22
GE Oil & Gas
ValVue SVI II AP Quick Start
Mounting the SVI II AP on Rotary Valves
This section describes the procedure for mounting the SVI II AP on rotary control
valves that have less than 60° rotation, such as a Camflex
*
or a Varimax
*
.
Figure
9 shows a side view of a Camflex actuator and the SVI II AP actuator
mounting brackets.
Figure 9
Camflex with Mounting Bracket (Side View)
Mounting the SVI II AP on a Rotary Actuator
Tools required:
3⁄16" Hex Key
5⁄32" Hex Key
3 mm, 4 mm, 5 mm Hex Key
7⁄16" Wrench
To mount the SVI II AP:
1. Attach the SVI II AP rotary mounting bracket to the valve actuator using two
(2) 5⁄16 - 18 UNC flat-head cap screws. In the preferred mounting position, the
long end of the mounting bracket is on your left when facing the actuator, for
any position of the valve and actuator.
2. Bolt the extension shaft to the valve position take-off shaft using a 1⁄4 - 28
UNF socket flathead screw. Secure the machine screw holding the extension
shaft with a torque of 144 in-lbs (16.269 N-m).
3. On internal valve pressure the thrust shaft is pushed out to the mechanical
stops, usually a thrust bearing. On valves where the valve position take-off is
mounted directly on the end of the plug shaft, a Camflex for example, the shaft
must be bearing on its stop to properly set up the SVI II AP Controller. During
hydrostatic testing the shaft is thrust to its stop and a normally tightened
packing retains it in that position.
Summary of Contents for SVI II AP-2
Page 6: ...GE Oil Gas SVI II AP Quick Start Guide 6 ...
Page 10: ...10 GE Oil Gas ValVue SVI II AP Quick Start This page intentionally left blank ...
Page 64: ...64 GE Oil Gas ValVue SVI II AP Quick Start This page intentionally left blank ...
Page 90: ...90 GE Oil Gas ValVue SVI II AP Quick Start Spare Parts ...
Page 91: ...91 Specifications and Spare Parts ...