Table 3.15. Trip Rating Plug Specifications
Trip Plug Catalog
Number
Plug
Rating
May Be Used With
Minimum
Sensor
Maximum
Sensor
GTP0060U0101
60A
1
150A
3
150A
3
GTP0080U0101
80A
1
150A
3
200A
4
GTP0100U0103
100A
2
150A
3
200A
4
GTP0125U0103
125A
1
150A
3
200A
4
GTP0150U0404
150A
150A
3
400A
GTP0200U0404
200A
200A
4
400A
GTP0225U0406
225A
400A
600A
GTP0250U0407
250A
400A
630A5
GTP0300U0408
300A
400A
800A
GTP0350U0408
350A
400A
800A
GTP0400U0410
400A
400A
1000A
GTP0450U0612
450A
600A
1200A
GTP0500U0613
500A
600A
1250A
5
GTP0600U0616
600A
600A
1600A
GTP0700U0816
700A
800A
1600A
GTP0750U0820
750A
800A
2000A
GTP0800U0820
800A
800A
2000A
GTP0900U1020
900A
1000A
2000A
GTP1000U1025
1000A
1000A
2500A
GTP1100U1225
1100A
1200A
2500A
GTP1200U1232
1200A
1200A
3200A
GTP1500U1640
1500A
1600A
4000A
GTP1600U1640
1600A
1600A
4000A
GTP1900U2050
1900A
2000A
5000A
GTP2000U2050
2000A
2000A
5000A
GTP2200U2550
2200A
2500A
5000A
GTP2400U2564
2400A
2500A
6400A
5
GTP2500U2564
2500A
2500A
6400A
5
GTP3000U3064
3000A
3000A
6400A
5
GTP3200U3264
3200A
3200A
6400A
5
GTP3600U4064
3600A
4000A
6400A
5
GTP4000U4064
4000A
4000A
6400A
5
GTP4000K4040
6
4000A
4000A
4000A
GTP5000U5064
5000A
5000A
6400A
5
GTP6000U6064
6000A
6000A
6400A
5
1 WavePro & AKR only. EntelliGuard G min. trip plug is 150A.
2 PowerBreak only. EntelliGuard G min. trip plug is 150A.
3 WavePro & AKR only. EntelliGuard G min. sensor is 400A.
4 PowerBreak only. EntelliGuard G min. sensor is 400A.
5 IEC only sensor, UL equivalents are 600A.
6 Used on ITE and Allis Chalmers Conv Kits
Table 3.16. Trip Rating Plug Codes
Sensor Designation
Sensor Rating
01
150A
1
02
200A
2
03
225A
4
04
400A
06
600A
07
630A
3
08
800A
10
1000A
12
1200A
13
1250A
3
16
1600A
20
2000A
25
2500A
30
3000A
32
3200A
40
4000A
50
5000A
60
6000A
64
6400A
3
1 Sensor available in WavePro and AKR only.
2 Sensor available in Power Break only.
3 Sensor available in IEC listed circuit breaker only.
4 Used on Conv Kits
Table 3.17 lists the plugs available for each sensor in the
various circuit breakers in which the EntelliGuard TU may be
installed.