Operations and Maintenance Manual
E4H Series Water Purification Machine
25
24.
Connect the permeate line to the point of use of the permeate. Check for leaks and
ensure that you have no kinks in hoses, or blockage of any piping on the permeate
and concentrate outlet lines.
25.
Make any necessary final adjustments to flows and pressure according to step 17.
26.
NOTE: The membrane(s) in your machine are rated for certain flow rates at 77ºF
(25ºC). Maximum flow rates are achieved when the membranes have been
completely rinsed and on-line for at least 24 hours.
27.
Record all operating parameters at initial startup on a log sheet. A start up data log
sheet is included in section 9.3 of this manual.
28.
A daily log sheet, which includes general operating conditions (pressures, flows,
concentrations, pH, and pretreatment conditions), and routine or special
maintenance (flushing or cleaning as needed) must be kept . This log sheet will be
required by GE Water & Process Technologies if a warranty question arises.