NE-M Installation Guide
H5692448
850050111
Issue 03 August 2017
12
•
Local or remote viewing and configuration of system
parameters, alarm thresholds, and user-definable
alarm inputs and relays
•
Extensive rectifier/converter Monitoring and Control
•
Advanced Battery Management to maximize and
manage battery health
•
Emergency Power Off (EPO) to meet local emergency
services code requirements
•
System voltage and current monitoring
•
LVBD and LVLD Low Voltage Disconnect contactor
control and monitoring
•
dc Distribution monitoring
•
Standard and Programmable Alarms
•
Extensive Voltage, Current, Temperature, and Binary
Input monitoring
•
Standard and programmable Office Alarm relays
•
Digital communications to all system devices
•
Remote Peripheral Modules (RPMs)
See the Galaxy Millennium II Installation and User’s Guide for further detail.
Aux Display - NE830A (Optional)
The Aux Display is a voltage monitor that alarms when the voltage of the power system is out of the normal operating
range. It is mounted on the door of the distribution box.
Figure 5 NE830 Display
•
Fully independent of the main system controller
•
Displays one or two system voltages and battery state:
•
Single voltage systems, -48V, +24V
•
Dual voltage systems, -48V and +24V with common return
•
The display and LED color indicates battery charge state and wiring errors:
•
Green display
= batteries are not discharging
•
Red display = batteries are discharging
•
Amber display = wiring error
•
A Battery on Discharge alarm relay with form-C contacts is provided
•
Can be panel, wall or frame rail mounted within 150 ft. of the power system
Rectifiers and Converters
NE-Series rectifiers and converters are hot-pluggable for quick, simple, plug-and-play installation without tools.
Figure 6 Rectifier and Converter Type Badge
NE Eco Rectifiers
Input
AC or DC (PV or solar)
Compatibility All Infinity Rectifier Positions
Eco Feature
MPPT (Maximum Power Point Tracking) maximizes power harvested from PV arrays
NE Non-Eco Rectifiers
Input
AC only
Compatibility All AC powered Infinity Rectifier Positions
5
Non Eco rectifiers will not function properly when powered by DC (PV or solar) input in Eco systems.
Type Badge