background image

Step 6: Combine the zip ties to make a loop and install zip ties around top set of breakers in panel as shown in 

picture below. Pull on ends to make tight around breakers. Trim zip ties as needed and install Warning 
label next to release tab on zip tie at generator breaker

 

 
Step 7: Re-Install panel cover, Verify proper operation of interlock. Main breaker 

ON,

 generator breaker 

OFF

 

and generator breaker 

CAN NOT

 be turned on.   Generator breaker 

ON

, main breaker 

OFF

 and main 

breaker 

CAN NOT

 be turned on. Please verify that inside panel cover is touching all breaker, if not 

adjust panel cover with top and bottom screw on cover. 

 

  

         

 

 

      Generator On 

 

 

 

     Main On 

Place Generator start-up procedure label on panel box, Place CAUTION label on panel box and electric meter 
pan. 
 
The MAIN and the GENERATOR breakers should NEVER be able to be turned on at the same time.  If panel 
cover is removed the Generator breaker is NEVER to be turned on.  If for any reason the interlock does not 
function properly, DO NOT USE and contact us immediately at 

[email protected]

 for support and 

instructions. 
 
Thank You for your support, 
GenInterlock Team 
 

DISCLAIMER: 

GenInterlock.com is NOT responsible for misuse or improper 

installation. All electrical equipment should be installed and maintained by 
qualified personnel. Any consequences arising from improper use is the 
responsibility of the user.   
 

GenInterlock.com 

[email protected]

 

732-339-4191

 

Reviews: