High Level [SPAN]
g1.
Liquid application
:
Move the flexure (59) against the adjusting screw shoulder (114), which corresponds to the high level of calibration
fluid [SG CALIB] (on displacer side). Wait for a few seconds until the displacer stabilizes.
g2.
Interface application:
Move the flexure (59) against the adjusting screw shoulder (114), which corresponds to the high level of highest specific
gravity fluid of calibration [HSG CALIB] (on displacer side). Wait for a few seconds until the displacer stabilizes.
g3.
Enter and validate the [SPAN]: the [LEVEL:%] value indicated on the display must equal 100.0%. If not, restart the
procedure until very close to this value. See Appendix B.
h.
Press the * button when [SAVE] is displayed to validate the [ZERO] and [SPAN] settings.
i.
Reinstall all plugs (107), (190), and (115).