P40 Agile P14D, P14N, P94V
Version History
P40Agile-VH-EN-9
7
Major Minor
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes
Technical Documentation
·
actVal Data Attribute now finalised as INT32 requirement in SCL (Edition 1 Only)
·
Values under High impedance menu do not show values in primary when relay is set to primary in S1.
·
Pending Reports when BufTm>0? Ed1
·
Agile latch reset when setting group is changed
·
Connection / Disconnection issues
·
Class 0 should be configurable to select either Counter or corresponding Frozen Counter
·
DNP3oE Versions - Courier Tunnelling doesnot work
·
For DNPOE build, the frozen counter always keeps the same value with the static counter without accepting a
Freeze command.
·
The behaviour of frozen counter is different between DNP3 and DNPOE before the freeze command is sent
·
DNPOE after operated some DI and AI events at the same time ,the relay Ethernet board seems locked and after
a while the relay reboot.
·
IEC 61850 Interoperability problem when a client writes to any/all unsupported Trigger Options
·
Problems with ICD files for P140 50A
·
8.333Hz is displayed in the first generated Fault Record after relay reboot.
·
P145 Underfrequency issue in Russia
·
SecRmsMMXU1 showing values in primary, not secondary
·
IEC 61850: incorrect Courier cell mapping to TotWh and TotVArh in MMTR LNs
·
CB Fail trip may fail to operate under faults with DC transient offsets
·
"FUNCTION KEYS" column is visible for 20TE devices in P14 Agile data model.
·
Default GOOSE “Min Cycle Time” is wrong.
·
Visibility of setting "I>1 TMS" and "I>1 Time Dial" is wrong in Group 2
·
EPATR-B curve
·
High Impedance Fault issue
·
DNP3OE Versions - Command management during IED disconnection / connection
·
Freq Avg Cycles & df/dt Avg Cycles should use power cycle instead of PCON calls cycles
·
The unit of Records/RFLO1/CF/FltDiskm is incorrect
·
Very sharp pick current level lead relay tripping on IREF
·
The error message" Runtime Error C991:3011" appear on P14N relay when glance over the cells in overcurrent
column from HMI
·
Column [4E00] PSL TIMERS is invisible from relay
·
Default Setting of Relay is in-consistent to Look & Feel
·
P94VR Look & Feel consistency check issues via courier interface
·
“Ethernet failover” option displays in IED Configurator
·
New settings Moving average cells ([42 41] -> [42 2D]) are not working in Modbus.
·
When download the software to the P14DZ relay and power cycle,the error message - "Runtime Error
2e0b:0101" appear and relay reboot
·
The sequence number should not increase when relay send retry unsolicited message