GE OSKF Instruction Manual Download Page 11

 

 

Instruction Manual                                                                                                                             

 

 

© GE Grid Solutions 

 

11

 

6.2.

 

Primary bar type (if applicable)  

 
Primary 

bar 

is 

always 

supplied 

completely assembled with the delivered 
CT.  Clean  the  primary  terminal  as 
explained  in  “CONTACT  SURFACES 
PREPATION” 

 

6.3.

 

Double / Triple Reconnection 

Primary type (if applicable)  

 
The  current  ratio  of  the  OSKF  can  be 
single with only one single bar, double or 
triple  primary  ratio.  Double  or  triple 
primary  ratio  can  be  easily  changed  by 
the  user  following  the  instruction  of  the 
approved  set  of  drawing.  This  changing 
ratio  is  made  by  means  of  reconnection 
bars  located  in  the  top  tank,  closer  to 
primary terminals. See set of drawing to 
know how the reconnection bars need to 
be  positioned  in  order  to  have  the 
required ratio. 

 

6.4.

 

Grounding 

 
The transformer fixation base has one or 
two  plates  that  should  be  linked  to  the 
substation  ground  system  through  the 
grounding  connector  supplied  with  the 
equipment. 

 

6.5.

 

Secondary terminals 

 
Connect  protection  and/or  measure 
instruments  to  the  secondary  terminals 
as  shown  on  the  nameplate.  See  the 
tightening  torque  in  drawings  of  the 
project 

 

A  point  of  each  secondary  terminal 
must  be  connected  to  the  ground  in 
order to fix the potential. 
Secondary  terminals  not  used  must 
be short-circuited and grounded. 
 

6.6.

 

Terminal marking 

 
Primary and secondary terminal marking 
are  done  according  to  the  specified 
standard. See set of drawing. 
Primary  and  secondary  connection 
scheme  are  shown  on  schematic  plates, 
fixed on the CT.                

 

7.

 

OIL LEVEL INDICATOR 

 

The  position  of  the  oil  indicator  can  be 
verified through the rectangular window 
of the top cover. 
 
The  plate  of  the  indicator  is  divided  in 
three  areas.  Central  area  shows  the 
green  strip  and  higher  and  lower  areas 
are  shown  with  a  red  strip.  In  normal 
conditions,  the  indicator  shows  the 
green strip of the indicator. 
 
In case of oil level indicator is in either of 
the  red  areas,  the  transformer  must  be 
removed  from  operation  and  GE 
informed immediately. 
 

 

Summary of Contents for OSKF

Page 1: ...GE Grid Solutions INSTRUCTION MANUAL 19201 CURRENT TRANSFORMER TYPE OSKF...

Page 2: ...ruction Manual GE Grid Solutions 2 GE Grid Solutions Av Nossa Senhora da Piedade 1021 37504 358 Itajub MG Brasil AIB 01 10 11 2017 RGO FML AIB 00 24 11 2013 TAA TCRP Owner revision Date Prepared Appro...

Page 3: ...STORED IN A HORIZONTAL POSITION FOR MORE THAN FOUR MONTHS IF THE TIME OF TRANSPORTION AND STORAGE EXCEEDS THIS PERIOD IT IS MANDATORY TO UNPACK AND PUT THE TRANSFORMER INTO A VERTICAL POSITION FIXING...

Page 4: ...7 3 4 Storage 9 4 BELLOWS BLOCKING SYSTEM AND ASSEMBLY IN THE STRUCTURE 9 4 1 Bellows blocking system 9 4 2 Assembly in the structure 10 5 CONTACT SURFACES PREPARATION 10 6 CONNECTIONS 10 6 1 Primary...

Page 5: ...stics of the OSKF Current Transformers For more details see set of drawings 1 Top Cover 2 Oil Level Indicator metallic bellows 3 Lifting eyes 4 Primary terminals aluminum or copper 5 Cast aluminum 6 P...

Page 6: ...th gaps OSKF may have metering and protection cores with different loads and different accuracy classes Secondary turns are evenly wound around the circumference of the ring shaped cores Changing rati...

Page 7: ...ny sign of damage or oil leakage the customer inspector or the service agent in charge of receipt shall make a written remark on shipment documents The receipt control mainly for the porcelain insulat...

Page 8: ...for the slings nylon belts reinforced and avoids blows and vibrations Follow the instructions shown in the drawing below for lifting the CT All cables or slings shall be kept in vertical position duri...

Page 9: ...is also put in place on the periphery of the bellows to protect it against contact with the top cover In order to remove the blocking system place the current transformer in vertical position on a fla...

Page 10: ...he structure If not it is necessary to insert a shim before putting the fixation screws Remove the lower lid of black plastic if applicable from secondary terminal box It is only used for transport It...

Page 11: ...g connector supplied with the equipment 6 5 Secondary terminals Connect protection and or measure instruments to the secondary terminals as shown on the nameplate See the tightening torque in drawings...

Page 12: ...sealed If required small quantity of oil can be taken Always verify oil level indicator before take oil samples Never complete oil volume without prior formal authorization of GE Important remark Duri...

Page 13: ...6 Remove the top cover to have access to the bellows and verify if there is any signal of oil leakage near the fixation of the bellows and or if the bellows is in good condition Tests It is recommend...

Page 14: ...with resin Oil disposing company properly licensed to perform such activity Oil PCB free classified as Class I hazardous residue Oil disposing company properly licensed to perform such activity Mater...

Reviews: