background image

Page 4

Telaire Ventostat™ 8000 Series

Setting 9 is intended for use in parking garages where 

CO

2

 can be used 

as an indicator of the presence of combustion fumes. As part of most 
types of combustion, 

CO

2

 is generated at a rate that is 50 times or more 

than other, more harmful contaminants. This is particularly the case with

 the extensive use of catalytic converters that tend to remove
most of the carbon monoxide from vehicle exhaust. The 

700

ppm

 setting should maintain levels of other exhaust

contaminants well below levels of concern

.

Custom Settings

In addition to the nine standard settings programmed into the 8000 series 

(see Table 2 above), users can also custom program the sensor for their 
own application. 

Outlined below is a brief description of each of the adjustable custom 
settings:

Control Range - 

The range that will correspond to the analog signal 

output range. The range consists of a low level and a high level in 

ppm

Setting this range does not limit the actual measurement or display 
range.

Analog Output Range - 

Can be expressed in V or mA. This range 

will correspond to the range of 

CO

2

 concentrations established in the 

measurement range. The output in V or mA is selected based on the wir-
ing terminals. It is possible to simultaneously connect to both the V and 
mA outputs.

Proportional or Exponential Control - 

Proportional (linear) control 

increases the signal output in proportion to the increase in 

CO

2

 concen-

trations for the measurement range and analog output range selected. 
Exponential control provides an output function that is exponential over 
the selected range of the sensor. The effect of the exponential output is to 
initially introduce more ventilation to the space as concentrations are at 
the lower level of the control range. The exponential output is particu-
larly useful for areas of potential high occupancy and high air volume 

where significant time may be required for 

CO

2

 levels to build up. 

Potential applications include arenas, gyms, auditoriums and large con-
ference areas. Examples of both types of outputs appear in Figure 9 on 
the next page

.

Relay Set Point - 

Establishes the level at which the on-board relay 

will activate. The relay is a double pole single throw 

(DPST)

 relay that 

allows the user to operate the relay normally open or normally closed 
based on the selection of wiring terminals connected on the sub-base

.

Relay Hysteresis (Deadband)

 - 

Is the point at which the relay will 

deactivate. It is entered as a 

ppm

 value below the setpoint. A sensor with 

a relay setting of 1000 and a hysteresis of 50 would activate at 

1000 

ppm

 and deactivate at 

950 ppm

.

Table 2:  Standard Settings Adjustable via Keypad UIP Interface

Setting 

No.

Type of 

Equipment

Type of 

Output

Ventilation 

Rate (cfm/

Person)

Analog 
Output

CO2 

Control 

Range

(ppm)

Optional 

Relay 

Setpoint

(ppm)

Relay 

Hysteresis

(ppm)

1

Interface w/Standard 

Building Control 
System

Proportional

Any

0 - 10V

4 - 20 mA

0 - 2000

1000

50

2

Interface w/Standard 

Building Control 
System

Proportional

Any

2 - 10V

7 - 20 mA

0 - 2000

1000

50

3

Interface w/Standard 

Building Control 
System

Exponential

Any

0 - 10V

4 - 20 mA

0 - 2000

1100

50

4

Economizer (Hvac)

Proportional

15

0 - 10V

4 - 20 mA

0 - 1100

1100

50

5

Economizer (Hvac)

Proportional

20

0 - 10V

4 - 20 mA

0 - 900

900

50

6

Economizer (Hvac)

Exponential

15

0 - 10V

4 - 20 mA

0 - 1100

1100

50

7

Economizer (Hvac)

Exponential

20

0 - 10V

4 - 20 mA

0 - 900

900

50

8

Health & Safety

Proportional

NA

0 - 10V

4 - 20 mA

0 - 9999

5000

500

9

Parking/Air Intakes/

Loading Docks

Proportional

NA

0 - 10V

 4 - 20 mA

0 - 2000

700

50

Summary of Contents for Telaire Ventostat 8001

Page 1: ...controller on the base by aligning the top clips and then securing to the bottom clips as shown in Figure 1 View B above A snap sound will indicate that the sensor is secure The sensor will now have power A 2 minute warm up will take place After 2 minutes the sensor will stabilize and display the Normal Mode current CO2 readings 5 At this point one of nine preset programs or one custom channel can...

Page 2: ...ure is weatherproof for measuring outside air CO2 con centrations It also includes heat stabilizers Model 1505 Harsh Environment Enclosure For extreme envi ronments where the sensor might be subjected to condensation or water spray such as those found in greenhouses or breweries NEMA 3R rated Figure 3 Accessory Enclosures Typical Wiring Diagrams The typical wiring diagrams appear in Figure 4 throu...

Page 3: ...ntrations drop to outside levels while the building is unoccupied Generally a building must be regularly unoccupied for 4 hours or more for this self calibration system to operate properly Under these conditions the ABC Logic feature should maintain sensor calibration over the lifetime of the sensor The ABC Logic feature should be turned OFF where a building is continuously occupied 24 hours per d...

Page 4: ...o initially introduce more ventilation to the space as concentrations are at the lower level of the control range The exponential output is particu larly useful for areas of potential high occupancy and high air volume where significant time may be required for CO2 levels to build up Potential applications include arenas gyms auditoriums and large con ference areas Examples of both types of output...

Page 5: ... Settings The non standard custom settings can be changed at any time after the sensor is powered up The seven settings variables are PPM Range Scale proportional or exponential Output V or mA Output Range V Output Range mA Relay Setpoint Relay Hysteresis The Altitude and ABC Logic features can be changed without entering into the Non Standard NONSTD menu 1 After 2 minute warmup period press CLEAR...

Page 6: ...ying the sensor operation using the UIP 8000 computer interface or checking the output signal on the building automation system 4 If there is no output signal call GE Telaire or your distributor dealer for a return authorization number Suspect the sensor is out of calibration 1 Compare the sensor reading to a GE Telaire 7001 hand held CO2 monitor 2 Take another sensor from the building and replace...

Page 7: ...lly Closed wire either way gold bifurcated 2A max 24VAC Adjustable setpoint factory set at 1000 ppm 50 ppm hysteresis Wiring 18 28 AWG stranded copper wire only 2 wires each for power analog output relay Digital I O RS 232 interface for use with optional PC software and cable in UIP kit 2072 Warranty Repairs GE Sensing will repair Telaire product that fails to meet the terms provided for in the Re...

Page 8: ......

Reviews: