CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-57
2
"
461B
Block GPS Time Reference
0 to 4294967295
---
1
F300
0
"
461D
Maximum Channel Asymmetry
0 to 10
ms
0.1
F001
15
"
461F
Round Trip Time
0 to 10
ms
0.1
F001
15
B90 Power System (Read/Write Setting)
B90
4627
Terminal Nominal Frequency
25 to 60
Hz
1
F001
60
"
4628
Terminal Reference
0 to 23
---
1
F400
0
"
462F
Terminal Frequency Tracking Function
0 to 1
---
1
F102
1 (Enabled)
Transformer General (Read/Write Setting)
G30, T35, T60
4630
Transformer Number of Windings
2 to 6
---
1
F001
2
"
4631
Transformer Phase Compensation
0 to 1
---
1
F160
0 (Internal
(software))
"
4632
Transformer Load Loss at Rated Load
1 to 20000
kW
1
F001
100
"
4633
Transformer Rated Winding Temperature
Rise
0 to 4
---
1
F161
1 (65°C (oil))
"
4634
Transformer No Load Loss
1 to 20000
kW
1
F001
10
"
4635
Transformer Type of Cooling
0 to 6
---
1
F162
0 (OA)
"
4636
Transformer Top-oil Rise Over Ambient
1 to 200
°C
1
F001
35
"
4637
Transformer Thermal Capacity
0 to 200
kWh/°C 0.01
F001
10000
"
4638
Transformer Winding Thermal Time
Constant
0.25 to 15
min
0.01
F001
200
"
4639
Transformer Reference Winding Manual
Selection
0 to 7
---
1
F470
0
(Auto. Selecti
on)
Transformer Windings (Read/Write Settings) (6 Modules)
G30, T35, T60
4640
Transformer Winding 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
4641
Transformer Winding 1 Rated MVA
0.001 to 2000
MVA
0.001 F003
100000
"
4643
Transformer Winding 1 Nominal Phase-
Phase Voltage
0.001 to 2000
kV
0.001 F003
220000
"
4645
Transformer Winding 1 Connection
0 to 2
---
1
F163
0 (Wye)
"
4646
Transformer Winding 1 Grounding
0 to 1
---
1
F164
0 (Not within
zone)
"
4647
Transformer Winding 1 Angle w.r.t. Winding
1
-359.9 to 0
degrees 0.1
F002
0
"
4651
Transformer Winding 1 Resistance
0.0001 to 100
ohms
0.000
1
F003
100000
"
4653
...Repeated for Transformer Winding 2
"
4666
...Repeated for Transformer Winding 3
"
4679
...Repeated for Transformer Winding 4
"
468C
...Repeated for Transformer Winding 5
"
469F
...Repeated for Transformer Winding 6
Incipient Cable Fault Detector (Read/Write Settings) (2 or 6 Modules)
F35, F60
46B2
Incipient Cable Fault Detector 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
46B3
Incipient Cable Fault Detector 1 Block
0 to 4294967295
---
1
F300
0
"
46B5
Incipient Cable Fault Detector 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
46B6
Incipient Cable Fault Detector 1 Pickup
0.1 to 10
pu
0.01
F001
50
"
46B7
Incipient Cable Fault Detector 1 Mode
0 to 1
---
1
F254
0 (Number of
Counts)
"
46B8
Incipient Cable Fault Detector 1 Counts
1 to 10
---
1
F001
2
"
46B9
Incipient Cable Fault Detector 1 Time
Window
0 to 1000
s
0.01
F003
1000
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...