background image

 

 

Ground Directional 

 Relay Type IBCG

ADJUSTMENTS

 

 

TARGET AND SEAL-IN UNIT

When used with trip coils operating on currents

ranging from 0.2 to 2.0 amperes at the minimum

control voltage, the target and seal-in tap screw

should be set   the 

 tap. When the trip

coil current ranges from 2 to 30 amperes at the

minimum control voltage, the tap screw should be

placed in the 2.0 ampere tap.

The seal-in 

 tap screw is the screw holding

the right-hand stationary contact of the seal-in unit.

To change the tap setting, first remove the connect-

ing plug. Then take a screw from the left-hand sta-

tionary contact and place it in the desired tap. Next,

remove the screw from the other tap and place it

back in the left-hand contact. This procedure is

necessary to prevent the right-hand stationary con-

tact from getting out of adjustment.
CURRENT SETTING

The minimum current at which the time 

current unit will close its contacts is determined

by the position of 

 plug in the tap block. The tap

 

 block 

IS 

marked   amperes, as shown

When the tap setting   changed with the relay in

its case, the following procedure must be followed:

(1) remove the connecting plug; this de-energizes

the relay and shorts the current transformer sec-

ondary 

(2) remove the tap plug and place

it   the tap marked for the desired pickup current.

(3) replace the connecting plug.

The minimum current required to rotate the

disk slowly and to close the contacts 

 with-

in five per cent of the value marked on the tap plate

for any tap setting and time dial position.   this

adjustment has been disturbed, it can be restored by

means of the spring adjusting ring. The ring can be

turned by inserting a screw driver blade in the

notches around the edge. By turning the ring, the

operating current of the unit can be brought into

agreement with the tap setting employed. This ad-

justment also permits any desired setting to be ob-

tained intermediate between the available tap settings.

Test connections for making pickup and time

checks on the time overcurrent unit are shown in

Fig. 13 and Fig. 14. Use a source of 120 volts or

greater with good wave form and constant frequency.

 transformers or phantom loads should not

be employed in testing induction relays since their

use may cause a distorted wave form.

 SETTING

The operating 

 of the time overcurrent unit

for any 

 value of current and tap setting is

determined by the time 

 setting. This operating

time is inversely proportional to the current magni-

tude as illustrated by the time curves in Figs. 16, 1’7

10

and 18. Note that the current values on these curves

are given as multiples of the tap setting. That is,

for a given time dial setting, the time will be the

same for 80 

 on the   ampere tap as for 50

amperes on the 5 ampere tap, since in both cases,

the current is 10 times tap setting.

 selective action of two or more relays is

required, determine the maximum possible short-

circuit current of the line and then choose-a time

value for each relay that differs sufficiently to in-

sure the proper sequence   the operation of the

several circuit breakers. Allowance must be made

for the time involved in opening each breaker after

the relay contacts close. For this reason, unless

the circuit time of operation is 

there should be a difference of about 0.5 second

(at the maximum current) between relays whose

operation is to be selective.
EXAMPLE OF 

The time and current settings of the time

overcurrent unit can be made easily and quickly.

Each time value shown in Figs. 16, 17 and   indi-

cates the time required for the contacts to close with

a particular time-dial setting when the current is a

prescribed number of times the current-tap, setting.

In order to obtain any particular time-current set-

ting, insert the removable plug in the proper tap

receptacle and adjust the time dial to the proper

position.

The following example illustrates the

procedure in making a relay setting.

Assume that the breaker is being used   a cir-

cuit where the circuit breaker should trip on a sus-

tained current of approximately 450 amperes, and

that the breaker should trip in one second on a short-

circuit current of 3750 amperes. Assume further

that current transformers of 

 ratio are used.

The current tap setting is found by dividing

minimum primary tripping current by the 

transformer ratio.

equals 7.5 amperes.

 this case, 450 divided   

Since there is no 7.5 ampere

 the B-ampere tap is used. To find the proper

time-dial setting to 

 one second time delay al

3750 

 divide 3750   the transformer ratio.

This 

 62.5 amperes 

 current which

is 7.3 times the &l-ampere setting. By referring to

the time-current curves 

 16. 17 and 113. it will

be seen that 7.3 times the 

 operating cur-

rent gives a one second time delay for a No. 3.4

time dial setting on an inverse time relay a No. 5.3

time dial setting on a very inverse time relay and a

No. 10 time dial setting on an extremely inverse

time relay.

The above results should   checked by means

of an accurate timing device. Slight readjustment of

the dial can be made until the desired time is

obtained.

Aid in making the proper selection of relay

settings may be obtained on application to the near-

est Sales 

 of the General Electric Company.

Courtesy of NationalSwitchgear.com

Summary of Contents for IBCG51E21

Page 1: ...S GROUND DIRECTIONAL OVERCURRENT RELAYS I v 1 5 r T r V Types IBCG51E21 and Up IBCGS2E21 and Up IBCG53E21and Up IBCG54E21 and Up IBCG77E IBCG78E I ffffftAL MANAGEMENT DEPARTMENT 6ENERALA ELECTRIC PHILADELPHIA PA Courtesy of NationalSwitchgear com ...

Page 2: ...UG BLOCK TARGET TIME OVERCURRENT UNIT TAP SCREW SEAL IN UNIT DRAG MAGNET DISK SPRING ADJUSTMENT RING LOW GRADIENT CONTACT STATIONARY LOW BACKSTOP SCREW GRADIENT CONTACT MOVING DIRECTIONAL UNIT TIME OVER CURRENT UNIT MAGNET AND COIL 4 ASSEMBLY THYRlTE CRADLE TRANSFORMER Type IBCG5 IE Courtesy of NationalSwitchgear com ...

Page 3: ...hould be used in cases where the fault current magnitude is depend ent mainly upon the location of the fault in relation to the relay and only slightly or not at all upon tbe system generating setup The reason for this is that relays must be set to be selective with maximum fault current flowing For fault currents below this value the operating time becomes greater as the current is decreased If t...

Page 4: ...ll operate repeatedly within one or two per cent of the same time CURRENT COILS The continuous and short time ratings of the 4 operating coil circuits are shown in Table The current polarizing coils have a rating of 5 amperes and a one 1 second rating of 150 amperes RATINGS OF OPERATING COIL CIRCUITS Ratings Cont One Sec Rating A m p s 1 5 100 l 1 5 2 2 5 3 4 5 6 5 200 4 5 6 8 10 12 16 10 220 l Th...

Page 5: ... residual circuits of current transformers The burden is therefore only imposed for duration the ground fault and need be considered only for this brief period TABLE IV CIRCUIT OF DIRECTIONAL AND OVERCURRENT UNIT OPERATING COILS AT GO CYCLES BURDENS AT MINIMUM PICKUP I React Ohms 20 0 2 65 0 76 5 10 0 17 0 44 1 40 0 16 0 042 Volt 3 Factor Min 22 5 5 60 2 90 0 83 13 3 5 60 1 40 0 85 0 96 0 51 8 15 ...

Page 6: ...I SEAL IN UNIT TOC TIME WERCURREMT UNIT D DIRECTIONAL UNIT SI SEAL IN UNIT TOC TIME OVERCURRENT UNIT D DIRECTIONAL UNIT m SHORT FfUGER SHORT FINGER IBCG5 IE 4 IBC52E Relay Cl D C2 1 OPER C2 Cl D 1 P2Vpi PER Cl D SI C2 7 TOC c2 WOUND SHADING COILS D D D C3 C4 CURR POL THYRITt C3 VC4 CURR POL THYRITE r TX TOC 1 TX Os I Os P3 UJJJ mrr u I 0 D PCT 5oclisi TX rrrn POT P4 POL u POL o ct ar Q Sl si i X X...

Page 7: ...ER QO 9 Connections IBCG78E Relay View IBC677E Relay A C us 1 2 A C BJS 3 TO NBJTRAL OF P0 TRANSFORMER WASE RELAYS U Li Ur1 raca V1 CO RUSE RELAYS 1 CO o TO 10 XI Hi RUSE QO 9 L RELAYS 1 1 p LA 7 LAJ L o L52M ejToc 9 TRIP US u 32 W4 1 t 32 I SIMILAR CIRCUITS FORMER 1 0 IP 1 SPi SIMILAR CIRCUITS FOR OTHER TO RELAYS 1 1 i 2 3 2 1 J 52 2 ROTE RELAY OPERATES FOR FAULTS IN DIRECTION OF JRRCW 3 2 1 CO a...

Page 8: ...phase field which in turn develops torque on the operating disk The very inverse and extremely inverse time units are of the type similar to that used in meters except as follows the upper portion of the iron structure has two con centric windings on the middle leg of the magnetic circuit One of these is a tapped current winding connected to taps on the tap block the other is a floating winding wh...

Page 9: ...ary contact members have made contact stationary contact support and the contact are assembled together b means of a mounting screw L and the two locknuts M Ground Directional Overcurrent Relay Type GEH 2032 INSTALLATION The location should be clean and dry free from dust and excessive vibration and well lighted to inspection testing The relay should be mounted on a vertical surface The outline pa...

Page 10: ...he time will be the same for 80 on the ampere tap as for 50 amperes on the 5 ampere tap since in both cases the current is 10 times tap setting selective action of two or more relays is required determine the maximum possible short circuit current of the line and then choose a time value for each relay that differs sufficiently to in sure the proper sequence the operation of the several circuit br...

Page 11: ... is sometimes prac tical to introduce a single phase current in one phase of the primary circuits in such a way that current flows through both the transformer neutral current transformer and one of the line current transformers If this cannot be done a careful wiring check must suffice Fig 15 shows the test connections for checking the polarity of the directional unit itself MAINTENANCE It is rec...

Page 12: ... off This gives access to the cup as sembly and exposes the assembly should be protected to keep it free from dust metallic particles until the nit is reassembled To remove the shaft and rotor from the head assembly the spring clip at the top of the must be pulled out and the clutch adjusting out of the side of the molded contact The shaft and can now be pulled out of molding The rotor must be han...

Page 13: ... should be potential or current polarization not both The 50 ohm resistor should be replaced an adjustable resistor capable of providing the current range listed in Table V relay rating in question A screw projecting from the side of the moving con tact controls the clutch pressure and quently the current value at which the clutch will slip With rated frequency and at rated volts for polarization ...

Page 14: ... and I Type 10 10 V a N sNi V A V CO 10 1 X I i 9 V 8 V V UJ 7 7 I f 4 s QO 9 X UJ v X CO 3 V o X o V x r 2 o CN O s aQ 00 s QO oo N E o K N 1 0 o 07 2 u 00 09 M joa 02 11 01 1 9 4 S 9 9 r 9 0 9 MULTIPLES OF RELAY TAP SETTING IBCG53 BCG5H 17 Time Current Curves 15 Courtesy of NationalSwitchgear com ...

Page 15: ...erse Time GEH 2032 IBCG Directional 90 40 30 20 10 7 3 2 CO 1 o in o 5 UJ CO k UJ 5 W Ik w v 10 6 in o 5 1 JO Jl J7 3 a 00 2 09 O M Q I 03 a E 2 H 02 01 30 40 90 80 70 80 00g 20 3 4 5 8 7 8 0 10 9 0 7 8 9 1 MULTI PLES OF RELAY TAP SETTING I8 Overcurrent Unit Courtesy of NationalSwitchgear com ...

Page 16: ...sions for Type 17 MTG MTG p 5 ft I 6 8 5 Q 1 T rofcS gJ 10 ir 3 j 8 STUOS i FOR SURFACE MTG CSJ T ro 1 3 5 7 9 Qgoop OOOQO 2 4 6 8 10 FRONT 10 32 SCREW 0R STUO n Ai 10 32 4MTG 8 SCREW li II 2 27 2 27 CASE X_ in 7 UJ 32 32 32 32 J O i RANEL J l 4DRILL H 6 HOLES cc z O ft m co 4DRILL 4 10 HOLES 3 K 2J J 0 m r 0 i Ul o JC CLUJ CVJ Ul 1 ro cro X G 1 3 o 2 fls 5 b 1 o 5 UJ iSM HJ it JJJ z a O Q HARDWAR...

Reviews: