APPENDIX C
SCREEN DESCRIPTION FOR ADVANCED SETUP MENU – 2/2
SMART F
I
LT
ERING
Validate by pressing the * to enter the Smart Filtering menu.
S
MART
F
I
LT
ERING
ON
Activate the Smart Filtering function.
S
MART
F
I
LT
ERING
OFF
Deactivate the Smart Filtering function.
TUNE
Validate by pressing the * to manually or automatically tune the smart filtering
parameters.
D
EAD
Z
ONE
of
INT
E
G
RATION
: %
Manual adjustment of this parameter between 0.01% and 10%.
W
INDOW of
VAL
IDATION
: s
Manual adjustment of this parameter between 0.1 s and 32 s.
AUTO
MATIC
TUNE
Validate by pressing the * to automatically tune the smart filtering parameters.
↑
BACK
Return to previous menu.
S
PECIFIC
G
RAVITY
M
ETER
CALIB
RATION
Validate by pressing the * to calibrate the Specific Gravity Meter. Enter the sub-menu
and proceed as a normal level calibration.
S
PECIFIC
G
RAVITY for
CALIB
RATION
Validate by pressing the * to set the specific gravity of the liquid used during the
calibration procedure. Settable value ranges from 0.001 to 10.
ZERO
When displayed, empty the tank (or simulate) so that displacer is fully out of liquid. Wait
till the displacer is stable then press * to define the zero, which is the Reference Low (REF
L).
SPAN
When displayed, fill the tank (or simulate) so that displacer is fully immersed in liquid.
Wait till the displacer is stable then press * to define the span, which is the Reference
High (REF H).
CANCEL
Validate by pressing the * to cancel the parameters saving procedure.
SAVE
Validate by pressing the * to start the saving procedure of parameters previously
entered in the instrument memory.