8 COMMISSIONING TESTS
8.7 PLACING THE RELAY IN SERVICE
8
10. Under subheading
A2 METERING
ÖØ
DMND
ÖØ
REACTIVE PWR
, verify the
LAST REACTIVE PWR DMND
and
MAX REACTIVE
PWR DMND
values.
11. Under subheading
A2 METERING
ÖØ
DMND
ÖØ
APPARENT PWR
, verify the
LAST APPARENT PWR DMND
and
MAX APPAR-
ENT PWR DMND
values.
8.7.3 DIELECTRIC STRENGTH TESTING
A fully assembled production version of the relay is tested in its metal case. The dielectric strength of all the input/output
terminals are tested with respect to its grounded chassis and Terminal G12 (safety ground). The test voltage of the tester,
from the initial value of 0 V AC, is raised to 1.6 kV AC in such a manner (slowly) that no appreciable transients occur. The
voltage is maintained for 1 minute and is then reduced smoothly to zero as rapidly as possible. According to IEC255-5, the
Hi-Pot test is repeated with a voltage not less than 500 V AC.
Figure 8–7: DIELECTRIC STRENGTH WIRING