background image

CP Converter Shelf - Quick Start Guide 

Document 850033106   r04   2015 April 

J1 Alarms and Inputs - page 4 

J4 1-Wire Battery Temp and Voltage Monitor 

J5 LAN Port 

J2 External Alarm Inputs - page 4 

J7 External Distribution Shelf.- page 4 

RS-232 Craft port 

Step 5 - Set Jumpers - LAN Port and Relay per Galaxy Pulsar Edge Controller Quick Start Guide

 

Signal Connections

 

Step 6 - Install Controller per Galaxy Pulsar Edge Controller Quick Start Guide

 

Connectors are on rear. 

1.  J1-2  Alarms and Inputs - Connect to office alarms and signals. 

See 

Information:  Alarm Connections

  for Details 

2. J5 

LAN - Connect to Ethernet network. 

3. J7 

DIST - Connect to external distribution - if present. 

Step 7 - Install Signal and Communications Cables

 

1. Connect 1-Wire Battery Temp and Voltage Monitor to J3 

Step 8 - Install 1-Wire Battery Temp and Voltage Monitor per Galaxy Pulsar Edge Controller Quick Start Guide

 - Optional 

Step 9 - Install Converter s

 

Latch 

1.  Slide converter into its slot approximately 3/4 of the way. 
2.  Open the faceplate by sliding the faceplate latch to the left until the faceplate releases and 

swings outward.  

3.  Slide the unit into the slot until it engages with the back of the shelf. Swing the faceplate closed 

to fully seat the converter. Verify the faceplate is latched. 

Step 10 - Initial Start Up

 

Verify that all AC, DC and Alarm connections are complete and secure. Turn on AC input breakers. If there are no alarms, make required 

adjustments to the default settings on the controller for this installation. 

Step 11 - Configure Controller per Galaxy Pulsar Edge Controller Quick Start Guide

 

Verify and edit controller basic configuration parameters per site engineering instructions. 

Summary of Contents for J2045J389E

Page 1: ...sition mounting ears as required 8 screws each Torque to 25 in lb 2 8Nm Phillips screwdriver 2 Attach shelf to the frame using a minimum of four screws two on each side 12 24 provided Torque to 35 in lb 4Nm 5 16 socket Chassis Ground Output Return Ground 48V Output DC Inputs Converter Inputs POS NEG NEG POS 1 2 4 3 Step 3 Connect 48V Output and Output Return Lugs 1 4 on 5 8 centers not provided To...

Page 2: ...ery Temp and Voltage Monitor to J3 Step 8 Install 1 Wire Battery Temp and Voltage Monitor per Galaxy Pulsar Edge Controller Quick Start Guide Optional Step 9 Install Converter s Latch 1 Slide converter into its slot approximately 3 4 of the way 2 Open the faceplate by sliding the faceplate latch to the left until the faceplate releases and swings outward 3 Slide the unit into the slot until it eng...

Page 3: ... Alrm 4 J2 All Controllers Controller Information Alarm Connections See the Compact Power Line Brochure for details Alarm connections are on the rear of the shelf J1 is Alarm Outputs and J2 is Alarm Inputs Change alarm descriptions via LAN port Web pages or Craft port EasyView2 when required J1 1 Includes a mixture of Alarm Inputs and or Alarm Outputs de pending on the controller model 2 Connector...

Page 4: ...ng Network Connect to an Isolated Ground Plane Isolated Bonding Network or an Integrated Ground Plane Mesh Bonding Network or Common Bonding Network Installation Environment Install in Network Telecommunication Facilities OSP or where NEC applies DC return may be either Isolated DC return DC I or Common DC return DC C Reference Documents These documents are available at www gecriticalpower com Doc...