4.
Status Mode
STATUS
PICKUP
Figure
57.
Trip Unit status display for long-time overcurrent
pickup.
Trip Target and Fault Displays
When the breaker trips, information about the trip
can be displayed in Status mode. Figure 58 illustrates
a typical fault display following a trip.
Fault
Fault
Magnitude
Phase
0 c LIAMPS
...
1
Ll I
Display
Mode
STATUS
FAULT
Trip
Targets
Fault
Indication
Figure
58.
Typical fault display following a breaker trip.
The
FAULT
segment indicates that the breaker has
tripped because of an overcurrent condition or a
protective relay. This segment remains visible until it
is cleared, including displays in Setup and Meter
mode. This provides an indication that trip informa
tion is available, even if other screens are being dis
played. If the trip was caused by a protective relay,
the
FAULT
segment flashes in Setup or Meter mode.
Mter an overcurrent trip, the
FAULT
segment and the
appropriate overcurrent target are displayed in all
modes, without blinking, until cleared.
Long-Time Overcurrent Fault Display
Mter a long-time overcurrent trip, the trip informa
tion display contains the fault current magnitude at
trip, the phase on which the fault occurred, and the
overload
( I >)
and long-time
( L T
)
trip targets. This
display is illustrated in Figure 59.
31
[0
LT
'
�1
' AMPS
STATUS
FAULT
Figure
59.
Trip Unit Status display for long-time overcurrent trip.
Short-Time Overcurrent Fault Display
Mter a short-time trip, the status display appears as
in Figure 60. The information presented is similar to
that in the long-time overcurrent display, with the
short-circuit
( I >>
) and short-time
( ST )
targets.
' '
,
'
·
' c
(/f2
kA
STATUS
FAULT
Figure
60.
Trip Unit status display for short-time overcurrent
·
trip.
Instantaneous Fault Display
The status display for an adjustable instantaneous
trip is illustrated in Figure 6 1 . Because of the fast
response of this function, the Trip Unit displays only
the threshold current for the fault, not the actual
fault current nor the phase on which the fault
occurred. For high-range instantaneous trips, the
threshold current is also not displayed, only the trip
target.
5
.
..
,,
-. .=t Lf
INST
kA
STATUS
FAULT
Figure
61.
Trip Unit status display for instantaneous overcurrent
trip.