GFK-2993F 81
For public disclosure
6.2.5 Guidelines for Maximum Configured Variables
All variables read from the Server by a Machine Adapter are published. The OPC UA Machine Adapter supports OPC UA
Subscription functionality, which can be used to limit the variables published to those that have either changed or changed
more than a specified amount since the last subscription interval. Other protocols do not include this functionality; Machine
Adapters for these protocols will publish all variables configured to be read each interval.
Variables of type LREAL (OPC UA type Double) are supported for both OPC UA and Modbus TCP Machine Adapters; one
LREAL may be configured and published in the place of two 4-byte or smaller variables. This formula may be used to
calculate the effective number of 4-byte or smaller variables when also configuring and publishing LREAL variables:
(# of 4-Byte or smaller variables) + (# of LREAL variables * 2) = Effective Variable Count
When using multiple Subscriptions, the maximum number of configured variables and the maximum number of published
variables is cumulative across all Subscriptions on a given Field Agent. When using different PublishInterval settings for
different subscriptions, the fastest PublishInterval in use should be used to determine the maximum numbers of configured
and published variables.
6.2.5.1
Using the OPC UA Machine Adapter without Store and Forward
NOTE
Using the OPC UA Machine Adapter without Store and Forward is not currently supported on the EFA or VFA.
When Store and Forward is disabled, the OPC UA Machine Adapter limits for the Mini Field Agent platform are displayed in
the following table.
Supported Configurations for OPC UA Machine Adapter with Store and Forward Disabled on MFA
PublishInterval (ms)
Configured 4-Byte Variables
Max Published
500-999
600
300
1000-1999
1,200
600
≥2000
1,200
1,200
Note
For ICMFA000000-AAxx only, multiply the values in the above table by 0.83 to calculate the OPC UA Machine
Adapter limits when Store and Forward is disabled.
Note
Some OPC UA Servers may negotiate a different interval at the time of the connection if the configured
PublishInterval does not match its available subscription intervals. It is recommended to confirm that the OPC UA Server to
which the Mini Field Agent is connected can serve data at the requested interval.
Note
The minimum supported OPC UA Machine Adapter PublishInterval on the Mini Field Agent is 500ms when running
Predix Machine 17.1.2 or later.
Summary of Contents for Mini Field Agent
Page 1: ...GFK 2993F Field Agents User Guide July 2017 For public disclosure...
Page 31: ...GFK 2993F 31 For public disclosure Notes...
Page 50: ...GFK 2993F 50 For public disclosure 2 Verify that the Field Agent Updater page displays...
Page 60: ...GFK 2993F 60 For public disclosure 5 10 1 4 1 Using Certificate Enrollment...
Page 62: ...GFK 2993F 62 For public disclosure 5 10 1 4 2 Using OAuth Authentication Code Enrollment...
Page 65: ...GFK 2993F 65 For public disclosure Notes...
Page 67: ...GFK 2993F 67 For public disclosure...
Page 86: ...GFK 2993F 86 For public disclosure Notes...
Page 87: ...For public disclosure...