NE-M Installation Guide
H5692448
850050111
Issue 03 August 2017
13
Table 1 Rectifiers and Converters
Rectifier/Converter
Input
Output
Eco Compatible
Eco Rectifier
blue
NE050ECO48ATEZ
ac 110/200-240 Vac
dc 60Vdc (+/-30V)
to 310Vdc (+/-150)
11A max
48V
, 50A
Yes
Eco Rectifier
orange
NE100ECO24TEZ
ac 110/200-240 Vac
dc 60Vdc (+/-30V)
to 310Vdc (+/-150)
11A max
24V
, 100A
Yes
Converter
blue
NE040DC48ATEZ
24 Vdc
48V
, 40A
Yes
NE030DC48A
48V
, 30A
Yes
Converter
orange
NE075DC24A
48 Vdc
24V
, 75A
Yes
Rectifier
blue
NE075AC48ATEZ
110/200-277 Vac
48V
, 75A
AC Only
NE055AC48ATEZ
110/200-277 Vac
48V
, 55A
NE050AC48ATEZ
110/200-277 Vac
48V
, 50A
NE050AC48A
200-240 Vac
48V
, 50A
Rectifier
orange
NE100AC24ATEZ
110/200-277 Vac
24V
, 100A
AC Only
NE100AC24A
208/200-240 Vac
NE850 Slot Filler
6
REQUIRED
– Eco rectifiers in all DC (PV or solar) powered rectifier positions.
RECOMMENDED
– Eco rectifiers in all Eco system rectifier positions.
NOT RECOMMENDED –
non-Eco rectifiers
in Eco systems.
Non Eco rectifiers will not function properly when powered by DC (PV or solar) input in Eco systems.
Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling all system rectifier positions.
Non Eco rectifiers may be installed in AC powered rectifier positions of Eco systems.
7
44A with 120Vac input
8
22A with 120Vac input
9
NOT RECOMMENDED for use in Eco systems
- Non Eco rectifiers will not function properly when powered by DC (PV or
solar) input in Eco systems.
Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling system rectifier positions.
10
25A with 120Vac input
11
50A with 120Vac input
12
Non-TEZ rectifiers are no longer orderable and have lower efficiency than TEZ rectifiers