APPENDIX F
SCREEN DESCRIPTION FOR VIEW DATA MENU
* DLT REV
ISION
Indicates current instrument revision (firmware and hardware).
* SIL 2 / NON SIL
Indicates if the device is configured as a SIL 2 certified instrument or not.
* BA
SIC
SETUP
Validate by pressing the * to read current Basic Setup data.
* AD
VANCED
SETUP
Validate by pressing the * to read current Advanced Setup data.
* DIAGNOS
TIC
Validate by pressing the * to enter the Diagnostic menu.
READ C
OUN
T
E
R
Validate by pressing the * to enter the sub-menu of cumulated Diagnostic data.
N
UM
B
E
R of FILL
INGS
Totalizes the amount of liquid entering the tank. Counter increments by one when
accumulated positive change in level corresponds to one height of displacer.
TIME LOW
Time (number of hours) during which the instrument worked /-5 % of low level
calibrated value.
TIME HIGH
Time (number of hours) during which the instrument worked /-5 % of high level
that is between 95 % and 105 % of calibrated value.
TIME WORK
ING
Time (number of hours) during which the instrument has been on service.
↑
BACK
Return to previous menu.
RESET C
OUN
T
E
R
Validate by pressing the * to reset the diagnostic data to zero in memory.
SENS
OR
TEMP
ERATURE
Indicates sensor circuit board temperature.
MOD
U
L
E
TEMP
ERATURE
Indicates main circuit board temperature.
↑
BACK
Return to previous menu.
* S
PECIFIC
G
RAVITY
METER
Validate by pressing the * to read the Specific Gravity value of the liquid when the
displacer is fully immersed. The Specific Gravity Meter must have been previously
calibrated. If the Specific Gravity Meter has not been calibrated, the screen ERROR is
displayed: this is the only way to know if the Specific Gravity Meter has been previously
calibrated. In both cases, push * to return to main Diagnostic menu.
ERROR
Displayed when the Specific Gravity Meter has not been calibrated.
↑
BACK
Return to previous menu.