LogicalDeviceDirectory Yes Logical node IEC 61850 7 2 clause 10 S6 GetLogicalNodeD...

Page 239: ...tURCBValues Yes Logging IEC 61850 7 2 clause 17 Log control block S30 GetLCBValues S31 SetLCBValues Log S32 QueryLogByTime S33 QueryLogAfter S34 GetLogStatusValues Generic substation event model GSE G...

Page 240: ...uracy of internal clock SNTP IRIG B PTP T3 Supported TimeStamp resolution 1 s 2 20 s Name Description Beh The data object Beh is mandatory in every logical node The value of Beh stVal in LLN0 of the M...

Page 241: ...vice The Master logical device contains communications related logical nodes including GOOSE reports log and virtual inputs d This textual description is in every logical node When in a NamPlt data ob...

Page 242: ...vice to know that such a change has occurred you need to revise the value of configRev paramRev The configurable data attribute paramRev has a scope that includes the entire device and thus is modifie...

Page 243: ...sboClass SboClasses CF 0 operate once R operTimeout INT32U CF 0 R MltLev SPG R setVal BOOLEAN SP True R GoEna Port1 ENG PORT1 TxGOOSE ENABLE setting R setVal ENUMERATED SP PORT1 TxGOOSE ENABLE R C GoE...

Page 244: ...NG129 RP Unbuffered Report RptID Factory default is NULL R W C RptEna BOOLEAN RP Factory default is false R W Resv BOOLEAN RP Factory default is false R W DatSet ObjectReference RP Unbuffered Report D...

Page 245: ...fRev Factory default is false R C OpFlds PACKEDLIST BR Buffered Report OptFlds Factory default is 1 R W C OpFlds sequence number BOOLEAN Factory default is true C OpFlds report time stamp BOOLEAN Fact...

Page 246: ...del R W C sboTimeout INT32U CF 30000 R sboClass SboClasses CF 0 operate once R operTimeout INT32U CF 0 R GrAct SPS Not instantiated in C30 R stVal BOOLEAN ST SETTING GROUP ACT R BlkRef1 ORG Not instan...

Page 247: ...when ANY MAJOR ERROR On 2 when ANY MINOR ERROR On otherwise 1 R Proxy SPS Indicates if this LN is a proxy R stVal BOOLEAN ST R RsStat SPC Mapped to command CLEAR ALL RELAY RECORDS R Ctrl pulseConfig...

Page 248: ...RE operand R stVal BOOLEAN ST PTP FAILURE R RxGooseOf f SPS RxGOOSE OFF operand R stVal BOOLEAN ST RxGOOSE OFF R RrtdComFa il SPS RRTD COMM FAIL operand R stVal BOOLEAN ST RRTD COMM FAIL R SecEthFail...

Page 249: ...Status showing that Sim messages are being received and accepted for RxGOOSE R stVal BOOLEAN ST Status showing that really Sim messages are received and accepted R LastStNum INS Actual value RxGOOSE s...

Page 250: ...NT32 CF 2147483647 R stepSize INT32 CF 1 R units Unit CF R units SIUnit ENUMERATED 1 R units multiplier ENUMERATED 0 the code for a multiplier of 1 R InRef ORG RxGOOSE Member R setSrcRef ObjectReferen...

Page 251: ...nDur INT32U 0 indicates the duration is locally defined R pulseConfig offDur INT32U 0 R pulseConfig numPls INT32U 1 R ctlModel CtlModels CF GGIO2 CF SPCSO CTLMODEL R C sboTimeout INT32U CF 30000 R sbo...

Page 252: ...selected by setting ANALOG IN VALUE R mag AnalogueValue MX R mag f FLOAT32 The operand selected by setting ANALOG IN VALUE deadbanded R db INT32U CF ANALOG IN DB R W C zeroDb INT32U CF 0 R DbMax ASG...

Page 253: ...R vendor VISIBLE STRING255 DC Mapped to LPHD1 PhyNam vendor R swRev VISIBLE STRING255 DC Mapped to LPHD1 PhyNam swRev R configRev VISIBLE STRING255 DC Prot configRev The factory default value is the e...

Page 254: ...SUPV OP operand R general BOOLEAN ST BKRSUPV SUPV OP R OpHiSet ACT BKRSUPV HISET OP operand R general BOOLEAN ST BKRSUPV HISET OP R OpLoSet ACT BKRSUPV LOSET OP operand R general BOOLEAN ST BKRSUPV L...

Page 255: ...T OP C setting for setting group R setSrcRef ObjectReference SP BF AMP HISET OP C for group Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R...

Page 256: ...g f FLOAT32 BUS ZONE REST current magnitude R instCVal ang f FLOAT32 BUS REST current angle UR range 180 180 converted to 0 360 R cVal Vector MX R cVal mag f FLOAT32 instCVal mag f deadbanded R cVal a...

Page 257: ...ting group R setSrcRef ObjectReference SP EFP BREAKER OPEN for group Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C InRef 2 ORG EFP MANU...

Page 258: ...st Prot UR element B90 Undervoltage element function data obj data attribute Type FC UR Name Description R W C Str ACD UNDERVOLTAGE PKP operands R general BOOLEAN ST UNDERVOLTAGE PKP R dirGeneral ENUM...

Page 259: ...o the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C OpIn ACT BKR FAIL RETRIP operands R general BOOLEAN ST Re trip operand BKR FAIL RETRIP R phsA BOOLEA...

Page 260: ...d R stVal BOOLEAN ST BUS SAT R DifAClc WYE Phase differential currents R phs CMV R phs instCVal Vector MX R phs instCVal mag f FLOAT32 BUS DIFF I d magnitude in primary amps R phs instCVal ang f FLOAT...

Page 261: ...ence SP Source GoCB of input if via GOOSE R C LNName CmpOv0PTOV1 LDevice inst Prot UR element Compensated Overvoltage functions data obj data attribute Type FC UR Name Description R W C Str ACD COMP O...

Page 262: ...BLOCK Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C InRef1 ORG DUTT RX1 setting R setSrcRef ObjectReference SP DUTT RX1 Reference to th...

Page 263: ...ence SP BLOCK SCHEME RX1 Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C InRef2 ORG BLOCK SCHEME RX2 setting R setSrcRef ObjectReference...

Page 264: ...bjectReference SP BLK1 SCHME DIR REV2 Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C InRef11 ORG BLK1 SCHME DIR REV3 setting R setSrcRef...

Page 265: ...a GOOSE R C InRef07 ORG GND DIR O C REV setting R setSrcRef ObjectReference SP GND DIR O C REV Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOS...

Page 266: ...ANGE in Hz s R instMag AnalogueValue MX R instMag f FLOAT32 FREQUENCY RATE OF CHANGE R Mag AnalogueValue MX R mag f FLOAT32 FREQUENCY RATE OF CHANGE on deadband exception R units Unit CF R units SIUin...

Page 267: ...bj data attribute Type FC UR Name Description R W C Str ACD GROUND IOC PKP operand which indicates that Op operates when delay expires R general BOOLEAN ST GROUND IOC PKP R dirGeneral ENUMERATED ST 0...

Page 268: ...CHO COND setting R setSrcRef ObjectReference SP HYB POTT ECHO COND Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C InRef8 ORG HYB POTT W...

Page 269: ...Only instantiated in L90 R general BOOLEAN ST 87L TRIP 1P OP R RxTr1 ACT Only instantiated in L90 R general BOOLEAN ST logical OR of phsA phsB phsC R phsA BOOLEAN ST 87L DIFF RECVD DTT A R phsB BOOLEA...

Page 270: ...GPS FAIL R Blk SPS 87L DIFF BLOCKED operand which becomes On when the 87L function is blocked due to communication problems R stVal BOOLEAN ST 87L DIFF BLOCKED R BlkH SPS Only instantiated in L90 R s...

Page 271: ...with deadband R phs units Unit CF R phs units SIUnit ENUMERATED 5 the code for amps R phs units multiplier ENUMERATED 0 the code for a multiplier of 1 R phs db INT32U CF LinDfPDIF1 DifAClc phs db R W...

Page 272: ...ence SP Source GoCB of input if via GOOSE R C InRef 09 ORG DD CONTROL LOGIC setting of setting group R setSrcRef ObjectReference SP DD CONTROL LOGIC setting Reference to the data attribute to input R...

Page 273: ...0 360 R phs units Unit CF R phs units SIUnit ENUMERATED 5 the code for amps R phs units multiplier ENUMERATED 0 the code for a multiplier of 1 R phs db INT32U CF LinDf1MMXU1 A phs db R W C phs zeroDb...

Page 274: ...on phase current below 5 of nominal R stVal BOOLEAN ST LINE PICKUP I R UnV SPS LINE PICKUP UV PKP operand R stVal BOOLEAN ST LINE PICKUP UV PKP R LeoSt SPS LINE PICKUP LEO PKP operand R stVal BOOLEAN...

Page 275: ...EQ IOC PKP R dirGeneral ENUMERATED ST 0 the code for unknown R Op ACT NEG SEQ IOC OP operand R general BOOLEAN ST NEG SEQ IOC OP R Dpo SPS NEG SEQ IOC DPO operand R stVal BOOLEAN ST NEG SEQ IOC DPO R...

Page 276: ...ce to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C LNName NeuDocRDIR LDevice inst Prot UR element Neutral Directional Overcurrent element data obj...

Page 277: ...l ENUMERATED ST 0 the code for unknown It is unknown as the element is non directional R Op ACT NEUTRAL OV OP operand R general BOOLEAN ST NEUTRAL OV OP R Dpo SPS NEUTRAL OV DPO operand which is the i...

Page 278: ...R phsA BOOLEAN ST POTT TRIP A R phsB BOOLEAN ST POTT TRIP B R phsC BOOLEAN ST POTT TRIP C R Tr3p ACT POTT TRIP 3P operand R general BOOLEAN ST POTT TRIP 3P R Tx1 SPS POTT TX1 operand R stVal BOOLEAN...

Page 279: ...RG POTT1 SCHEME BLOCK setting R setSrcRef ObjectReference SP POTT1 SCHEME BLOCK Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C InRef5 OR...

Page 280: ...ST PUTT TRIP 3P R Tx1 SPS PUTT TX1 operand R stVal BOOLEAN ST PUTT TX1 R Tx2 SPS PUTT TX2 operand R stVal BOOLEAN ST PUTT TX2 R Tx3 SPS PUTT TX3 operand R stVal BOOLEAN ST PUTT TX3 R Tx4 SPS PUTT TX4...

Page 281: ...Prot UR element Phase Distance Z settings data obj data attribute Type FC UR Name Description R W C Str ACD PHS DIST Z PKP operand in Phase To Phase R general BOOLEAN ST PH DIST Z PKP R dirGeneral ENU...

Page 282: ...individual three phases R general BOOLEAN ST PHASE IOC OP R phsA BOOLEAN ST PHASE IOC OP A R phsB BOOLEAN ST PHASE IOC OP B R phsC BOOLEAN ST PHASE IOC OP C R Dpo SPS PHASE IOC DPO operand R stVal BO...

Page 283: ...ption R W C Str ACD PHASE TOC PKP operands including individual three phases which indicates that Op operates when delay expires R general BOOLEAN ST PHASE TOC PKP R dirGeneral ENUMERATED ST 0 the cod...

Page 284: ...sC BOOLEAN ST PHASE UV PKP C R dirPhsC ENUMERATED ST 0 the code for unknown It is unknown as the element is non directional R Op ACT PHASE UV OP operand including individual three phases R general BOO...

Page 285: ...ObjectReference SP Source GoCB of input if via GOOSE R C BlkRef ORG POWER SWING BLK setting for setting group R setSrcRef ObjectReference SP POWER SWING BLK Reference to the data attribute to input R...

Page 286: ...bute Type FC UR Name Description R W C Str ACD DIR POWER PKP operand which becomes On when either stage 1 or stage 2 of this element has picked up R general BOOLEAN ST DIR POWER PKP R dirGeneral ENUME...

Page 287: ...ional Power element stage 2 functions data obj data attribute Type FC UR Name Description R W C Str ACD DIR POWER STG2 PKP operand which becomes On when the directional power comparator has operated R...

Page 288: ...perands R general BOOLEAN ST XFMR INST DIFF OP R phsA BOOLEAN ST XFMR INST DIFF OP A R phsB BOOLEAN ST XFMR INST DIFF OP B R phsC BOOLEAN ST XFMR INST DIFF OP C R BlkRef ORG INST DIFF BLOCK setting fo...

Page 289: ...F PctDifPDIF1 DifAClc phs db R W C phs zeroDb INT32U CF R angRef ENUMERATED CF See UR product manual regarding FREQUENCY AND PHASE REFERENCE R DifA2ndH WYE Phase differential currents R phs CMV R phs...

Page 290: ...HASOR UR range 180 180 converted to 0 360 R phs units Unit CF R phs units SIUnit ENUMERATED 5 the code for amps R phs units multiplier ENUMERATED 0 the code for a multiplier of 1 R phs db INT32U CF Pc...

Page 291: ...rand R stVal BOOLEAN ST TRIP AR INIT 3 POLE R Tr3pFrcd SPS TRIP FORCE 3 POLE operand 3 pole trip mode is being forced R stVal BOOLEAN ST TRIP FORCE 3 POLE R StrZ2PhDl SPS TRIP Z2PH TMR INIT operand R...

Page 292: ...ng Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C InRef08 ORG TRIP FORCE 3 POLE setting R setSrcRef ObjectReference SP TRIP FORCE 3 POLE...

Page 293: ...operand R stVal BOOLEAN ST SRC VT FUSE FAIL DPO R Alm1 SPS SRC VT FF ALARM R stVal BOOLEAN ST SRC VT FF ALARM R VSigLos SPS SRC VT FUSE FAIL VOL LOSS operand R stV al BOOLEAN ST SRC VT FUSE FAIL VOL...

Page 294: ...tribute Type FC UR Name Description R W C NamPlt LPL Logical node Prot configuration information R vendor VISIBLE STRING255 DC Mapped to LPHD1 PhyNam vendor R swRev VISIBLE STRING255 DC Mapped to LPHD...

Page 295: ...element Selected values from Fault Report Data file data obj data attribute Type FC UR Name Description R W C FltZ CMV Mandatory data attribute which in this case is fixed at zero R cVal Vector MX R...

Page 296: ...R stVal BOOLEAN ST AR ENABLED R Disabled SPS AR DISABLED operand R stVal BOOLEAN ST AR DISABLED R ArRip SPS AR RIP operand R stVal BOOLEAN ST AR RIP R P1Rip SPS AR 1 P RIP operand R stVal BOOLEAN ST...

Page 297: ...attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C InRef03 ORG Mode 3 Activation setting R setSrcRef ObjectReference SP AR Mode 3 Activation setting Reference to...

Page 298: ...input if via GOOSE R C InRef15 ORG AR BKR CLOSED setting R setSrcRef ObjectReference SP AR BKR CLOSED setting Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of i...

Page 299: ...ivLivDpo SPS SYNC SYNC DPO operand which indicates that one or both sources are not live or that angle frequency and voltage difference and range conditions have been met R stVal BOOLEAN ST SYNC SYNC...

Page 300: ...ia GOOSE R C LNName ThmOvlPTTR LDevice inst Ctrl UR element THERMAL OVERLOAD PROTECTION element data obj data attribute Type FC UR Name Description R W C Op ACT THERMAL PROT OP operand R general BOOLE...

Page 301: ...setSrcRef ObjectReference SP AR REDUCE MAX TO 2 setting Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C InRef04 ORG AR REDUCE MAX TO 3 s...

Page 302: ...tMag f FLOAT32 AGING FACTOR R mag Analogue Value MX R mag f FLOAT32 instMag i on deadband exception R units Unit CF R units SIUnit ENUMERATED 1 R units multiplier ENUMERATED 0 is multiplier for 1 R db...

Page 303: ...Device inst Ctrl UR element Loss of Life Function data obj data attribute Type FC UR Name Description R W C Op ACT XFMR LIFE LOST OP operands R general BOOLEAN ST XFMR LIFE LOST OP R Str ACD XFMR LIFE...

Page 304: ...jectReference SP LOSS OF LIFE BLOCK for group Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C LNName LLN0 LDevice inst System data obj da...

Page 305: ...rl stVal CODED ENUM ST Bkr0XCBR Pos stVal R stSeld BOOLEAN ST The controllable data status is selected R pulseConfig PulseConfig CF R pulseConfig cmdQual ENUMERATED 0 pulse R pulseConfig onDur INT32U...

Page 306: ...ase trip BREAKER TRIP A BREAKER TRIP B and BREAKER TRIP C operands R general BOOLEAN ST BREAKER OFF CMD R phsA BOOLEAN ST BREAKER TRIP A R phsB BOOLEAN ST BREAKER TRIP B R phsC BOOLEAN ST BREAKER TRIP...

Page 307: ...boClass SboClasses CF 0 operate once R operTimeout INT32U CF 0 R BlkCls SPC Blocks breaker close commands from all sources R Ctrl stVal BOOLEAN ST R pulseConfig PulseConfig CF R pulseConfig cmdQual EN...

Page 308: ...e Bkr XCBR LDevice inst System UR element Breaker Control element data obj data attribute Type FC UR Name Description R W C Loc SPS Value of operand selected by setting XCBR ST LOC OPERAND R stVal BOO...

Page 309: ...ption R W C Ind1 SPS Concatenation of value of CONTACT INPUT ID On operand value R stVal BOOLEAN ST Cont Ip On R Ind2 SPS Concatenation of value of CONTACT INPUT ID Off operand value R stVal BOOLEAN S...

Page 310: ...Config onDur INT32U 2 ms actually one pass R pulseConfig offDur INT32U 0 R pulseConfig numPls INT32U 1 R ctlModel CtlModels CF DiscCSWI Pos ctlModel R W C sboTimeout INT32U CF DiscCSWI Pos sboTimeout...

Page 311: ...LEAN ST 2 R OpOpn ACT SWITCH OFF CMD open operand R general BOOLEAN ST SWITCH OFF CMD R OpCls ACT SWITCH ON CMD close operand R general BOOLEAN ST SWITCH ON CMD R BadSt1 SPS SWITCH BAD STATUS operand...

Page 312: ...stent R pulseConfig onDu r INT32U 0 R pulseConfig offDur INT32U 0 R pulseConfig numPls INT32U 0 R ctlModel CtlModels CF Disc0XSWI BlkCls ctlModel R W C sboTimeout INT32U CF 30000 R sboClass SboClasses...

Page 313: ...ENUMERATED 1 the code for dimensionless R units multiplier ENUMERATED 0 the code for a multiplier of 1 R SwTyp ENS Disconnect switch type fixed at 2 Disconnector R stVal BOOLEAN ST 2 R BadSt1 SPS SWIT...

Page 314: ...e SP Source GoCB of input if via GOOSE R C InRef2 ORG SWITCH A 3P OPND setting if 1 SWITCH B OPND setting if 2 or SWITCH C OPND setting if 3 R setSrcRef ObjectReferenc e SP SWITCH A 3P OPND if 1 SWIT...

Page 315: ...iplier of 1 R db INT32U CF MMXU TotW DEADBAND R W C zeroDb INT32U CF Power cut off level R TotVAr MV SRC Three Phase Reactive Power in primary VAr R instMag AnalogueValue MX R instMag f FLOAT32 SRC Th...

Page 316: ...sVC scaleFactor FLOAT32 1 1000 R sVC offset FLOAT32 0 R PFSign ENG Sign convention for power factor PF is fixed at Lead Lag usually named IEEE R setVal ENUMERATED SG 2 the code for Lead Lag usually na...

Page 317: ...the code for primary volts W A R phsAB units multiplier ENUMERATED 0 the code for a multiplier of 1 R phsAB db INT32U CF MMXU PPV phsAB DEADBAND R W C phsAB zeroDb INT32U CF Voltage cut off level R ph...

Page 318: ...R phsCA units Unit CF R phsCA units SIUnit ENUMERATED 29 the code for primary volts W A R phsCA units multiplier ENUMERATED 0 the code for a multiplier of 1 R phsCA db INT32U CF MMXU PPV phsCA DEADBA...

Page 319: ...R units multiplier ENUMERATED 0 the code for a multiplier of 1 R db INT32U CF MMXU RMS PPV phsCA DEADBAND R W C zeroDb INT32U CF Voltage cut off level R P h V PhV WYE SRC Phase Voltage phasors in prim...

Page 320: ...or FLOAT32 1 10 R phsB angSVC offset FLOAT32 0 R phsC CMV R phsC instCVal Vector MX R phsC instCVal ma g f FLOAT32 SRC Phase CG Voltage Magnitude R phsC instCVal an g i INT32 SRC Phase CG Voltage Angl...

Page 321: ...Phase BG Voltage RMS R mag AnalogueValue MX R mag f FLOAT32 instMag f deadbanded R units Unit CF R units SIUnit ENUMERATED 29 the code for primary volts W A R units multiplier ENUMERATED 0 the code fo...

Page 322: ...R phsA angSVC ScaledValue Config CF R phsA angSVC scaleFactor FLOAT32 1 10 R phsA angSVC offset FLOAT32 0 R phsB CMV R phsB instCVal Vector MX R phsB instCVal ma g f FLOAT32 SRC Phase B Current Magnit...

Page 323: ...ctor FLOAT32 1 10 R phsC angSVC offset FLOAT32 0 R res CMV R res instCVal Vector MX R res instCVal mag f FLOAT32 SRC Neutral Current Magnitude R res instCVal ang i INT32 SRC Neutral Current Angle UR r...

Page 324: ...ultiplier of 1 R db INT32U CF MMXU RMS A phsB DEADBAND R W C zeroDb INT32U CF Current cut off level R AcRMS MV SRC Phase C Current RMS in primary amperes R instMag AnalogueValue MX R instMag f FLOAT32...

Page 325: ...ERATED CF See UR product manual regarding FREQUENCY AND PHASE REFERENCE R W WYE SRC Phase Real Power in primary watts R phsA CMV R phsA instCVal Vector MX R phsA instCVal ma g f FLOAT32 SRC Phase A Re...

Page 326: ...AT32 instCVal mag f deadbanded R phsA units Unit CF R phsA units SIUnit ENUMERATED 63 the code for primary volt amperes reactive VIsin R phsA units multiplier ENUMERATED 0 the code for a multiplier of...

Page 327: ...of 1 R phsA db INT32U CF MMXU VA phsA DEADBAND R W C phsA zeroDb INT32U CF Power cut off level R phsB CMV R phsB instCVal Vector MX R phsB instCVal ma g f FLOAT32 SRC Phase B Apparent Power R phsB cV...

Page 328: ...aleFactor FLOAT32 1 1000 R phsA magSVC offset FLOAT32 0 R phsB CMV R phsB instCVal Vector MX R phsB instCVal ma g i INT32 SRC Phase B Power Factor R phsB cVal Vector MX R phsB cVal mag i INT32 instCVa...

Page 329: ...ang i INT32 instCVal ang i deadbanded R units Unit CF R units SIUnit ENUMERATED 29 the code for primary volts W A R units multiplier ENUMERATED 0 the code for a multiplier of 1 R db INT32U CF MMXN Au...

Page 330: ...units SIUnit ENUMERATED 5 the code for primary amperes R units multiplier ENUMERATED 0 the code for a multiplier of 1 R db INT32U CF MMXN RMS GndCur DEADBAND R W C zeroDb INT32U CF Current cut off le...

Page 331: ...for a multiplier of 1 R c3 db INT32U CF MSQI Seq0 Cur DEADBAND R W C c3 zeroDb INT32U CF Current cut off level R seqT ENUMERATED MX 0 the code for pos neg zero R phsRef ENUMERATED CF 0 the code for p...

Page 332: ...nits multiplier ENUMERATED 0 the code for a multiplier of 1 R c3 db INT32U CF MSQI Seq0 V DEADBAND R W C c3 zeroDb INT32U CF Voltage cut off level R seqT ENUMERATED MX 0 the code for pos neg zero R ph...

Page 333: ...NCY R Mag AnalogueValue MX R mag f FLOAT32 instMag i deadbanded R Q Quality MX See document IMD Quality R units Unit CF R units SIUnit ENUMERATED 33 the code for hertz 1 s R units multiplier ENUMERATE...

Page 334: ...2 instMag f deadbanded R units Unit CF R units SIUnit ENUMERATED 5 the code for primary amperes R units multiplier ENUMERATED 0 the code for a multiplier of 1 R db INT32U CF DmdMtrMMTR AaDmd db R C ze...

Page 335: ...amperes with associated date SRC DMD IC DATE R instMag AnalogueValue MX R instMag f FLOAT32 SRC DMD IC MAX R mag AnalogueValue MX R mag f FLOAT32 instMag f deadbanded R units Unit CF R units SIUnit E...

Page 336: ...parent power in volt ampere R units multiplier ENUMERATED 0 the code for a multiplier of 1 R db INT32U CF DmdMtrMMTR VArMaxDmdDt db R C zeroDb INT32U CF Power cut off level R VADmd MV SRC DMD VA in pr...

Page 337: ...nit CF R units SIUnit ENUMERATED 72 the code for real energy in watt hours Wh R units multiplier ENUMERATED 0 the code for a multiplier of 1 R db INT32U CF EnrMtrMMTR NegTotWh db R W C PosTotVArh MV S...

Page 338: ...f1 ORG CLEAR ENERGY setting R setSrcRef ObjectReference SP setting reference to clear Energy which shows the receiving of dynamically clearing signal for energy calculation Reference to the data attri...

Page 339: ...g R setSrcRef ObjectReference SP DATA LOGGER TRIGGER setting Reference to the data attribute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C LNName DigCntFCNT LDevice in...

Page 340: ...bute to input R C setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R C InRef6 ORG COUNTER FREEZE COUNT setting R setSrcRef ObjectReference SP COUNTER FREEZE COUNT setting Reference to the...

Page 341: ...g R mag AnalogueValue MX R mag f FLOAT32 FLEXELEMENT OpSig on deadband exception R units Unit CF R units SIUnit ENUMERATED 1 the code for dimensionless per unit R units multiplier ENUMERATED 0 the cod...

Page 342: ...ctReference SP Source GoCB of input if via GOOSE R C InRef2 ORG Non Volatile Latch LATCH RESET setting R setSrcRef ObjectReference SP Non Volatile Latch RESET setting Reference to the data attribute t...

Page 343: ...once R operTimeout INT32U CF 0 R LNName SelSwGAPC LDevice inst Gen UR element Selector Switch element data obj data attribute Type FC UR Name Description R W C IndY SPS SELECTOR POS Y operand value R...

Page 344: ...RMS ACsrcMMXU AbDmd MV Phase B demand DmdMtrMMTR AbMaxDmdDt MV Phase B Max Demand with Date time stamp The ClcMth cannot be used for MAX as the time stamp definition of IEC 61850 is different from UR...

Page 345: ...spectively PctDifPDIF1 Blk5thH1 SPS Indicates fifth harmonic blocking active where the last digit of instance number 1 2 or 3 refers to phase A B and C respectively PctDifPDIF1 BlkH1 SPS The second ha...

Page 346: ...PTUV B_IocPIOC B_EfpPIOC B_TocPTOC B_UvPTUV BusDifPDIF CmpOvPTOV DigElGAPC FlxElGAPC GndIocPIOC GndTocPTOC HPTmpSPTR1 LinPkpPIOC NegIocPIOC NegOvPTOV NegTocPTOC NeuIocPIOC NeuTocPTOC NeuOvPTOV OvHzPTO...

Page 347: ...terminal corresponding to instance number LinDfPDIF GrAct1 SPS Setting group corresponding to index is active Master LLN0 not in C30 HzChgRte MV Frequency rate of change measured value RteHzPFRC Id1...

Page 348: ...orresponding RxGOOSE analog input FlexAnalog quantity to normalize it to a per unit quantity GGIO3 OpBia ACT B90 Operate indicates the trip decision of a biased protection logic B_DifPDIF OpHiSet ACT...

Page 349: ...net failure LPHD SeqDlTmcs ING Time interval allowed for a single reclose shot Timing is started whenever reclose shot is initiated and is active until a breaker closed signal is sent Rec3pRREC Rec13p...

Page 350: ...f IEC 61850 is different from UR DmdMtrMMTR VArDmd MV Reactive power demand in VAR DmdMtrMMTR VArMaxDmdDt MV Max reactive power demand in VAR with associated date time stamp The ClcMth cannot be used...

Page 351: ...on 2003 export I16 Version 2007 export Yes Yes I17 Predefined data sets I18 Predefined control blocks Yes Yes I19 Substation bay template with IED part I110 Communication section with default address...

Page 352: ...Set to RO or to Conf able 46 I212 Support ldName on other IEDs 9 3 4 Yes Yes I213 Interpret input signal references to source control blocks 9 3 13 Yes Yes I214 Imports UTF 8 coding of XML Yes Yes II...

Page 353: ...OldData N Inconsistent N Inaccurate Source Y Process N Substituted Y Test N OperatorBlocked Sr2 1 2 Which status value ST quality bits are supported can be set by server Validity Y Good Y Invalid N Re...

Page 354: ...e the conditions Notes The VLAN tag may be removed by a Ethernet switch and shall not be checked The simulation flag shall always be checked Ed2 The ndsCom shall always be checked Ed2 Y destination MA...

Page 355: ...by trip Y Object not selected Edition 2 specific values Y Object already selected N No access authority N Ended with overshoot N Abortion due to deviation N Abortion by communication loss Y Blocked b...

Page 356: ...s ceases to respond What is the time server lost detection time On one time server Internal clock is used On all time servers Internal clock is used 50 seconds Tm3 1 2 How long does it take to take ov...

Page 357: ...es na 663 FCDA element cannot be a functionally constrained logical node Y 668 Autotransformer modeling Y 719 ConfDataSet maxAttributes definition is confusing Y 721 Log element name na 768 bType VisS...

Page 358: ...7 2 not in 8 1 Y 1127 Missing owner attribute in BTS and UTS na 1163 Old report in URCB Y 1202 GI not optional Y Part 7 3 697 Persistent command PulseConfig Y 698 Wrong case is BAC dB attribute na 722...

Page 359: ...InOv and LCCH OutOv InOv na 800 Misspelling in CSYN na 802 CCGR and Harmonized control authority na 808 Presence condition of ZMOT DExt and new Dos na 831 Setting of ConfRevNum in LGOS Y 838 Testing...

Page 360: ...t before the start of parsing of CID ICD file This is logged from mmsServer task Error parsing SCL file SCL file parsing error apply_private_settings Modbus address in hex Modbus address in decimal fo...

Page 361: ...he CID file The GOOSE subscription parsing is in progress at this stage g2_process_goose_extref scl_gcb_find fail IED IED name of publisher srcLDInst LDInst lnName lnName srcCBName srcCBName of extRef...

Page 362: ...hen the GGIO3 logical node is missing The GOOSE subscription parsing is in progress at this stage ERROR Inref to ExtRef conversion setSrcRef value This message is logged when there are no more extRefs...

Page 363: ...LGOS The GOOSE subscription parsing is in progress at this stage E3 2 0 ERROR GSEControl name GSEControl name attribute is too long This message is logged when the GSEControl name is longer than suppo...

Page 364: ...OSE subscription parsing is in progress at this stage E3 2 0 ERROR missing doName in InRef internal address of InRef in LGOS This message is logged when the doName is missing from InRef The GOOSE subs...

Page 365: ...d to dummy IED A dummy IED is created for each remote IED The GOOSE subscription parsing is in progress at this stage E3 2 0 ERROR Couldn t add LLN0 to the dummy ied This message is logged when LLN0 l...

Page 366: ...ion fails The GOOSE subscription parsing is in progress at this stage check_lgos_gocbref iedName or apName missing This message is logged when iedName or apName is missing in the LGOS logical node The...

Page 367: ...ported on this platform This message is logged when a 64 bit basic type is detected in the CID file INT64U not supported on this platform This message is logged when an unsigned 64 bit basic type is d...

Page 368: ...plicate logical device creation is requested due to configuration errors in the CID file Cannot find type lnType for logical node logical node This message is logged when lnType is not found for a log...

Page 369: ...error is detected when performing special conversion for Boolean or enumeration types Cannot convert DA or BDA Val data attribute value to data for data attribute attribute This message is logged when...

Page 370: ...his message is informational ERROR GGIO3 missing This message is logged when the logical node GGIO3 is missing from the local IED implying errors with the CID file Compare with the IID file and look f...

Page 371: ...ion that is currently active in the device and the backup copy is the last known good copy This message is logged when the working copy is corrupted and the configuration from the backup copy is ready...

Page 372: ...This message is logged when MinTime value conflicts are detected between the various gse sections of the specified IED Subnet section Conflict found for MaxTime in gse cbName This message is logged w...

Page 373: ...upported length dai_val_validate Val DAI value conversion for logical node DAI fixed name FAILED This message is logged when conversion of DAI value failed Attempt to change value of DAI DAI flattened...

Page 374: ...port control block name must be configured in Master LLN0 This message is logged when a report control is detected in a node other than Master LLN0 check_iec_report too many buffered ReportControl Thi...

Page 375: ...to insert reference DAI flattened name after new DAI flattened name After a reboot after sending a CID file we failed to add a missing DAI SCL_Node failed to add DAI DAI flattened name to end of list...

Page 376: ...s different from that in the reference file in the device NO LDevice logical device in IED IED name No logical devices were found in the IED section of the CID file NO LN prefix of logical node lnClas...

Page 377: ...erent number of BDA when compared to the reference in the device No BDA base data attribute found in DAType data attribute type in the new IED The base data attributes are missing the specified DAType...

Page 378: ...rovide for the GOOSE configuration process to begin with each IED providing the names of the outputs it can publish in an SCL file The SCL files at this stage have the file name extension icd an acron...

Page 379: ...Configuration process The figure shows the SCL file flow in the configuration process under this implementation model Figure 3 13 SCL file flow for IED configuration An ICD file is obtained from each...

Page 380: ...that is the SCD file the Configurator obtains and imports an IID an acronym for Instantiated IED Description file from the IED IID files contain a description of the capabilities of the IED and the v...

Page 381: ...s other than Private elements The values subject to these requirements include local that is non standard or native outputs that the IED is able to publish using means not defined in the standards For...

Page 382: ...s via GOOSE These inputs are modeled within the so called Public elements that is elements other than Private elements The inputs subject to these requirements include any which are able to receive va...

Page 383: ...any number of inputs to be modeled in a logical node using ORG data objects Where the input is a grouped setting there is to be one ORG data object for each group The first digit of the data object in...

Page 384: ...that the IED can support max 0 means the IED is only a GOOSE subscriber The Services element is not to contain a ClientServices element with element attribute called goose The IED element also contai...

Page 385: ...e that it is subscribing to has been reconfigured changing the outputs published As the IED is unaware of this it cannot be certain that the external object references given to it in a CID file contin...

Page 386: ...an ICD or IID file from the target IED the CID also contains one IED element for each IED that the target IED receives a GOOSE message from These other IED elements are to be identical to the IED ele...

Page 387: ...ch 61850 2003 SCL xmlns xsi http www w3 org 2001 XMLSchema instance xsi schemaLocation http www iec ch 61850 2003 SCL SCL xsd version 2007 revision A Header id ICD file for Acme Mini model 123 Communi...

Page 388: ...lnClass GGIO DO name InRef1 type ORG LNodeType LNodeType id LGOS lnClass LGOS DO name St type SPS DO name GoCBRef type ORG LNodeType DOType id ORG cdc ORG DA name setSrcRef fc SG dchg true bType ObjR...

Page 389: ...Proxy cdc SPS DA name stVal fc ST dchg true bType BOOLEAN Val false Val DA DA name q fc ST qchg true bType Quality DA name t fc ST bType Timestamp DOType EnumType id Beh EnumVal ord 1 on EnumVal Enum...

Page 390: ...name GOOSE1DS FCDA ldInst LD1 prefix lnClass PIOC lnInst 1 doName Op fc ST daName general DataSet GSEControl name GoCB1 datSet GOOSE1DS appID E1Q1BP1LD1_GOOSE1 LN0 LN lnClass LPHD inst 1 lnType LPHD L...

Page 391: ...edAP SubNetwork Communication IED name E1Q2BP1 Services GSESettings appID Conf cbName Conf datSet Conf GOOSE max 1 Services AccessPoint name S1 Server Authentication none true LDevice inst LD1 LN0 ins...

Page 392: ...rds require that logical nodes communicate with other logical nodes IEC 61850 7 1 Edition 2 0 2011 07 clause 9 6 That is to say from an application viewpoint the logical nodes and only the logical nod...

Page 393: ...s an ExtRef element and a data object Ind1 in the figure within the same logical node In devices that implement this feature the ICD file contains ExtRef elements each pre configured with the name of...

Page 394: ...d GOOSE Boolean input 1 intAddr Ind1 ExtRef desc unassigned GOOSE Analog input 1 intAddr AnIn1 Inputs LN LNodeType id ExtRefs lnClass GGIO DO name Ind1 type SPS DO name AnIn1 type MV LNodeType To spec...

Page 395: ...standard envisioned for SCL Except for being implemented under edition 1 0 of the standard Option B is the same as the G2 Implementation Model which is outlined later To satisfy customer preference UR...

Page 396: ...xplanation T LNName The name shall be composed of the class name the LN Prefix and LN Instance ID according to IEC 61850 7 2 Clause 22 Data objects Descriptions NamPlt LPL Name plate of the logical no...

Page 397: ...clause 6 1 2 3 referencing the publishing GOOSE control block except that if the publishing logical device uses function related naming that is its LDevice element contains an ldName attribute the LD...

Page 398: ...ibed GOOSE The first InRef wherein intAddr is the empty string marks the end of the GOOSE message Any following InRef are ignored The format of LGOS InRef intAddr references is the referenced logical...

Page 399: ...ries Relay Highest DNP level supported For Requests Level 2 For Responses Level 2 Device function Master Slave Notable objects functions and or qualifiers supported in addition to the Highest DNP Leve...

Page 400: ...t responses Sometimes Configurable Timeouts while waiting for Data Link Confirm None Fixed at ____ Variable Configurable Complete Appl Fragment None Fixed at ____ Variable Configurable Application Con...

Page 401: ...reset after one pass of FlexLogic The On Off times and Count value are ignored Pulse Off and Latch Off oper ations put the appropriate Virtual Input into the Off state Trip and Close operations both p...

Page 402: ...put Change with Relative Time 1 read 06 no range or all 07 08 limited quantity 10 0 Binary Output Status Variation 0 is used to request default variation 1 read 00 01 start stop 06 no range or all 07...

Page 403: ...ithout Flag 1 read 22 assign class 00 01 start stop 06 no range or all 07 08 limited quantity 17 28 index 129 response 00 01 start stop 17 28 index see Note 2 22 0 Counter Change Event Variation 0 is...

Page 404: ...e 00 01 start stop 17 28 index see Note 2 32 0 Analog Change Event Variation 0 is used to request default variation 1 read 06 no range or all 07 08 limited quantity 1 32 Bit Analog Change Event withou...

Page 405: ...Note 2 52 2 Time Delay Fine 129 response 07 limited quantity quantity 1 60 0 Class 0 1 2 and 3 Data 1 read 20 enable unsol 21 disable unsol 22 assign class 06 no range or all 1 Class 0 Data 1 read 22...

Page 406: ...3 13 cold restart No Object function code only 14 warm restart No Object function code only 23 delay meas Object Request Response Object no Variation no Description Function codes dec Qualifier codes...

Page 407: ...On Latch Off Paired Trip Paired Close BINARY INPUT POINTS Static Steady State Object Number 1 Change Event Object Number 2 Request Function Codes supported 1 read 22 assign class Static Variation rep...

Page 408: ...nput 25 25 Virtual Input 26 26 Virtual Input 27 27 Virtual Input 28 28 Virtual Input 29 29 Virtual Input 30 30 Virtual Input 31 31 Virtual Input 32 32 Virtual Input 33 33 Virtual Input 34 34 Virtual I...

Page 409: ...as negative values the maximum positive representation is 32767 for 16 bit values and 2147483647 for 32 bit values This is a DNP requirement BINARY COUNTERS Static Steady State Object Number 20 Change...

Page 410: ...ay settings are available to set default deadband values according to data type Deadbands for individual Analog Input Points can be set using DNP Object 34 Static Steady State Object Number 30 Change...

Page 411: ...60870 5 103 IEC 60870 5 1 Transmission frame formats IEC 60870 5 2 Link transmission procedures IEC 60870 5 3 General structure of application data IEC 60870 5 4 Definition and coding of application...

Page 412: ...x Xmin So Xt 8191 Xmax Xmin X 4096 Xmax Xmin Xmax Xmin We can further simplify the formula for situations where 1 Xmin Xmax positive and negative values Xt 8191 2 Xmax X a 4096 Xmax b 0 2 If Xmin 0 on...

Page 413: ...terrogation 0 Time synchronization 2 Reset FCB 3 Reset CU 4 Start restart 5 Power on Status indications in monitor direction INF Semantics 16 Auto recloser active 17 Teleprotection active 18 Protectio...

Page 414: ...Fault location X in ohms 74 Fault forward line 75 Fault reverse busbar 76 Teleprotection signal transmitted 77 Teleprotection signal received 78 Zone 1 79 Zone 2 80 Zone 3 81 Zone 4 82 Zone 5 83 Zone...

Page 415: ...rrogation 0 Time synchronization General commands in control direction INF Semantics 16 Auto recloser on off 17 Teleprotection on off 18 Protection on off 19 LED reset 23 Activate characteristic 1 24...

Page 416: ...INTEROPERABILITY DOCUMENT CHAPTER 5 IEC 60870 5 103 COMMUNICATION 5 Current L2 Current L3 Voltage L1 E Voltage L2 E Voltage L3 E Active power P Reactive power Q Frequency f Voltage L1 L2 Measurand max...

Page 417: ...pted from the IEC 60870 5 104 standard The boxes indicate the following used in standard direction not used cannot be selected in IEC 60870 5 104 standard 1 SYSTEM OR DEVICE System Definition Controll...

Page 418: ...Three Octets Unbalanced interchange circuit V 24 V 28 standard Unbalanced interchange circuit V 24 V 28 recommended if 1200 bits s Balanced interchange circuit X 24 X 27 100 bits sec 200 bits sec 300...

Page 419: ...lue M_ME_NC_1 14 Measured value short floating point value with time tag M_NE_TC_1 15 Integrated totals M_IT_NA_1 16 Integrated totals with time tag M_IT_TA_1 17 Event of protection equipment with tim...

Page 420: ...point command normalized value with time tag CP56Time2a C_SE_TA_1 62 Set point command scaled value with time tag CP56Time2a C_SE_TB_1 63 Set point command short floating point value with time tag CP...

Page 421: ...20 to 36 37 to 41 44 45 46 47 1 M_SP_NA_1 X X X X X 2 M_SP_TA_1 3 M_DP_NA_1 4 M_DP_TA_1 5 M_ST_NA_1 6 M_ST_TA_1 7 M_BO_NA_1 8 M_BO_TA_1 9 M_ME_NA_1 10 M_ME_TA_1 11 M_ME_NB_1 12 M_ME_TB_1 13 M_ME_NC_1...

Page 422: ...70 M_EI_NA_1 X 100 C_IC_NA_1 X X X X X 101 C_CI_NA_1 X X X 102 C_RD_NA_1 X 103 C_CS_NA_1 X X X 104 C_TS_NA_1 Type identification Cause of transmission No Mnemonic 1 2 3 4 5 6 7 8 9 10 11 12 13 20 to...

Page 423: ...bled are defined in a project specific list 105 C_RP_NA_1 X X 106 C_CD_NA_1 107 C_TS_TA_1 110 P_ME_NA_1 111 P_ME_NB_1 112 P_ME_NC_1 X X X 113 P_AC_NA_1 120 F_FR_NA_1 121 F_SR_NA_1 122 F_SC_NA_1 123 F_...

Page 424: ...cute setpoint command C_SE ACTTERM used No additional definition Short pulse duration duration determined by a system parameter in the outstation Long pulse duration duration determined by a system pa...

Page 425: ...ion of transmission delay Acquisition of transmission delay Definition of time outs Maximum range of values for all time outs 1 to 255 s accuracy 1 s Maximum number of outstanding I format APDUs k and...

Page 426: ...rds used in the Internet The suitable selection of documents from RFC 2200 defined in this standard for given projects has to be chosen by the user of this standard Ethernet 802 3 Serial X 21 interfac...

Page 427: ...ion AB1 English GEK publication number 1601 part number Firmware Release date ECO GEK 119629 1601 0401 AB1 7 3x 7 November 2014 14 1408 GEK 119629A 1601 0401 AB2 7 3x 1 September 2015 15 2215 Page Cha...

Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...

Page 429: ...2 122 Brick Modbus 2 60 Broken conductor detection Modbus 2 102 Broken rotor bar Modbus 2 128 Bus differential Modbus 2 27 2 33 2 77 Bus replica Modbus 2 90 C Capacitor control Modbus 2 44 2 123 Chan...

Page 430: ...vent recorder files explained for Modbus 2 8 Modbus registers 2 38 Exception responses 2 6 F Fault report Modbus 2 36 2 53 2 117 Features per product 1 1 Field unit Modbus 2 22 2 32 2 44 2 60 File for...

Page 431: ...al OC Modbus 2 98 Neutral IOC Modbus 2 65 Neutral overvoltage Modbus 2 109 Neutral TOC Modbus 2 64 Neutral voltage unbalance Modbus 2 39 2 42 2 125 Non volatile latches Modbus 2 132 Number of elements...

Page 432: ...hermal model Modbus 2 79 2 104 Thermal overload protection Modbus 2 102 Third harmonic neutral undervoltage Modbus 2 81 TICS conformance statement 3 141 Time between starts Modbus 2 88 Time of day tim...

Reviews: