Wire AC line to power supplies in accordance with 

the applicable local, state, and country electrical 

codes. Connect black to black or brown, white to 

white or blue, and green to green using 18 AWG 

(0.82mm

2

) wire connectors. 

Connect the red wire (+) of the LED system to 

the red wire (+) of the power supply. Connect 

the black wire (-) of the LED system to the black 

or blue wire (-) of the power supply.

NOTE:  All power supplies except GEPS12-180U must be installed in an enclosure or be provided with a GEPSJB60 

power supply extended enclosure. 
Interconnect multiple runs of Tetra Flexible Tape together using twist-on wire connectors or in-line (IDC) connectors. 

Join black wires (-) together and red wires (+) together.
NOTE: 
 Make sure not to exceed power supply power limits (see step 1 above).
NOTE: The UL Retrofit Classification is only applicable when retrofitting a listed sign.

AC line

Black to black 

or brown (-)

Green to green

White to white 

or blue (+)

Power supply

To Flexible Tape 

or Lead Connector Wires

Red (+)

Red (+)

Black (-)

Black or blue (-) 

1.  (Existing Signs Only) Prior to installation, survey the site for information regarding power and accessibility inside and outside the 

building. Ensure that the branch circuit supplying the existing transformer or ballast will be within the voltage ratings of the new LED 

power supply, and have a current rating not exceeding 20A, or that permitted by applicable local, state, or country electrical codes 

(whichever is less).   

2.  (Existing Signs Only) Remove the existing lighting equipment to be replaced, such as neon tubing or fluorescent tubes; and 

associated transformers and ballasts.  Care should be taken not to break the existing neon or fluorescent tubes. NOTE: Follow all 

federal and local regulations when disposing of neon tubing, fluorescent tubes, transformers and ballasts.

3.  (Existing Signs Only)  If removal of the existing lighting equipment eliminates the disconnect switch, as required by applicable local, 

state, or country electrical codes; a new disconnect switch must be installed.

4.  (Existing Signs Only) Repair and seal any unused openings in the electrical enclosure. Openings greater than 12.7-mm (1/2-in) 

diameter require a metal patch secured by screws or rivets and caulked with non-hardening caulk. Smaller openings may be sealed 

with non-hardening caulk.

5.  (Existing Signs Only) A clean and dry mounting surface ensures optimum adhesion if the self-adhesive method of mounting is 

chosen. Follow the manufacturer’s directions when using a non-oil based solvent, such as rubbing alcohol to clean the surface area 

where you intend to mount the module. before installing, ensure the surface is dry.

6.  Using the layout guidelines above, determine required number of LED modules required to illuminate the sign.
7.  A Tetra

®

 12VDC Class 2 Power Supply, as listed below, must be used with this retrofit kit.  Using the Maximum Loading chart below, 

determine the number of Tetra

®

 Class 2 Power Supplies required to power the number of LED modules required to illuminate the 

sign, so as not to overload the Tetra

®

 Class 2 Power Supply chosen.

8.  Follow the instructions above to properly mount the LED modules. 
9.  Connect the DC output of the power supply to the LED modules using the Electrical Connections instructions above.
10. Connect the power unit to the supply in accordance with the applicable local, state, and country electrical codes, and the instructions 

found in the power supply installation guide.

11. If required, the disconnect switch shall be installed by qualified personnel, in accordance with applicable  local, state, and country 

electrical codes.

Retrofit Instructions

FOR UL ONLY

FOR UL ONLY

NOTE: All electrical connections should be suitably protected from mechanical damage and the environment. Seal all 

connections in locations that may be exposed to water with electrical grade RTV silicone.

3

4

Tetra

®

 LED Tape Gen 2

Installation Guide

5

Summary of Contents for Tetra GETP35-2

Page 1: ...dotyczące bezpieczeństwa można znaleźć w następującej lokalizacji https products gecurrent com eu PT A versão em Português das instruções de instalação e das informações de segurança pode ser encontrada na seguinte localização https products gecurrent com eu RO Versiunea în limba românǎ a instrucţiunilor de instalare şi a informaţiilor de siguranţǎ pot fi gǎsite la https products gecurrent com eu ...

Page 2: ...pas d installation Veuillez contacter un électricien qualifié Risque d incendie ou de choc électrique Installez cet ensemble seulement dans des enseignes hôtes qui ont été identifiés dans les instructions d installation et dont la capacité d entrée de l ensemble ne dépasse pas la capacité d entrée de l enseigne L installation de cet équipement de remplacement DEL peut impliquer le perçage ou le po...

Page 3: ...ve End cap Tape backing Silicone Clean mounting surface At the cut end carefully peel back the silicone cover over the soldering pads Make sure not to remove the silicone over the LED Using UL certified 18AWG wire solder a red wire to the pad and a black wire to the pad Heat shrink Silicone cover Red Black Seal the soldering points with electrical silicone Replace the silicone cover and secure it ...

Page 4: ...n the cover Remove the stopper from the tape guide NOTE If the stopper is missing and the connector cover has been locked please change to another one Partially remove the tape backing on the end to be connected Align red lead with the contact on the tape and the black lead with the contact Fully insert the tape into the open end of the tape guide with the LEDs facing the cover Press the cover dow...

Page 5: ...isting lighting equipment eliminates the disconnect switch as required by applicable local state or country electrical codes a new disconnect switch must be installed 4 Existing Signs Only Repair and seal any unused openings in the electrical enclosure Openings greater than 12 7 mm 1 2 in diameter require a metal patch secured by screws or rivets and caulked with non hardening caulk Smaller openin...

Page 6: ...t 9 1 m 50 ft 15 2 m 86 ft 26 2 m 180W Power Supply 20 ft 6 1 m 30 ft 9 1 m 50 ft 15 2 m 86 ft 26 2 m SKU Rating 25W Power Supply 60W Power Supply 180W Power Supply GETP35 2 GETP40 2 GETP50 2 GETP60 2 4 5W m 1 37W ft 4m 13 ft 10m 32 ft 10m 32 ft per output channel 30m 96 ft per power supply GETPH35 2 GETPH40 2 GETPH50 2 GETPH60 2 10 6W m 3 22W ft 1 7m 5 6 ft 4m 13 ft 4m 13 ft per output channel 12...

Reviews: