Summary of Contents for Telaire Ventostat 8001

Page 1: ...controller on the base by aligning the top clips and then securing to the bottom clips as shown in Figure 1 View B above A snap sound will indicate that the sensor is secure The sensor will now have power A 2 minute warm up will take place After 2 minutes the sensor will stabilize and display the Normal Mode current CO2 readings 5 At this point one of nine preset programs or one custom channel can...

Page 2: ...ure is weatherproof for measuring outside air CO2 con centrations It also includes heat stabilizers Model 1505 Harsh Environment Enclosure For extreme envi ronments where the sensor might be subjected to condensation or water spray such as those found in greenhouses or breweries NEMA 3R rated Figure 3 Accessory Enclosures Typical Wiring Diagrams The typical wiring diagrams appear in Figure 4 throu...

Page 3: ...ntrations drop to outside levels while the building is unoccupied Generally a building must be regularly unoccupied for 4 hours or more for this self calibration system to operate properly Under these conditions the ABC Logic feature should maintain sensor calibration over the lifetime of the sensor The ABC Logic feature should be turned OFF where a building is continuously occupied 24 hours per d...

Page 4: ...o initially introduce more ventilation to the space as concentrations are at the lower level of the control range The exponential output is particu larly useful for areas of potential high occupancy and high air volume where significant time may be required for CO2 levels to build up Potential applications include arenas gyms auditoriums and large con ference areas Examples of both types of output...

Page 5: ... Settings The non standard custom settings can be changed at any time after the sensor is powered up The seven settings variables are PPM Range Scale proportional or exponential Output V or mA Output Range V Output Range mA Relay Setpoint Relay Hysteresis The Altitude and ABC Logic features can be changed without entering into the Non Standard NONSTD menu 1 After 2 minute warmup period press CLEAR...

Page 6: ...ying the sensor operation using the UIP 8000 computer interface or checking the output signal on the building automation system 4 If there is no output signal call GE Telaire or your distributor dealer for a return authorization number Suspect the sensor is out of calibration 1 Compare the sensor reading to a GE Telaire 7001 hand held CO2 monitor 2 Take another sensor from the building and replace...

Page 7: ...lly Closed wire either way gold bifurcated 2A max 24VAC Adjustable setpoint factory set at 1000 ppm 50 ppm hysteresis Wiring 18 28 AWG stranded copper wire only 2 wires each for power analog output relay Digital I O RS 232 interface for use with optional PC software and cable in UIP kit 2072 Warranty Repairs GE Sensing will repair Telaire product that fails to meet the terms provided for in the Re...