DET-653C
EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12
Section 5. Catalog Numbering Guide
©2012 General Electric All Rights Reserved
62
Digit 6 – Mounting Type Poles
Designation
Mounting
Poles
Code
OEM
drawout
3
1
4, right
2
4, left
3
stationary
3
4
4, right
5
4, left
6
GE Equipment
drawout
3
D
stationary
3
F
•
Right, Left indicates the location of the fourth pole, typically used to
switch the neutral.
•
Stationary and drawout breakers come with back connected
terminations. Optional front flat terminations are available. See page 40.
•
P type circuit breaker available only in 3-pole.
Digit 7 – Spring Charging Motor
Spring Charging Motor (EO)
Code
DC
24/30Vdc
A
48Vdc
B
60Vdc
C
72Vdc
D
110/130Vdc
E
250Vdc
F
AC
48Vac
G
120Vac
H
240Vac
J
277Vac
K
Blank/none*
X
*An "X" (Blank/None) denotes a Manually Operated device (MO) Spring
Charge Contact, GSCC1, included with all Motor Operators.
•
When a Spring Charging Motor is selected, a Closing Device must be
selected from Closing Devices for Digit 8, and a Shunt Trip Device must
be selected from Shunt Trip 1 Devices for Digit 9.
•
Shunt Trip 1 with a coil voltage different from the Spring Charge Motor
may be user-selected.
Digit 8 – Closing Devices
Closing Coil Type
Code
Closing Coil
(CC)*
24Vdc
A
30Vdc
B
48Vac/dc
C
60 – 72Vdc
D
110Vdc/130Vdc; 120Vac
E
208Vac
F
220Vdc; 240Vac
G
250Vdc; 277Vac
H
Command
Operated
Closing Coil
(CCC)**
24Vdc
M
30Vdc
N
48Vac/dc
P
60 – 72 Vdc
Q
110Vdc/130Vdc; 120Vac
R
208Vac
S
220Vdc; 240Vac
T
Blank/none
X
*The Closing Coil (CC) permits either local or remote release of the spring
charged closing mechanism by electrical operation.
**The Command Operated Closing Coil (CCC) includes an additional
anti-pumping safety feature to ensure that the electrical closing signal
must be released before further closure is attempted, a shut off is
initiated if the closing signal is maintained.
•
Manual button through breaker cover is included as standard
assembly.
•
When a Spring Charging Motor is selected (Digit 7), a Closing Device
must be selected from Closing Devices for Digit 8, and a Shunt Trip
Device must be selected from Shunt Trip 1 Devices for Digit 9.
•
SELECT ONE DEVICE ONLY.
Digit 9 – Shunt Trip 1
Extended Range Shunt Trip (ANSI/UL)*
Code
24Vdc
M
48Vac/dc
P
70 – 72Vdc
Q
110/125Vdc; 120Vac
R
208Vac
S
220Vdc; 240Vac
T
250Vdc; 277 Vac
V
Blank/none
X
*The Extended Range Shunt Trip is specifically intended and required
for UL ANSI Ground Fault applications. The pick up range is 55-110%
of the ST coil voltage.
•
When a motor is selected from the Spring Charging Motor (Digit 7)
a Shunt Trip 1 must be selected.
•
SELECT ONE DEVICE ONLY.