Relocation Procedures 

Note: in case relocation is required, the joint of evaporator gas/liquid pipes of the indoor unit shall be cut off with 
a cutting knife. Connection is only allowed after re-flaring (the same to the outdoor unit).  

Maintenance Instructions 

Maintenance Precautions 

Precautions 

• 

For all the faults requiring welding the refrigeration pipelines or components inside the refrigeration system 

of R32 refrigerant air conditioners, maintenance at the user’s site is never allowed.  
• 

For the faults requiring radical disassembly and bending operation of the heat exchanger, such as the 

replacement of the outdoor unit chassis and integral disassembly of the condenser, inspection and maintenance at 
the user’s site are never allowed. 
• 

For the faults requiring replacement of the compressor or parts & components of refrigeration system, 

maintenance at the user’s site is not allowed. 
• 

For other faults not involved in the refrigerant container, internal refrigeration pipelines and refrigeration 

elements, the maintenance at the user’s site is allowed, including the cleaning and dredging of the refrigeration 
system requiring no disassembly of refrigeration elements and no welding.  
• 

In case replacement of gas/liquid pipes is required during maintenance, the joint of evaporator gas/liquid 

pipes of the indoor unit shall be cut off with a cutting knife. Connection is only allowed after re-flaring (the same 
to the outdoor unit).  

Qualification Requirements of Maintenance Personnel 

1. 

All the operators or the maintenance personnel involved in refrigerating circuits shall be provided with the 

effective certificate issued by an industry-accepted assessment institute, to ensure that they are qualified for safety 
disposal of refrigerant as required in the assessment regulations.  
2. 

The equipment can only be maintained and repaired as per the method recommended by the manufacturer. 

In case the assistance from personnel of other disciplines is required, the assistance shall be supervised by the 
personnel with qualification certificate involved in flammable refrigerant.  

7

Summary of Contents for GES-NIG25OUT

Page 1: ...e front grille Loading and Unloading Transporting Management Storage Requirements 3 Installation Instructions 3 Relocation Procedures 7 Maintenance Instructions 7 Scrapping and Recovery 10 Indoor Outd...

Page 2: ...n easily nd it Install the air conditioner in accordance with the instructions in this installation manual Be sure to use only the specified accessories and parts for installation work Install the air...

Page 3: ...lation Air conditioners must be treated at a specialized treatment facility for reuse recycling and recovery By ensuring this product is disposed of correctly you will help to prevent potential negati...

Page 4: ...e white or red white reflective stripes shall be pasted on the sides and tail of the transporting vehicles to remind the vehicles behind of keeping distance 9 The transporting vehicles shall run at a...

Page 5: ...re source and oil heater shall be avoided below the indoor unit 4 The power supply shall be provided with earthing wire and be reliably earthed 5 While punching the wall with an electric drill whether...

Page 6: ...ting solution The pressure shall be maintained for more than 5 minutes and then whether the system pressure is reduced or not shall be observed In case the pressure is reduced leakage can be identifie...

Page 7: ...tallation is firm or not The unit may fall vibrate or make a noise Whether the inspection on air leakage is completed The refrigerating capacity heating capacity may be insufficient Whether the unit i...

Page 8: ...ontainer internal refrigeration pipelines and refrigeration elements the maintenance at the user s site is allowed including the cleaning and dredging of the refrigeration system requiring no disassem...

Page 9: ...Nitrogen cylinders acetylene cylinders and oxygen cylinders shall be placed separately The distance between the gas cylinders above and the working area involved in open fire shall be at least 6m The...

Page 10: ...the refrigeration system shall be earthed The refrigerant charged shall be of the type and volume specified on the nameplate Excessive charging is not allowed After maintenance of the refrigeration sy...

Page 11: ...During the use of refrigerant charging tools cross contamination of different refrigerants shall be avoided The total length including the refrigerant pipelines shall be shortened as much as possible...

Page 12: ...vacuumized before usage and be kept under normal temperature if possible The recovery equipment shall always be under favorable working state and be equipped with operation instructions to facilitate...

Page 13: ...y attaching a vibration proof mat The marks from to in the gure are the parts numbers The distance between the indoor unit and the oor should be more than 2m The models adopt HFC refrigerant R32 more...

Page 14: ...e Heating insulating material Piping hole cover Fixing of outdoor unit Fix the unit to concrete or block with bolts 10mm and nuts rmly and horizontally When tting the unit to wall surface roof or roof...

Page 15: ...WARNING CAUTION N Open the window and well ventilated the room explosion proof fuse 14...

Page 16: ...32 3 fire or explosion will be caused fire or explosion fire or explosion fire or explosion fire or explosion fire explosion 15...

Page 17: ...R32 2 3 R 2 3 R R32 R32 R32 R32 R32 16...

Page 18: ...shock fire or explosion Install a explosion proof breaker for current leakage at the power source to avoid the risk of the electric shock Do not use large capacity fuses steel wire or copper wire Dam...

Page 19: ...R32 R32 R32 R32 R32 R32 R32 R32 R32 18...

Page 20: ...3 R32 R32 R32 R32 R32 R32 R32 19...

Page 21: ...R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A 20...

Page 22: ...G50OUT GES NMG70OUT GES NJG25OUT 800 280 550 510 130 313 GES NJG35OUT 800 280 550 510 130 313 GES NJG50OUT GEM NM40OUT M 780 270 540 566 106 5 317 GEM NM50OUT M 810 288 688 583 113 5 319 5 800 280 550...

Page 23: ...tion A is more than 5m oil trap shoud be installed every 5 7 Max Length In case the pipe length B is more thanDm the refrigerant should be charged according to E g m Connection of pipes charge additio...

Page 24: ...23...

Page 25: ...24 R32 R32...

Page 26: ...mm2 4G1 0mm 2 4G1 0mm 2 GES NIG25OUT GES NIG35OUT GES NMG25OUT GES NMG35OUT GES NJG25OUT GES NJG35OUT GES NJG50OUT GES NMG50OUT GES NIG25OUT GES NMG25OUT GES NIG35OUT GES NMG35OUT GES NJG50OUT GES NMG...

Page 27: ...poor 17 16 15 Lack of refrigerant Check if there is leakage in the unit m 26 Model Connecting wiring Power cable 3G2 5 mm 2 4G1 0 mm 2 DOUBLE DOUBLE GEM NM40OUT M GEM NM50OUT M GEM NM40OUT M GEM NM50...