DIAGNOSTIC STATUS CODES
IT TRANSISTOR CONTROL
Page
32
April 2012
TRACTION
STATUS CODE
DESCRIPTION OF STATUS
CAUSE OF STATUS INDICATION
-66
The field current exceeds the current limit
of the field transistor.
This status code will be displayed when the field
transistor exceeds its current limit. The line
contactor will drop out and the key switch will have
to be recycled to restart the control.
MEMORY RECALL
YES
CORRECTIVE ACTIONS
TROUBLE-SHOOTING DIAGRAM
Circuits valid
for
Traction
Controller
SYMPTOM
Control will not operate or is sluggish on
start up. Line contactor opens.
POSSIBLE CAUSES
Shorted field F1 to F2
F1 or F2 terminals shorted to battery
positive (B+)
Confirm that all inductive
loads/accessories are suppressed.
Motor armature or field shorted to
frame.
Defective control.
Replace controller unit.
L
P9
P7
P8
P1
P17
P2
P6
P4
P5
TU
RF SW
.
FO
R
W
A
R
D SW
.
REV
E
RS
E SW
.
ACC POT
TACHOMETER
P15 P14 P16
P10
BU
ZZ
ER
RE
D
GR
E
E
N
BL
AC
K
P12
REGEN
B
R
AK
E S
W
P21
MO
T
O
R
OV
ER T
E
MP
+72V
+72V
+72V
+72V
+72V
+72V
+72V
P22
P23
P20
RS232
72V
NEG
P3
NE
G
I
N
PUT
ST
A
R
T SW
.
72V
NEG
P13
NE
G
I
N
PUT
BR
AKE
S
W
.
72V
NEG
TRACTION
STATUS CODE
DESCRIPTION OF STATUS
CAUSE OF STATUS INDICATION
-76
Capacitor (1C) voltage too high during
pedal up regen braking.
This status code will be displayed when the voltage at
1C exceeds 96 volts during the regenerative braking
cycle.
MEMORY RECALL
YES
CORRECTIVE ACTIONS
TROUBLE-SHOOTING DIAGRAM
Circuits valid
for
Traction
Controller
SYMPTOM
Line contactor opens and closes, then
opens and can only close by opening
and closing the key switch.
POSSIBLE CAUSE
Batteries are overcharged.
Regen current too high, cycle key
switch off then on.
Defective control.
Replace controller unit.