3-2
3-3
3.2.2 Program Mode
Program mode provides various functions, such as setting and checking function code data, monitoring mainte-
nance information and checking input/output (I/O) signal status. These functions can be easily selected with the
menu-driven system. Table 3.2 lists menus available in Program mode. The leftmost digit (numeral) of each letter
string indicates the corresponding menu number and the remaining three digits indicate the menu contents.
When the drive re-enters Program mode, the menu that was selected last in Program mode will be displayed.
Restricting menus to be displayed
In order to simplify operation, the menu-driven system has a special function (specified by function code E52)
that restricts the menus to be displayed. The factory default is to display Menu #1 “Data setting” only, allowing no
switching to any other menu.
Function Code E52 – Keypad (Mode Selection)
Function code data (E52)
Menus selectable
0: Function code data setting mode
Menu #1 “Data setting” (factory default)
1: Function code data check mode
Menu #2 “Data checking”
2: Full-menu mode
Menu #1 through #6 (#7*)
* Menu #7 appears only when the remote keypad (option) is set up for use.
If the full-menu mode is selected, pressing the or key will cycle through menus. With the key, you may select
the desired menu. Once all of the menus have been cycled through, the display will return to the first menu.
Table 3.2 Menus Available in Program Mode
Menu
LED
monitor
shows:
Main functions
Refer to:
Menu #1
“Data setting”
1.F_ _
F codes (Fundamental functions)
Selecting each of these function codes
enables its data to be displayed/
changed.
Section 3.4
1.E_ _
E codes (Extension terminal functions)
1.C_ _
C codes (Control functions of frequency)
1.P_ _
P codes (Motor parameters)
1.H_ _
H codes (High performance functions)
1.J_ _
J codes (Application functions)
1.y_ _
y codes (Link functions)
Menu #2
“Data checking”
2. EP
Displays only function codes that have been changed from their factory defaults.
You may refer to or change those function codes data.
Section 3.5
Menu #3
“Drive monitoring”
3.oPE
Displays the running information required for maintenance or test running.
Section 3.6
Menu #4
“I/O checking”
4. _o
Displays external interface information.
Section 3.7
Menu #5
“Maintenance
information”
5.CHE
Displays maintenance information including accumulated running time.
Section 3.9
Menu #6
“Alarm information”
6.AL
Displays the latest four alarm codes. You may refer to the running information at the
time when the alarm occurred.
Section 3.9
Menu #7
“Data copying”
7.CPy
Allows you to read or write function code data, as well as verifying it.
NOTE: To use this function, a remote keypad (option) is necessary.
StockCheck.com
Summary of Contents for Fuji Electric MICRO-SAVER AF-300
Page 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Page 20: ...1 4 Notes S t o c k C h e c k c o m ...
Page 36: ...2 16 Notes S t o c k C h e c k c o m ...
Page 56: ...3 20 Notes S t o c k C h e c k c o m ...
Page 102: ...7 8 Notes S t o c k C h e c k c o m ...
Page 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Page 118: ...8 16 Notes S t o c k C h e c k c o m ...