3 INSTALLATION
3.1 TRANSPORT
Transport UPS only in upright position!
The UPS is packaged on a pallet suitable for handling with
a forklift.
Pay attention to the center of gravity.
The UPS must be moved in
upright position
.
Do not tilt cabinets
more than +/- 10°
during handling.
Move the UPS in it’s original package to the final
destination site.
Do not stack other packages on top
: This could damage
the UPS.
If the UPS must be lifted by crane, use suitable lifting straps
and spreader bars.
Note of the center of gravity marked on the package.
Take all necessary precautions to avoid damage to the
cabinet while hoisting the UPS
.
Forklift
Crane
NOTE !
Fig. 3.1-1 UPS cabinets moving
Check for sufficient floor and elevator
loading capacity.
3.1.1 Dimensions and weight
Dimensions
SG Series 225 & 300
(W x D x H)
64.96 x 31.50 x 70.90 inches
1,650 x 800 x 1,800 mm
SGS_225-3
00_S2_UP
S dimensio
ns_GE_01U
S
H
W
D
Fig. 3.1.1-1 UPS cabinet dimensions
Weight
SG Series 225 & 300
UPS rating
Weight
Floor loading
lbs/sq.ft - kg/m
2
lbs / kg
SG Series 225 & 300
3,087 / 1,400
218 / 1,061
P.S.: Weights including the 5th harmonic filter.