3 SERIES RETROFIT – INSTRUCTION MANUAL
CONVERTING MIN II 67IG1 TO 350 32N
CHAPTER 2: CONVERTING SETTINGS FILES
2.5.1
Mapping settings
Figure 2-2: Sample settings screens
MIN II Settings
350 Settings
Table 2–2: Enervista setting conversion
67IG1 (MIN II)
67IG1
(MIN II)
32N WGN1 (350)
32N WGN1
(350)
Notes
67IG1 Enable
Ready
WGN 1 Function
Trip
67IG1 Trip
Ready
WGN 1 Voltage
Calculated (Vn)
67IG1 Voltage Low
10 Volts
WGN 1 Voltage PKP
0.1 x VT
convert V to x VTn
(for example, if Vn = 100 V, the new setting is 0.1 x VT)
WGN 1 Current
Calculated (In)
67IG1 Current Low
0.01 A
WGN 1 Current PKP
0.01 x CT
convert 0.01 A to x CTn
(for example: if CTn = 1 As the new setting is 0.01 xCT)
WGN 1 Power PKP
0.003 xCTxVT
enter in x CTxVT as explained below
WGN 1 Ref Power PKP
0.500 xCTxVT
Applicable only if Curve is selected under WGN 1
Curve
67IG1 Direction
Forward
WGN 1 ECA
90°
setting the ECA angle to 90 deg. provides for
FORWARD direction (positive power)
67IG1 Charact. Angle 90°
67IG1 Time Delay
0.5 s
WGN 1 Power PKP Delay
0.5 s
WGN 1 Curve
Definite Time
Applicable only if Curve is selected under WGN 1
Curve
WGN 1 Multiplier
1 s
Applicable only if Curve is selected under WGN 1
Curve
WGN 1 Relays
Relay:
Disabled
WGN 1 Block 1
Off
WGN 1 Block 2
Off
WGN 1 Block 3
Off