A–8
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
LM10 AND GE FANUC 90-30 WITH DEVICENET™
CHAPTER A:
Z
Enter a value of 7 bytes under input resource and 1 byte under
output resource.
This is the size of the slave status data and command data.
Z
Make changes to the slave side settings.
Z
Under the
General
tab, set the
MAC ID
equal to the MAC ID of the
slave device.
Z
Select the
Polled
option under the
Connection 1
tab.
The input and output byte size are defined and connection type is
Status and Control.
Z
Place the PLC online and download the hardware and logic to the
PLC.
Z
Observe the DeviceNet™ master module LEDs.
All three LEDs for NET POWER, MOD STATUS, and NET STATUS
should turn solid green.
Z
Open a new
Reference View Table
to monitor and control the
slave device, then add address %I00001 (Slave Status Bit Array).
Addresses %I00001 to %I00064 will display the status of all slave
devices connected to master card.
• For example, if the master card detects an LM10 slave device
with MAC ID 1, then address %I00002 will read “1”. Similarly, if a
slave is connected with MAC ID 2, then address %I00002 will read
“2”.
Z
Start the
PLC
.
The NS LED on the LM10 (MAC ID 1) will turn solid green once the
connection is established, and address %I00001 will read “1”.
Z
Double-click on
GE LM10
to view the data areas.
For Connection 1 inputs (to master), address %I00081 will display
the status. For Connection 1 outputs (from master), address
%Q00017 will contain the command for the slave.
Z
Add the
%I00081
and
%Q00017
registers to the Reference View
Table.
The reference view table for the LM10 is shown below.
Summary of Contents for LM10
Page 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...
Page 74: ...6 68 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL WARRANTY CHAPTER 6 MISCELLANEOUS ...
Page 106: ...I 4 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...