GE Reason H49
Technical Manual
H49/EN M/C22
129
10.5.4
BIU261D
10.5.4.1
Maximum measured burden in Volt-ampere (VA)
Item
Power supply voltage
VA
Maximum burden AC powered on main power supply
110 Vac
23.19
Maximum burden DC powered on main power supply
110 Vdc
16,16
Maximum burden DC powered on secondary power supply
110 Vdc
16,13
Maximum burden for binary input
110,4 Vdc
220,76 Vdc
0,16
0,69
10.5.4.2
Maximum measured inrush current (Vdc)
Power input voltage (Vdc)
Measured peak current (A)
Power-up duration (ms)
110
19,4
110
220
43,8
92
10.5.4.3
Maximum measured inrush current (Vac)
Power input voltage (Vac)
Measured peak current (A)
Power-up duration (ms)
110
12,84
126
230
14,8
109
10.6
Ethernet Management
Item
Description
Standards
IEEE802.3, 802.3u, 802.3x
Forwarding mode
Store and forward
Memory bandwidth
800 Mbps
MAC Address
512
Address learning
Automatic
Illegal frame
Dropped per 802.3
Late collision
Dropped after 512 bit times
Latency
20 µs measured at 75 % load with frames length of 64 bytes between the device
ports and the redundant ports.
250 µs measured at 75 % load with frames length of 1518 bytes between the
device ports and the redundant ports.