SecoGear – Installation, Operation and Maintenance Manual 40 of 56
Verify that the VCB safety stop in the switchgear
compartment has returned to the normal
extended position.
CAUTION
2. Verify that the VCB safety stop has returned to the
extended position, Figure 5-21. If necessary, release
by inserting a screw driver into the slot to dislodge,
Figure 5-22.
Figure 5-19. Rotate Interlock Pin Counterclockwise to Unlock the Latch Handle
1. Once the VCB is in the switchgear compartment,
disengage the lift truck compartment interlock by rotating
the interlock pin counterclockwise, Figure 5-19, then
move the handle to the left and pull the latch handle
toward you and from the switchgear compartment until it
is fully retracted, Figure 5-20.
Figure 5-20. Interlock Latch Handle
Figure 5-21. Stop in Proper Position
Figure 5-22. Eliminating Stop Interference
Figure 5-23. Release Floor Lock
3. Release the lift truck floor lock by depressing the lever on
the right or left-hand side of the floor lock and move the
lift truck away from the switchgear, Figure 5-23.