2-14
G650 Generator Protection & Control System
GEK-113328A
2.4 TECHNICAL SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4.1.16 PHASE UNDERVOLTAGE (27P)
2.4.1.17 NEUTRAL OVERVOLTAGE (59NH)
2.4.1.18 GROUND OVERVOLTAGE (59G)
Voltage Input
Fundamental Phasor of phase-to-ground or phase-to-
phase voltages (selectable by setting)
Pickup level
3 to 500 in steps of 1 V
Dropout level
102% to 103% of the pickup level
Level accuracy
±
1% reading
±
0.1% Full Scale from 10 to 500 V at
nominal frequency
Curve Shapes
Fixed time or inverse curve
Reset type
Instantaneous
Curve Multiplier (Time Dial)
0.00 to 900.00 s. in steps of 0.01 s.
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Minimum Voltage Threshold
0 to 500 in steps of 1 V
Logic
Any/Two/All phases logic selectable by setting
Supervised by Breaker
Selectable by setting
Snapshot Events
Selectable by setting
Voltage Input
Fundamental Phasor of the neutral voltage (calculated
from phases)
Pickup level
3 to 500 in steps of 1 V
Dropout level
97% to 98% of the pickup level
Level accuracy
±
1% reading
±
0.1% Full Scale from 10 to 500 V at
nominal frequency
Trip delay
0.00 to 900.00 s. in steps of 0.01 s
Reset delay
0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events
Selectable by setting
Voltage Input
Fundamental Phasor of the ground voltage (measured
from 4th voltage transformer)
Pickup level
3 to 500 in steps of 1 V
Dropout level
97% to 98% of the pickup level
Level accuracy
±
1% reading
±
0.1% Full Scale from 10 to 500 V at
nominal frequency
Trip delay
0.00 to 900.00 s. in steps of 0.01 s
Reset delay
0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events
Selectable by setting