background image

 

 

 

 

,

INTRODUCTION

Type 

 relays are ground directional 

current relays used primarily for the protection of

feeders and transmission lines. They are available

with either inverse, very inverse or extremely in-

verse time characteristics.

They consist of two units, a time overcurrent unit

 (top) of 

 induction disk type, and an instantaneous

power 

 unit 

(bottom) 

of the induction cup

type. The directional unit is either potential or cur-

rent polarized or both and, by means of its closing

contacts, directionally control,: the operation of the

time overcurrent unit.

Type 

 relays are used for 

 of a single line. They 

 low-range 

 coil which may be rated 

 or 

 am-

peres, although the 

 ampere rating is also

available. Under normal conditions, 

in either the 

 or current polarizing coils;

nor is there any voltage 

 coils.

Fig. 9 shows the external connections when the

 

 relay   used in conjunction with phase

relays polarized from wye-wye 

The polarizing voltage for the ground relay is

obtained by means of an auxiliary wye-broken-delta

potent&l transformer.

Fig. 

10 shows the external connections for the

Type

 ground relay when current 

from a local source of ground current.

On some applications, system conditions may

at 

 

   such that potential polarization is

desirable, and at other times be such that current

polarization would be preferred. The Type 

relay, with its dual polarization feature, is well suit-

ed for such applications. The curves 

 2 

 the 

 its performance when either potential or current

polarized alone. The simultaneous use of both sets

of polarizing coils is advantageous on applications

where current and potent&l polarizing sources are

available and there is a possibility that one or the

other source may   temporarily lost.

The differences between the various models

covered by this instruction book are shown   Table 1.

Inverse time relays should be used on systems

where the fault current flowing through a given relay

is 

 by the 

system generating cap-

acity at the time of the fault. Very inverse time and

extremely inverse time relays should be used in

cases where the fault current magnitude is depend-

ent mainly upon the location of the fault in relation to

the relay, and only slightly or not at all upon tbe

system generating setup. The reason for this is that

relays must 

be 

set to 

be 

selective with maximum

fault current flowing. For fault currents below this

value, the operating time becomes greater as the

current is decreased. If there is a wide range in

generating capacity, together 

 in 

circuit current with fault position, the operating time

with minimum fault current may 

be 

exceedingly long

with very inverse time relays and even longer with

extremely inverse time relays. For such cases, the

inverse time relay is more applicable.

The choice between very inverse and extremely

inverse time relays is more limited than between

them and the inverse time relay as they are more

nearly 

 in their time-current characteristic

curves. For grading with fuses the extremely in-

verse time relay should 

be 

chosen as the time-cur-

rent curves more nearly match the fuse curve.

Another advantage of the extremely inverse relay

is that 

it is 

better 

suited than both the inverse and

very inverse relays for picking up cold load. For

any 

 cold load pick-up capability, the resulting

settings will provide faster protection at high fault

currents with the extremely inverse relay than with

the less inverse relays.

TABLE I

Time

Circuit

teristic

 

contacts

Inverse

One

Inverse

 

 Very Inverse

Fig. 4

 Very Inverse

Fig. 5

 

 Inverse

 

  I n v e r s e   T w o

Fig. 6

 

PICKUP

When potential polarized, the directional unit

will operate at 3.6 volt-amperes at the 

Courtesy of NationalSwitchgear.com

Summary of Contents for IBCG51E21

Page 1: ...S GROUND DIRECTIONAL OVERCURRENT RELAYS I v 1 5 r T r V Types IBCG51E21 and Up IBCGS2E21 and Up IBCG53E21and Up IBCG54E21 and Up IBCG77E IBCG78E I ffffftAL MANAGEMENT DEPARTMENT 6ENERALA ELECTRIC PHILADELPHIA PA Courtesy of NationalSwitchgear com ...

Page 2: ...UG BLOCK TARGET TIME OVERCURRENT UNIT TAP SCREW SEAL IN UNIT DRAG MAGNET DISK SPRING ADJUSTMENT RING LOW GRADIENT CONTACT STATIONARY LOW BACKSTOP SCREW GRADIENT CONTACT MOVING DIRECTIONAL UNIT TIME OVER CURRENT UNIT MAGNET AND COIL 4 ASSEMBLY THYRlTE CRADLE TRANSFORMER Type IBCG5 IE Courtesy of NationalSwitchgear com ...

Page 3: ...hould be used in cases where the fault current magnitude is depend ent mainly upon the location of the fault in relation to the relay and only slightly or not at all upon tbe system generating setup The reason for this is that relays must be set to be selective with maximum fault current flowing For fault currents below this value the operating time becomes greater as the current is decreased If t...

Page 4: ...ll operate repeatedly within one or two per cent of the same time CURRENT COILS The continuous and short time ratings of the 4 operating coil circuits are shown in Table The current polarizing coils have a rating of 5 amperes and a one 1 second rating of 150 amperes RATINGS OF OPERATING COIL CIRCUITS Ratings Cont One Sec Rating A m p s 1 5 100 l 1 5 2 2 5 3 4 5 6 5 200 4 5 6 8 10 12 16 10 220 l Th...

Page 5: ... residual circuits of current transformers The burden is therefore only imposed for duration the ground fault and need be considered only for this brief period TABLE IV CIRCUIT OF DIRECTIONAL AND OVERCURRENT UNIT OPERATING COILS AT GO CYCLES BURDENS AT MINIMUM PICKUP I React Ohms 20 0 2 65 0 76 5 10 0 17 0 44 1 40 0 16 0 042 Volt 3 Factor Min 22 5 5 60 2 90 0 83 13 3 5 60 1 40 0 85 0 96 0 51 8 15 ...

Page 6: ...I SEAL IN UNIT TOC TIME WERCURREMT UNIT D DIRECTIONAL UNIT SI SEAL IN UNIT TOC TIME OVERCURRENT UNIT D DIRECTIONAL UNIT m SHORT FfUGER SHORT FINGER IBCG5 IE 4 IBC52E Relay Cl D C2 1 OPER C2 Cl D 1 P2Vpi PER Cl D SI C2 7 TOC c2 WOUND SHADING COILS D D D C3 C4 CURR POL THYRITt C3 VC4 CURR POL THYRITE r TX TOC 1 TX Os I Os P3 UJJJ mrr u I 0 D PCT 5oclisi TX rrrn POT P4 POL u POL o ct ar Q Sl si i X X...

Page 7: ...ER QO 9 Connections IBCG78E Relay View IBC677E Relay A C us 1 2 A C BJS 3 TO NBJTRAL OF P0 TRANSFORMER WASE RELAYS U Li Ur1 raca V1 CO RUSE RELAYS 1 CO o TO 10 XI Hi RUSE QO 9 L RELAYS 1 1 p LA 7 LAJ L o L52M ejToc 9 TRIP US u 32 W4 1 t 32 I SIMILAR CIRCUITS FORMER 1 0 IP 1 SPi SIMILAR CIRCUITS FOR OTHER TO RELAYS 1 1 i 2 3 2 1 J 52 2 ROTE RELAY OPERATES FOR FAULTS IN DIRECTION OF JRRCW 3 2 1 CO a...

Page 8: ...phase field which in turn develops torque on the operating disk The very inverse and extremely inverse time units are of the type similar to that used in meters except as follows the upper portion of the iron structure has two con centric windings on the middle leg of the magnetic circuit One of these is a tapped current winding connected to taps on the tap block the other is a floating winding wh...

Page 9: ...ary contact members have made contact stationary contact support and the contact are assembled together b means of a mounting screw L and the two locknuts M Ground Directional Overcurrent Relay Type GEH 2032 INSTALLATION The location should be clean and dry free from dust and excessive vibration and well lighted to inspection testing The relay should be mounted on a vertical surface The outline pa...

Page 10: ...he time will be the same for 80 on the ampere tap as for 50 amperes on the 5 ampere tap since in both cases the current is 10 times tap setting selective action of two or more relays is required determine the maximum possible short circuit current of the line and then choose a time value for each relay that differs sufficiently to in sure the proper sequence the operation of the several circuit br...

Page 11: ... is sometimes prac tical to introduce a single phase current in one phase of the primary circuits in such a way that current flows through both the transformer neutral current transformer and one of the line current transformers If this cannot be done a careful wiring check must suffice Fig 15 shows the test connections for checking the polarity of the directional unit itself MAINTENANCE It is rec...

Page 12: ... off This gives access to the cup as sembly and exposes the assembly should be protected to keep it free from dust metallic particles until the nit is reassembled To remove the shaft and rotor from the head assembly the spring clip at the top of the must be pulled out and the clutch adjusting out of the side of the molded contact The shaft and can now be pulled out of molding The rotor must be han...

Page 13: ... should be potential or current polarization not both The 50 ohm resistor should be replaced an adjustable resistor capable of providing the current range listed in Table V relay rating in question A screw projecting from the side of the moving con tact controls the clutch pressure and quently the current value at which the clutch will slip With rated frequency and at rated volts for polarization ...

Page 14: ... and I Type 10 10 V a N sNi V A V CO 10 1 X I i 9 V 8 V V UJ 7 7 I f 4 s QO 9 X UJ v X CO 3 V o X o V x r 2 o CN O s aQ 00 s QO oo N E o K N 1 0 o 07 2 u 00 09 M joa 02 11 01 1 9 4 S 9 9 r 9 0 9 MULTIPLES OF RELAY TAP SETTING IBCG53 BCG5H 17 Time Current Curves 15 Courtesy of NationalSwitchgear com ...

Page 15: ...erse Time GEH 2032 IBCG Directional 90 40 30 20 10 7 3 2 CO 1 o in o 5 UJ CO k UJ 5 W Ik w v 10 6 in o 5 1 JO Jl J7 3 a 00 2 09 O M Q I 03 a E 2 H 02 01 30 40 90 80 70 80 00g 20 3 4 5 8 7 8 0 10 9 0 7 8 9 1 MULTI PLES OF RELAY TAP SETTING I8 Overcurrent Unit Courtesy of NationalSwitchgear com ...

Page 16: ...sions for Type 17 MTG MTG p 5 ft I 6 8 5 Q 1 T rofcS gJ 10 ir 3 j 8 STUOS i FOR SURFACE MTG CSJ T ro 1 3 5 7 9 Qgoop OOOQO 2 4 6 8 10 FRONT 10 32 SCREW 0R STUO n Ai 10 32 4MTG 8 SCREW li II 2 27 2 27 CASE X_ in 7 UJ 32 32 32 32 J O i RANEL J l 4DRILL H 6 HOLES cc z O ft m co 4DRILL 4 10 HOLES 3 K 2J J 0 m r 0 i Ul o JC CLUJ CVJ Ul 1 ro cro X G 1 3 o 2 fls 5 b 1 o 5 UJ iSM HJ it JJJ z a O Q HARDWAR...

Reviews: