Chapter 1 • Introduction
1-2
Rev. 6, March 2011
Part 17997
The Hydran 201
i
System consists of an Intelligent Transmitter, named the Hydran 201T
i
,
and a family of Controllers, collectively named the Hydran 201C
i
Controllers.
When the Hydran 201T
i
Intelligent Transmitter is combined with the Hydran 201C
i
-1
One-Channel Controller, it is called a Hydran 201R Model
i
Incipient Fault Monitor. A
Hydran 201T
i
being used alone or with other Hydran 201C
i
Controllers is named a
Hydran 201
i
System Incipient Fault Monitor.
Both the Hydran 201R Model
i
and the Hydran 201
i
System Incipient Fault Monitors can
be networked. The network can be tied to a Supervisory Control and Data Acquisition
(SCADA) computer with a single RS-232 line, either locally at the substation or remotely
through a telephone line and modem.
1.2
COMPONENTS OF THE HYDRAN 201
I
SYSTEM
1.2.1
Hydran 201T
i
Intelligent Transmitter
The Hydran 201T
i
Intelligent Transmitter (Figure 1-1 on page 1-3) is the foundation upon
which the Hydran 201
i
System is built. It consists of a small cylindrical enclosure which
attaches directly to a transformer valve using a brass adaptor. This enclosure contains a
standard Hydran sensor, a thermal conditioning system and a microprocessor-based
intelligent electronic transmitter.
Terminal blocks are provided for easy connection of: ac power; alarm contacts (Gas High,
Gas High-High and System Fail); supervisory link; and one isolated, analog 4–20 mA
output. An RS-232 connector is provided for local computer interface.
A membrane keypad and an alphanumeric, backlit, LCD display enable full interaction
with the unit without requiring the use of an external computer.
The H201T
i
is described in detail in Chapter 2.
Summary of Contents for Hydran 201i
Page 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Page 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Page 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Page 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Page 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 299: ......