DUCT FITTINGS

Use this chart to compute 
maximum permissible lengths for
duct runs to outdoors.

NOTE:

Do not exceed maximum

permissible equivalent lengths!

Maximum duct length:
100 foot for 8

round duct

Flexible ducting:

If flexible metal ducting is used, 
all the equivalent feet values in 
the table should be doubled. 
The flexible metal duct should 
be straight and smooth and
extended as much as possible.

DO NOT use flexible plastic 
ducting.

NOTE:

Any home ventilation 

system, such as a ventilation hood,
may interrupt the proper flow of
combustion air and exhaust
required by fireplaces, gas 
furnaces, gas water heaters and
other naturally vented systems. 
To minimize the chance of 
interruption of such naturally 
vented systems, follow the 
heating equipment manufacturer’s
guidelines and safety standards
such as those published by NFPA
and ASHRAE.

This Hood Must Use an 

8

Round Duct.

9

Advance Planning

Total

Equivalent

Quantity Equivalent

Duct Piece

Dimensions

Length*

Used

Length

Round,

1 ft.

straight

(per foot
length)

3-1/4

x 12

1 ft. 

3-1/4

x 24

(per foot

straight

length)

8

round

90° elbow

17 ft.

8

round

45° elbow

10 ft.

3-1⁄4

x 10

14 ft.

3-1⁄4

x 12

15 ft.

90° elbow

3-1/4

x 10

8 ft.

3-1/4

x 12

9 ft.

45° elbow

3-1/4

x 10

33 ft.

3-1/4

x 12

36 ft.

90° flat elbow

8

″ 

to 3-1/4

x 10

2 ft.

8

″ 

to 3-1/4

x 12

2 ft.

or 3-1/4

x 10

transition

2 ft.

3-1/4

x 10

to 8

2 ft.

3-1/4

x 12

to 8

2 ft.

round transition

8

″ 

to 3-1/4

x 10

7 ft.

8

″ 

to 3-1/4

x 12

6 ft.

transition 90° elbow

3-1/4

x 10

to 8

5 ft.

3-1/4

x 12

to 8

5 ft.

round transition 90° elbow

8

round

wall cap
with damper32 ft. with damper

3-1/4

x 12

wall cap

with damper26 ft. with damper

8

round

roof cap

44 ft.

3-1/4

x 10

wall cap 

w/ damper24 ft.
round roof vent

*Actual length of straight duct plus

duct fitting equivalent. Equivalent
length of duct pieces are based 
on actual tests conducted by GE
Evaluation Engineering and reflect
requirements for good venting
performance with any ventilation
hood.

Total Duct Run

Summary of Contents for Monogram ZVC30LSS

Page 1: ...Installation Instructions 30 36 and 48 Custom Hood Insert ZVC30LSS ZVC36LSS ZVC48LSS 49 80415 12 06 JR...

Page 2: ...ation and Air Conditioning Engineers ASHRAE and the local code authorities C When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities D Ducted fans must...

Page 3: ...rries Jubilee Peppercorn Beef Flamb C Clean ventilating fans frequently Grease should not be allowed to accumulate on fan or filter D Use proper pan size Always use cookware appropriate for the size o...

Page 4: ...mper Plate 19 Step 5 Install Blower Motor 20 Step 6 Connect Wiring Harness 20 Step 7 Install Filters 21 Step 8 Finalize Installation 21 PRODUCT CLEARANCES The vent hood and liner assembly must be inst...

Page 5: ...er is shipped with each hood insert This non combustible liner protects the underside of the canopy Custom Liner If you are not using the supplied liner you may construct a custom non combustible line...

Page 6: ...er is shipped with each hood insert This non combustible liner protects the underside of the canopy Custom Liner If you are not using the supplied liner you may construct a custom non combustible line...

Page 7: ...the underside of the canopy Custom Liner If you are not using the supplied liner you may construct a custom non combustible liner Use the supplied liner as a template The opening must be 38 3 4 W x 1...

Page 8: ...of the control mounting assembly A 30 ft wire cord is provided Careful consideration must be given to the location of the remotely mounted control It is recommended that the 4 wire cord be routed thro...

Page 9: ...Round Duct 9 Advance Planning Total Equivalent Quantity Equivalent Duct Piece Dimensions Length Used Length Round 1 ft straight per foot length 3 1 4 x 12 1 ft 3 1 4 x 24 per foot straight length 8 ro...

Page 10: ...ve the liner foam and cardboard 3 Remove the tape securing the filters to the insert sleeve lift the tabs and remove the filters 4 Unscrew the 5 nuts securing the damper vent plate assembly and remove...

Page 11: ...nset hood while unpacking parts Blower motor Models ZVC30LSS and ZVC36LSS Insert sleeve Filters 2 wing nuts with lock washers for blower motor NOTE To be used on custom hood when controls are remotely...

Page 12: ...p to the ceiling On the ceiling measure 5 1 2 from the back wall to the centerline of an 8 1 2 hole Wall Ducting If ductwork will vent to the rear Use a level to draw a centerline straight up to the c...

Page 13: ...sleeve must be centered with the insert sleeve The insert sleeve should extend beyond the front and rear edge of the cooking appliance The insert sleeve in the ceiling must be centered left to right o...

Page 14: ...alled in a backsplash or countertop A cover plate is provided to cover the opening in the hood when the control is removed A 30 ft length of 4 wire cord is supplied to accommodate most installations B...

Page 15: ...the control with the 2 mounting plate screws 4 Pull the 4 wire cord through the opening in the wall the wall bracket and the back of the mounting bracket NOTE Use provided cable or cable designated b...

Page 16: ...rame the cutout opening to fit the liner NOTE The opening support must be 3 4 thick wood to accept the liner installation screws 2 Slide the liner up and into the opening until flush with bottom edges...

Page 17: ...tre maison est en aluminium assurez vous d utiliser un compos anti oxydant approuv et des raccords aluminium cuivre 1 Place insert sleeve on padded yet stable surface below cutout can use flattened ca...

Page 18: ...t to exhaust opening of insert sleeve and seal with aluminum tape NOTE House duct should drop to 11 1 2 above bottom edge of insert sleeve or the bottom of the 3 4 cabinet base 5 Tape the 4 washers in...

Page 19: ...embly and rotate so that vent side is up and bracket is located on left as you stand facing hood 2 Insert damper plate assembly into insert sleeve and carefully align with 8 house duct 3 Secure damper...

Page 20: ...While holding blower motor in place lift right side so that blower motor bolt holes align with bolts protruding from damper plate assembly and secure with lock washers and wing nuts hand tighten STEP...

Page 21: ...While maintaining slight backward pressure on filter open clip and press into place with two hands 3 To remove support filter with one hand while pulling filter clip down with the other STEP 8 FINALIZ...

Page 22: ...22 Notes...

Page 23: ...23 Notes...

Page 24: ...service in your area call 1 800 444 1845 Note Product improvement is a continuing endeavor at General Electric Therefore materials appearance and specifications are subject to change without notice GE...

Reviews: