15
IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide
GFK-3002A
Module Start-up
You Will Need:
•
This PACSystems Rackless RX3i CPU.
•
A compatible SELV 24Vdc, 48W power supply (72W if Energy Pack attached).
•
(Optionally) A compatible Energy Pack, IC695ACC403, and corresponding cable.
•
If no Energy Pack is to be attached, use the power supply cable described in
Section 2.4.
•
A DIN rail, typically mounted in an enclosure, as discussed above. Alternately,
mount the unit using the compatible panel-mount adaptor.
•
A computer running Proficy Machine Edition (PME) configuration and
programming software. PME Version 9.00 SIM 8 or later supports the CPE400.
Version 9.50 SIM 5 is required for Hot Standby Redundancy.
•
Ethernet cable for connecting the PME programmer computer to the CPE400.
•
Additional cables, as needed, to connect each port employed in the application.
•
A very small slotted screwdriver to secure the 24Vdc mating connector.
•
A T8 Torx screwdriver, if the micro-SD slot cover is to be removed. Note that the
cover must be replaced to achieve immunity from electrical noise.
•
A T10 Torx screwdriver, if exchanging the mounting adaptors.