17
FVR-C9S-2UX
Applicable motor output [Hp]
1/8
1/4
1/2
1
2
3
5
Drive type
FVRF12
FVRF25
FVRF50
FVRF001 FVRF002 FVRF003 FVRF005
C9S-2UX C9S-2UX C9S-2UX C9S-2UX C9S-2UX C9S-2UX C9S-2UX
Output rated capacity
[kVA]
0.28
0.56
1.0
1.6
2.8
4.0
6.6
Applicable wire size
Main circuit
14
12
(AWG)
Contol circuit
24
MCCB
15
20
30
ELCB
15
20
30
Listed fuse*
5
10
20
30
* The use of quick-acting fuses is required to validate UL listings. The factory recommendation is
C92-2-15
Bussman type JKS or equivalent.
CAUTION:
The control circuit terminal wiring should be
kept as far as possible from the main circuit
wiring to prevent operational error due to
noise interference. Never install them in the
same duct or conduit. (A separation dis-
tance of 4 inches [10cm] or more is recom-
mended.) If the control circuit wiring must
cross the main circuit wiring, make sure it
crosses at a right angle.
Use shielded, twisted wire for the control
circuit wiring , which should be as short as
possible (65 feet [20m] or less).
Install a surge absorber in parallel with any
magnet contactors, solenoids, relays or
timer coils, which are close to the drive.
Long wire lengths between the motor and
the drive will result in increased capacitance
and leakage current. This may cause earlier
activation of such protective function as
overcurrent protection, overheating protec-
tion and electronic thermal overload, or the
error in current detection may become large.
To avoid these, adjust the length of wiring
between the drive and the motor so that is
does not exceed the length shown below.
FVRF12C9S-2UX : 165 feet (50m)
FVRF25 to 005C9S-2UX : 325 feet (100m)
9. Application of Wiring and Equipment
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com