NE-M Installation Guide
H5692448
850050111
Issue 03 August 2017
72
Pulsar Controller Status
Display
Millennium Controller
Status Display
Rect/
Conv
LEDs
Dist.
Module
LED
Possible Problem(s)
Possible Solution(s)
MAJ Battery on
Discharge
Norm
green
green
System voltage has fallen below the
battery on discharge threshold set
by the user.
1. Investigate other alarms that may be present such as rectifier
related problems.
2. If AC power is present but the system voltage remains low, call
your local field representative.
Norm
amber
green
Rectifier is in current limit.
MAJ Battery on
Discharge and AC Fail
ACF
amber
green
•
Rectifier not receiving ac power.
•
ac input voltage is out of range.
MIN Rectifier Fail
Fail
red
(one
Unit)
green
•
Rectifier output has dropped
below 18V (36V), rectifier has
shut down
.
•
Excessive ambient temperature,
rectifier has shut down.
•
A rectifier or rectifier fan has
failed.
•
A rectifier high voltage shut
down
1. Verify that there is no obstruction of the airflow path and fans
are turning.
2. Reset the rectifier by removing the rectifier, waiting
approximately 30 seconds, and replacing the rectifier.
3. If problem persists, replace the rectifier.
4. If problem persists, call your local field representative.
31
When a rectifier or converter senses an over- or under-voltage condition it will shutdown, wait 4 seconds, and then attempt to restart. If the over- or under-voltage condition
remains it will cycle again. If the over- or under-voltage condition remains after 3 restart attempts the unit will lock out, and user intervention is required to restart.
BD AC DC
red green green
-54.48V1 1000A
FLOAT
Display Red
Major
Battery on
red
Discharge
red
Major
Battery on
red
Discharge
red
BD AC DC
red amber green
Display Red
-54.48V1 1000A
FLOAT
Major
AC Battery on
red
Sys Discharge
amber red
green green green
BD AC DC
-54.48V1 1000A
FLOAT
Display Amber
Minor
Rectifier/
amber
Converter
amber