CP Converter Shelf - Quick Start Guide 

Document 850033106   r04   2015 April 

Connector 

J1 - Controller Variants 

 

Pin 

Color  0

I

5R_D - 5 Alarm 

Relays 

3C3R - 3 Alarm 

Relays, 

9C0R_USB - 9 Inputs 

Color 

All 

BK 

Output: R3 = Rtn 

Input: PBT/TR 

Input: PBT/TR 

 

Input: SPD Fail 

BR 

Output: R2 = Rtn 

Input: Hi Ext. Temp. 

Input: Hi Ext. Temp. 

 

-- 

Output: R1 = Rtn 

Output: R1 = Rtn 

Input: Low Ext. Temp. 

 

Input: AUX MAJ 

Output: PMN Rtn 

Output: PMN Rtn 

Input: Fan Fail 

 

Input: Air Cond. Fail 

Output: PMJ Rtn 

Output: PMJ Rtn 

Input: Hydrogen Present 

 

Input: Door Open 

Output: R3 = ACF 

Input: RTNS 

Input: Returns 

 

BL 

-48V 

BL 

Output: R2 = RFA 

Input: Cust. Alrm 1 

Input: Cust. Alrm 1 

 

BR 

-48V 

Output: R1 = BD 

Output: R1 = BD 

Input: Cust. Alrm 2 

 

BK 

-48V 

Output: PMN 

Output: PMN 

Input: Cust. Alrm 3 

 

 

  

10 

Output: PMJ 

Output: PMJ 

Input: Cust. Alrm 4 

 

 

  

J2 - All Controllers 

Controller 

Information:  Alarm Connections

 

See the 

Compact Power Line  Brochure 

for details. 

Alarm connections are on the rear of the shelf - J1 is Alarm Outputs and J2 is Alarm Inputs. 

Change alarm descriptions via LAN port (Web pages) or Craft port (EasyView2) when required.  

J1

1. Includes a mixture of Alarm Inputs and / or Alarm Outputs de-

pending on the controller model. 

2. Connector Part: 

Cvilux HDR10-CP35H 

Alarm Inputs

1. “dry” contacts, apply no voltage. 

2. Return for all alarm inputs is pin 6. 

Alarm Outputs:

  relays contacts. 

J2

1. Includes 4 Alarm Inputs. 
2. Connector Parts: Molex 

39-01-2086 Housing 

39-00-0087 Contacts 

Alarm Inputs

1. Contact closures or opens to -48V. 

2. Pins 6, 7, and 8 provide -48V for these alarm inputs. 

Information:  Connections - External Distribution - J7

 

J7 Pin 

Wire Color 

Description 

BK 

FAJ 

2 BR 

Coil 

Rtn 

LVD_NC 

4 O 

LVD_NO 

Shunt - 

6 G 

OS 

BL 

Coil 1 

8 V 

Coil 

LVD Status Return 

10 W 

Shunt 

J7

1. Connector P/N 

Cvilux HDR10-CP35H 

Summary of Contents for J2045J389E

Page 1: ...sition mounting ears as required 8 screws each Torque to 25 in lb 2 8Nm Phillips screwdriver 2 Attach shelf to the frame using a minimum of four screws two on each side 12 24 provided Torque to 35 in lb 4Nm 5 16 socket Chassis Ground Output Return Ground 48V Output DC Inputs Converter Inputs POS NEG NEG POS 1 2 4 3 Step 3 Connect 48V Output and Output Return Lugs 1 4 on 5 8 centers not provided To...

Page 2: ...ery Temp and Voltage Monitor to J3 Step 8 Install 1 Wire Battery Temp and Voltage Monitor per Galaxy Pulsar Edge Controller Quick Start Guide Optional Step 9 Install Converter s Latch 1 Slide converter into its slot approximately 3 4 of the way 2 Open the faceplate by sliding the faceplate latch to the left until the faceplate releases and swings outward 3 Slide the unit into the slot until it eng...

Page 3: ... Alrm 4 J2 All Controllers Controller Information Alarm Connections See the Compact Power Line Brochure for details Alarm connections are on the rear of the shelf J1 is Alarm Outputs and J2 is Alarm Inputs Change alarm descriptions via LAN port Web pages or Craft port EasyView2 when required J1 1 Includes a mixture of Alarm Inputs and or Alarm Outputs de pending on the controller model 2 Connector...

Page 4: ...ng Network Connect to an Isolated Ground Plane Isolated Bonding Network or an Integrated Ground Plane Mesh Bonding Network or Common Bonding Network Installation Environment Install in Network Telecommunication Facilities OSP or where NEC applies DC return may be either Isolated DC return DC I or Common DC return DC C Reference Documents These documents are available at www gecriticalpower com Doc...