background image

GEI-50261 

Reasonable  care  should  be  exercised  in  unpacking  the  relay  in  order  that  none  of  the 
parts  are  injured  nor  the  ad justments  disturbed. 

If  the  relays  are  not  to  be  installed  immediately,  they  should  be  stored  in  their 
original  cartons  in  a  place  that  is  free  from  moisture,  dust  and  metallic  chips. 

Foreign  matter  collected  on  the  outside  of  the  case  may  find  its  way  inside  when  the 
cover  is  removed,  and  cause  trouble  in  the  operation  of  the  relay. 

ACCEPTANCE 

TESTS 

Immediately  upon  receipt  of  the  relay,  an  inspection  and  acceptance  test  should  be 

made  to  make  sure  that  no  damage  has  been  sustained  in  shipment  and  that  the  relay 
calibrations  have  not  been  disturbed. 

Visual 

Check  the  nameplate  stamping  to  make  sure  that  the  model  number,  rating  and 

calibration  range  of  the  relay  received  agree  with  the  requisition. 

Remove  the  relay  from  its  case,  and  check  by  visual  inspection  that  there  are  no 
broken  or  cracked  molded  parts  or  other  signs  of  physical  damage,  and  that  all 

screws  are  tight. 

Mechanical 

It  is  recommended  that  the  telephone-type  relay  be  checked  as  follows: 

With  the  telephone-type  relay  de-energized,  each  normally-open  contact  should  have  a 

gap  of 

.010-.015 

inch. 

Observe  the  wipe  on  each  normally-closed  contact  by 

deflecting  the  stationary  contact  member  towards  the  frame. 

Wipe  should  be 

approximately 

.005 

inch. 

The  wipe  on  each  normally-open  contact  should  be  approximately 

.005 

inch. 

This  can 

be  checked  by  inserting  a 

.005 

inch  shim  between  the  residual  screw  and  the  pole 

piece  and  operating  the  armature  by  hand. 

The  normally-open  contacts  should  make 

before  the  residual  screw  strikes  the  shim.  When  the  telephone  relay  is  picked  up, 

the  normally-closed  contact  should  have  a  gap  of 

.010 

to 

0.15 

inch. 

Electrical  Tests 

If  the  relay  has  not  been  damaged  in  shipment,  it  is  very  unlikely  that  the  relay 
adjustments  have  been  disturbed. 

Where  evidence  of  rough  handling  is  observed,  the 

following  electrical  tests  should  be  made. 

1. 

Balanced  three-phase  tests 

Connect  a  balanced  three-phase  voltage  of  correct  phase  sequence, 

rated 

frequency  and  good  wave  form  to  the  relay,  as  shown  in  Figure 

7, 

and  check  the 

voltage  across  relay  studs 

and 

with  a  high-resistance  voltmeter 

(1000 

ohms 

per  volt  or  more). 

The  voltage  observed  should  be  less  than 

1.5 

volts  for  a 

208 

volt  relay,  and 

1.0 

volts  for  a 

120 

volt  relay. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for NBVllA Series

Page 1: ...NGS 4 CALCULATIONS 6 CONSTRUCTION 7 RECEIVING HANDLING STORAGE 7 ACCEPTANCE TESTS 8 INSTALLATION PROCEDURE 10 PERIODIC CHECKS AND ROUTINE MAINTENANCE 10 RENEWAL PARTS 11 TYPE NBVllA GE Protection and...

Page 2: ...V11A Relay Top View Showing Location of Parts Referred to in Text TELEPHONE RELAY RESISTOR Rl RESISTOR R2 DIODE RECTIFIER BRIDGE Figure 2 8031804 Type NBVl1A Relay Left Side View Figure 3 8031803 Type...

Page 3: ...phase condition on light load as well as on heavy load The NBV is usually connected to a bus and it will effectively protect a group of many motors when the open circuit is between the source and the...

Page 4: ...l define the relay pickup voltage VR as the single phase voltage that when connected to the relay as shown in Figure 10 will just cause the relay to pick up This will be between 10 and 20 volts for th...

Page 5: ...otential transformers are connected in open delta as shown in Figure 6 B the burden is as shown in Table III For the best division of burden it is recormnended that terminal No 6 of the relay be conne...

Page 6: ...ages seen by the relay are the same as the relay would see if it were connected to a three phase system that had one phase shorted Thus if we assume v12 is shorted then in equation 1 V1 2 0 v2 3 v2 3...

Page 7: ...e front of the relay case contains an interlock arm that prevents the cover from being put back in place until the connection plugs have been inserted The relay case is suitable for either semi flush...

Page 8: ...With the telephone type relay de energized each normally open contact should have a gap of 010 015 inch Observe the wipe on each normally closed contact by deflecting the stationary contact member to...

Page 9: ...ave should decrease Continue increasing resistor R1 until the minimum voltage occurs As the magnitude of the wave decreases it will be due to the fundamental wave decreasing The harmonic content of th...

Page 10: ...y changing the Resistor R2 setting PERIODIC CHECKS AND ROUTINE MAIRTENANCE In view of the vital role of protective relays in the operation of a power system it is important that a periodic test progra...

Page 11: ...equired RENEWAL PARTS Sufficient quantities of renewal parts should be kept n stock for the prompt replacement of any that are worn broken or damaged When ordering renewal parts address the nearest Sa...

Page 12: ...A0254 Potential Transformer Connections for Type NBV11A Relay 0418A0807 2 Test Connections for Checking R C Circuit Adjustment 0418A0805 Internal Connections for Type NBV11A Relay Front View 0459A0252...

Page 13: ...tt tt r 4 Jt r _ h tt R H H d i t 1 GEI 50261 1 1 ttt t ft i i 1 i t 0 0 0 0 0 t N i Figure 4 SONOJ3Silll Nl 3 11 0459A0251 Operating Times of Type NBVllA Relay Contacts When Unbalanced Voltage Is Su...

Page 14: ...t 1 H 1 0 r M h _4j 1 t tl t i t _ 0 1 0 M _ i t t t r c c I I f c t t tf t _ t t j I fhl l0fi W 1 0 N M SONOJ3Sill1Vi t _ _ t 7 t o t l 1 0 0 M Nl Vi 11 _J_ 1 1 1 t T rq I tt i 0 Figure 5 0459A0250 O...

Page 15: ...NECTION FOR WYE CONNECTED P T S l 5 i L 1 0 6 B P T SECONDARIES 7 RELAY S1UDS RECOMMENDED CONNECTION FOR OPEN DELTA P T S Figure 6 0459A0254 Potential Transformer Connections for Type NBVllA Relay 15...

Page 16: ...GEI 50261 1 t l RATED VOLTAGE 3 FREQUENCY 2 2 3 1 3 9 10 Figure 7 0418A0807 2 Test Connections for Checking R C Circuit Adjustment 16 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 17: ...GEI 50261 TR I l i 5 7 6 I I I 111 112 fl j AUTo TRANSFORMER r 9 8 TR 10 x SHORT F I NGER Figure 8 0418A0805 Internal Connections for Type NBVllA Relay Front View 17 w w w E l e c t r i c a l P a r t...

Page 18: ...IONS VT 2 b UNBALANCED BY SHIFT OF ONE CORNER c UNBALANCED BY SHIFTING TWO CORNERS b TOWARD EACH OTHER ALONG VECTOR BETWEEN THEM 2 Figure 9 0459A0252 1 System Voltages under Balanced and Unbalanced Co...

Page 19: ...C VARIAC GEI 50261 1 2 4 6 9 COAITI VVITY LIGHT 10 W 7H VOLTA SOVI CI Figure 10 0459A0223 2 Test Connections for Setting Pickup of Type NBV11A Relay 19 w w w E l e c t r i c a l P a r t M a n u a l s...

Page 20: ...AF TER ENGAGING AUXILIARY B RUSH CONNECTING PLUG TRAVELS Y4 INCH BEFORE ENGAGING THE MAIN BRUSH ON THE TERMINAL B LOCK Figure 11 8025039 Cross Section of Drawout Case Showing Position of Auxiliary Br...

Page 21: ...60X0 0003 T SI TARGET 1 SEAL IN T D C TIME DELAY CLOS lNG F RA IC FILTER OtS5AS788 I I I I I I I 1 I I PT S I I J I I I j _J_ I J _ II _____ _ WHEII USED r l J o F _ J I 7 5 FUSES IF U f D AUX PT I I...

Page 22: ...8 6 4 2 L 29MM I 6 187 1 9MM 3 0 I 157MM 76MM 4 I II I I 4 406 l 112MM I _i_ CUTUUT 8 81 I 224M III 2 843 f 2 M 72MM 1 218 f t ____ 5MM 5 687 PANEL I I II 144MM 5 25 BACK VIEW DRILLED HOLES 1 156 29M...

Page 23: ...I il e I oc3ood 0 0 OG2 GEI 50261 BACK VIEW OF CASE Figure 14 0178A5824 1 Outline and Mounting Dimensions for the Harmonic Filter 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 24: ...3 94 200 Protection and Control GE Technology Center 205 Great Valley Parkway Malvern Pennsylvania 19355 1337 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: