5-30
750/760 Feeder Management Relay
GE Multilin
5.5 S4 OUTPUT RELAYS
5 SETPOINTS
5
5.5.4 AUXILIARY RELAYS
PATH: SETPOINTS
ÖØ
S4 OUTPUT RELAYS
ÖØ
3(7) AUX RELAY
Figure 3–9: Typical Wiring Diagram on page 3–7 shows relay contacts with no control power applied. If the
RELAY 3(7) NON-
OPERATED STATE
setpoint is “De-energized”, then the state of the relay contacts is as shown in the wiring diagram. If the
non-operated state is “Energized”, then the state of the relay contacts is opposite to that shown in the wiring diagram.
This
PULSED OUTPUT DWELL TIME
setpoint is only displayed if the
RELAY 3 OUTPUT TYPE
is selected as "Pulsed". This set-
point determines the time interval that the pulsed contacts remain in the operated state.
Figure 5–3: OUTPUT RELAYS 3 TO 7 AUXILIARY LOGIC
3 AUX RELAY
[ENTER] for more
RELAY 3 NAME:
Auxiliary
Range: 16 alphanumeric characters
RELAY 3 NON-OPERATED
STATE: De-energized
Range: Energized, De-energized
RELAY 3 OUTPUT TYPE:
Self-Resetting
Range: Self-Resetting, Latched, Pulsed
PULSED OUTPUT DWELL
TIME:
0.1 s
Range: 0.1 to 6000.0 s in steps of 0.1. Seen only if
RELAY 3(7) OUTPUT TYPE
is
"Pulsed"
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE