NX-8E CONTROL
33
LOCATIONS 110-169 ARE USED TO CHANGE THE ZONE TYPES (Configurations) AS LISTED IN THE TABLE
ON PAGE 19. THESE LOCATIONS ARE CONSIDERED ADVANCED PROGRAMMING AND SHOULD
ONLY BE CHANGED WITH A THOROUGH UNDERSTANDING OF THE OPERATION OF EACH BIT.
LOCATION 110 - ZONE TYPE 1 ALARM EVENT CODE (1 segment, numerical data)
Location 110 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 70. The zone ID will be that zone that is in alarm.
4+2 Format Note: If 4+2 format is being used, the number programmed in this location will be sent as the upper hex
digit. The digit in location 110 should be from 1 to 15 when using 4+2 formats. The zone ID or user ID will be the
lower hex digit of the zone that is in alarm.
LOCATION 111 - ZONE TYPE 1 CHARACTERISTIC SELECT (5 segments, feature selection data)
Segment 1:
1 = Fire (turn on if this is a fire zone).
2 = 24 hour (turn on for non-fire 24 hour zones).
3 = Keyswitch zone. (normally open switch)
4 = Follower (turn on for burglary zones that are Instant during non-entry times).
5 = Delay 1 zone (follows timer 1 entry and exit times).
6 = Delay 2 zone (follows timer 2 entry and exit times).
7 = Interior (turn on if this zone should Automatically Bypass or Bypass for Stay Arming).
8 = Local only (turn on if this zone should not be reported).
Segment 2:
1 = On if Zone Type will beep the keypad for alarm.
2 = On if Zone Type will sound the yelping siren for alarm.
3 = On if Zone Type will sound the temporal siren for alarm.
4 = On if Zone Type will chime.
5 = On if Zone Type can be bypassed.
6 = On if Zone Type is included in the group shunt.
7 = On if Zone Type is force armable.
8 = On if Zone Type is entry guard.
Segment 3:
1 = On enables Fast Loop Response. (50mS)- Off= 500mS
2 = On enables Double End Of Line Tamper zone. (Mainly used for tamper on wireless zones)
3 = On enables Trouble Reporting zone. (Day zone and Fire zones)
4 = On if Zone Type is a Cross Zone.
5 = On enables Dialer Delay zone. (See location 40, page 23)
6 = On if Zone Type will swinger shutdown. (See location 38, page 23)
7 = On enables Restore reporting.
8 = On enables Listen-In. (See location 40, page 23)
Segment 4:
1 = On enables Zone Activity Monitor. (See location 40, page 23)
2 = On enables End of Line Resistor Defeat on Non-Fire/Non-Keyswitch zones.
3 = On delays alarm activation 60 seconds (Do not enable unless configured with Access Control.)
4 = On enables zone to act as request to exit input / disables for alarm activation.
5-8 = Reserved.
Segment 5: Reserved.
LOCATION 112 - ZONE TYPE 2 ALARM EVENT CODE (1 segment, numerical data)
Location 112 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 70. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location
110 on page 33 for details.
LOCATION 113 - ZONE TYPE 2 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 33.
LOCATION 114 - ZONE TYPE 3 ALARM EVENT CODE (1 segment, numerical data)
Location 114 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 70. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location
110 on page 33 for details.
LOCATION 115 - ZONE TYPE 3 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 33.