GEK-113328A
G650 Generator Protection & Control System
B-15
APPENDIX B
B.1 FACTORY DEFAULT SETTINGS
B
SETPOINT > CONTROL ELEMENTS > OVERFREQUENCY
OVERFREQUENCY 1 > OVERFREQUENCY 2 > OVERFREQUENCY 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup level
Pickup Level
50.50
0.01 Hz
[20.00 : 65.00]
Trip time
Trip Delay
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01 s
[0.00 : 900.00]
Minimum voltage threshold
Minimum Voltage
30
1 V
[30 : 500]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > SYNCHROCHECK
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Dead bus voltage level
Dead Bus Level
10.00
0.01 V
[0.00 : 500.00]
Live bus voltage level
Live Bus Level
50.00
0.01 V
[0.00 : 500.00]
Dead line voltage level
Dead Line Level
10.00
0.01 V
[0.00 : 500.00]
Live line voltage level
Live Line Level
50.00
0.01 V
[0.00 : 500.00]
Voltage Difference
Max Volt Difference
10.00
0.01 V
[2.00 : 500.00]
Angle Difference
Max Angle Difference
10.0
0.1 Deg
[2.0 : 80.0]
Frequency Slip
Max Freq Difference
20
10 mHz
[10 : 5000]
Breaker Closing time
Time
0.50
0.01 s
[0.01 : 600.00]
Dead Line – Dead Bus Function
permission
DL-DB Function
DISABLED
N/A
[DISABLED – ENABLED]
Live Line – Dead Bus Function
permission
LL-DB Function
DISABLED
N/A
[DISABLED – ENABLED]
Dead Line – Live Bus Function
permission
DL-LB Function
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]