IC695PNC001-AJ PROFINET Controller Module
GFK-2573K
PNC Specifications
PROFINET Support
PROFINET Version 2.2 General Class A I/O-Controller.
Redundantly controlled operation conforms to PROFINET V2.3 Type S-2
System Redundancy.
RX3i CPU Compatibility
CPU315 or CPU320, with firmware version 7.0 or higher
CPE305/CPE310 with firmware version 7.10 or higher
Simplex or redundantly-controlled PROFINET I/O requires CRU320 release
8.40 or higher.
Power Requirements
3.3 V:
0.5 A with no SFP devices installed
1.2 A maximum (two SFP devices installed, 0.35 A per SFP device)
5 V:
1.5 A maximum
Operating Temperature Range
0 to 60°C maximum surrounding air temperature without a fan. A lower
maximum temperature may be required depending on PNC location and
SFP population. Refer to the section,
Operating Range for Air Temperature
in
GFK-2571,
PACSystems RX3i PROFINET Controller Manual.
Number of Port Connectors
Two RJ-45 and two SFP Cages
(SFP devices not included, available separately)
Micro USB Connector
One, for communication with a computer using Command Line Interface.
LAN
IEEE 802.2 Logical Link Control Class I
IEEE 802.3 CSMA/CD Medium Access Control 10/100/1000 Mbps
Maximum I/O Memory
128 Kbytes of combined input/output memory per PROFINET Controller
CPU Status Bits
32
PROFINET I/O Device Data Update Rates on
the PROFINET LAN
Configurable: 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128 ms, 256 ms
and 512 ms
Number of IP addresses
One
Number of MAC Addresses
Five. One per external port and one internal.
System Maximum Limits
PNCs per RX3i CPU
Four. Must be located in main rack. Cannot be located in a remote node.
I/O-Devices per I/O-Controller
128 per PROFINET Controller (Configured as an MRP Manager, the PNC is
limited to managing no more than 63 MRP Clients).
I/O-Devices per Network
255 per network, spread across up to 8 IO-Controllers
I/O-Devices per RX3i CPU
255 per RX3i CPU, spread across up to 4 PROFINET Controllers
I/O-Controllers per network
8
Number of PROFINET Slots per device
256
Number of PROFINET Subslots per slot
256
Number of PROFINET Submodules per RX3i
CPU
2048
Programmer Limits
Number of I/O-Controllers
128 (32 RX3i CPU targets × 4 IO-Controllers per RX3i CPU)
Number of I/O-Devices
4080 (255 per network × 16 PROFINET networks)
Total number of devices
4208 (does not include backplanes, power supplies, or I/O modules)
Hot-swappable
Yes
For product standards, general operating specifications, and installation requirements, refer to GFK-2314,
PACSystems
RX3i System Manual
.