![GE EntelliGuard AKR-30-800 Installation Manual Download Page 26](http://html.mh-extra.com/html/ge/entelliguard-akr-30-800/entelliguard-akr-30-800_installation-manual_122812026.webp)
25
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH41549 R05
Figure 12. Modify Bracket
Steps for removing the bracket pin:
1.
Remove the left bracket assembly (75C149309G061) from the compartment (
Figure 12
). The assembly is
bolted to the side sheet. Remove (4) ¼-20 thread forming screws using a socket wrench and 3/8” hex
socket.
2.
Remove the pin from the bracket (75A106208P204). The pin is riveted from the inside and has to be
drilled from the same side. Removing the bracket is necessary.
3.
Note that the assembly must be done by a trained service technician only.
4.
Apply corrosion resistance treatment to the exposed metal after removing the pin.
5.
Reassemble the bracket assembly and scrap or discard the pin. Torque ¼-20 thread forming screws to
85 in-lb.
Install AKD-8 (800-2000A) Retrofill Breaker
•
It must be ensured that the supply power to
the compartment is turned off/
compartment is de-energized for all the
incoming and outgoing circuits of the LVS
prior to any work being conducted on it.
•
During the installation and related work on
the equipment, it must be ensured that the
operator is using the prescribed PPE for the
specified tasks.
•
Ensure only qualified personnel install, operate, service, and maintain all electrical
equipment.