IC695PNC001-AJ PROFINET Controller Module

 

GFK-2573K 

Status Reporting  

The PNC provides 32 bits of status information to a configured location in the RX3i CPU’s reference memory.  
The status data consists of the Module OK bit, which indicates the health of the module itself, a status bit for each 

external port, and a bit that indicates the connection status of the configured devices.  
All Status bits are active high. The status location may be configured in %I, %Q, %AI, %AQ, %R, %G, %T, %M or %W or 

I/O Variable reference memory in the RX3i CPU.  

Status Bit Definitions 

Bit 

Name 

Description 

Module OK 

Indicates the health of the PNC module. 
1 indicates the module is functioning properly. 
0 indicates the module is powering up or has failed. 

Port1 Link Up

 

1 indicates the port is connected to another device and is operating correctly.  
0 indicates the port is not connected to another device or the port has an error preventing 
communications, or the SFP cage is empty or has an incompatible SFP device.

 

Port2 Link Up 

Port3 Link Up 

Port4 Link Up 

Reserved 

Reserved. Always 0. 

Port3 SFP OK 

Indicates the health of the SFP plugged in port 3. 
1 indicates that the SFP matches configuration and is operational.

 

0 indicates that either the SFP does not match configuration or is not operational.

 

Port4 SFP OK 

Indicates the health of the SFP plugged in port 4. 
1 indicates that the SFP matches configuration and is operational. 
0 indicates that either the SFP does not match configuration or is not operational.

 

All Devices 
Connected

1

 

1 indicates all configured devices are connected and communicating over PROFINET.  
0 indicates no devices are configured or one or more configured devices have not established 
a PROFINET connection. 

10 

Reserved 

Always 0. 

11 

MRP Enabled 

0 indicates that MRP is not enabled. 
1 indicates that MRP is enabled. 

12 

MRP Role 

If MRP is enabled: 

0 indicates that the PNC is currently an MRP client.  
1 indicates that the PNC is currently the MRP Manager. 

If MRP is not enabled, this bit will be set to 0. 

13 

MRP Ring Status 

If MRP is enabled and the PNC is currently the MRM: 

0 indicates that the ring is open (ring broken).  
1 indicates that the ring is closed (ring complete).  

If MRP is not enabled or if the PNC is an MRC, this bit will be set to 0. 

14-32   Reserved 

Set to 0 

 

1

 It is recommended that the All Devices Connected status bit be checked first to determine whether all devices belonging to 

the PNC are functioning. If this bit is 0, indicating that one or more devices is not OK, the PNIO_DEV_COMM function block 
can then be used to determine which specific devices are not communicating. For details on this status bit, refer to the section, 

Status Reporting

 in GFK-2571, 

RX3i PROFINET Controller Manual.

 

 

                                                                 

Summary of Contents for RX3i PROFINET

Page 1: ...ation via the micro USB port or using telnet Note The USB port is for system setup and diagnostics only It is not intended for permanent connection Support for star ring and daisy chain line network t...

Page 2: ...Control 10 100 1000 Mbps Maximum I O Memory 128 Kbytes of combined input output memory per PROFINET Controller CPU Status Bits 32 PROFINET I O Device Data Update Rates on the PROFINET LAN Configurable...

Page 3: ...t be installed in an ultimate enclosure that is manufactured to provide safety As a minimum the enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This e...

Page 4: ...tion or is not operational 8 Port4 SFP OK Indicates the health of the SFP plugged in port 4 1 indicates that the SFP matches configuration and is operational 0 indicates that either the SFP does not m...

Page 5: ...e RX3i system using a Universal Backplane such as IC695CHS007 CHS012 or CHS016 The PNC supports insertion removal while power is applied to the system hot swap This includes backplane power and field...

Page 6: ...such as Hyperterm The PNC is provided with a driver install application that can be used to enable a computer to communicate with a PNC via its USB port For details on using the Command Line Interfac...

Page 7: ...res and Enhancements on page 8 IC695PNC001 AF 1 23 Aug 2013 Corrects issue storing PROFINET device configuration greater than 64K bytes in size For details see GFK 2573F IC695PNC001 AE 1 22 Jul 2013 C...

Page 8: ...0 CPE310 CPE305 Boot Firmware Release 7 10 CRU320 Primary Firmware Release 8 00 CRU320 Boot Firmware Release 5 10 Other CPU models are not supported Programmer version requirements RX3i PNC001 Release...

Page 9: ...ware configuration or the current hardware configuration in the system is cleared prior to storing a new configuration If the controller is Faulted clear the I O Fault Table to recover Otherwise no ad...

Page 10: ...he failover occurs It is not recommended to use the PNC reset button in a normally operating system If the reset button must be used it is recommended to first attempt a brief press and release of the...

Page 11: ...perly and updates the maximum number of telnet connections log details command response When displaying numerous local log table entries using the log details command sometimes erroneous blank charact...

Page 12: ...t case ring recovery time is 96ms the rate needs to be more than 96ms divided by 3 which is 32ms The next available rate after 32ms is 64ms 16ms When using an I O Update Rate of 16ms you must set the...

Page 13: ...configurations When storing hardware configurations with more than 64 PROFINET I O Devices that include multiple PNC modules and 3rd party PROFINET I O Devices on a single network occasional Loss Add...

Reviews: