CAUTION
The SVI II AP High Flow digital valve positioner cannot be
placed in parallel with another volume booster. Contact the
factory for further instructions regarding configuration with
boosters as well as other non-standard configurations.
Connecting the Air Supply
After the tubing is installed, use the following procedure to connect the air supply.
1. Supply clean, dry compressed air to the filter regulator.
2. Turn on the air supply.
3. Adjust the filter regulator.
Supply pressure must be 5 - 10 psi greater than the spring range of the
actuator but may not exceed the rated actuator pressure. Refer to the valve or
actuator instruction manual.