22
1.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
To bend a pipe, give the roundness as large as possible not to crush the pipe ,
and the bending radius should be 30 to 40 mm or longer.
Connecting the pipe of gas side rst makes working easier.
The connection pipe is specialized for R32.
Half union
Flare nut
Torque wrench
CAUTION
Be careful that matters, such as wastes of sands,water,, etc. shall not enter the pipe.
The standard pipe length is Cm. If it is over D m, the function of the unit will be affected. If the pipe has
to be lengthened, the refrigerant should be charged, according to E g/m. But the charge of refrigerant
must be conducted by professional air conditioner engineer. Before adding additional refrigerant,
perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then
Spanner
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Pipe Diameter( )
Fastening torque
Liquid side6.35mm(1/4")
18N.m
Liquid/Gas side9.52mm(3/8")
42 N.m
Gas side 12.7mm(1/2")
55N.m
Gas side 15.88mm(5/8")
60 N.m
Max.Elevation:
In case the elevation A is more
than 5m, oil trap shoud be
installed every 5~7
Max. Length:
In case the pipe length B is
more thanDm, the refrigerant
should be charged, according
to E g/m.
Connection of pipes
charge
additional refrigerant.
Amax
Bmax
2.
M i n. Length: B min
In case the elevation B is more than 5m,
oil trap shoud be installed every 5~7m
Max. Length: B1 max =20m B2 max =20m
Max.Elevation: A1 max =15m A2 max =15m
In case the pipe total length (B1+B2) is more than
20m, the refrigerant should be charged, according
to 20 g/m.
B
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
Outdoor unit
Indoor unit
B1
Indoor unit
B2
Outdoor unit
Indoor unit
Oil trap
A3
A3 max =15m
(B1+B2) max =30m
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
CAUTION
Indoor unit
Min. Length: B1 min =3m B2 min =3m
GES-NIG25OUT
GES-NIG35OUT
GES-NMG25OUT
GES-NMG35OUT
GES-NMG70OUT
GES-NJG25OUT
GES-NJG35OUT
GES-NJG50OUT
GES-NMG50OUT
GEM-NM40OUT M
GEM-NM50OUT M
6.35x0.65mm
9.52x0.65mm
6.35x0.65mm
12.7x0.7mm
Outdoor Unit
Amax Bmax
C
D
E
GEM-NM40OUT M
GEM-NM50OUT M
15
20
5
7
20
15
20
5
7
20
Outdoor Unit
Amax Bmax
C
D
E
GES-NIG25OUT
10
15
5
7
20
GES-NIG35OUT
10
15
5
7
20
GES-NMG25OUT
GES-NMG35OUT
10
15
5
7
20
GES-NMG50OUT
GES-NMG70OUT
GES-NJG25OUT
10
15
5
10
20
GES-NJG35OUT
10
15
5
10
20
GES-NJG50OUT
10
15
5
7
20
15
25
5
7
20
15
25
5
7
20
15
25
5
10
20
Bmin
3
3
3
3
3
3
3
3
3
Bmin
3
3
Summary of Contents for GEM-NM40OUT M
Page 15: ...WARNING CAUTION N Open the window and well ventilated the room explosion proof fuse 14 ...
Page 17: ...R32 2 3 R 2 3 R R32 R32 R32 R32 R32 16 ...
Page 19: ...R32 R32 R32 R32 R32 R32 R32 R32 R32 18 ...
Page 20: ...3 R32 R32 R32 R32 R32 R32 R32 19 ...
Page 21: ...R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A 20 ...
Page 24: ...23 ...
Page 25: ...24 R32 R32 ...